The nec defines nickel cadmium battery nominal voltage at how much Per cell
1.2 V
The battery that Uses lead dioxide for the positive plate and sponge lead for the negative plate is the nickel cadmium type of battery. True or false
Faults
Nickel cadmium batteries provide backup power for what percentage of substations
Five
When a substation DC system charger is supplying a trickle charge to maintain a pre determined voltage level to a bank of batteries, it is called what type of charge
Float
The reason for ventilation in a substation battery Room is to avoid the potential buildup of what gas
Hydrogen
DC power used to operate switch gear and a substation is an example of what type of load
Momentary
According to IED standard for 85, the load supplied by a bank of substation batteries must be divided into how many types
Three
Lead acid batteries used in a substation battery Room are normally rated at how many votes each
To
N FPA 70E requires ventilation to ensure the concentration of free hydrogen gas inside a Room where batteries are contained does not exceed 1%. True or false
True
What type of battery is sealed, when the exception of a valve that opens automatically to relieve excessive internal pressure
Vibrate related
Supervisory control and data acquisition is an example of what type of load that is supplied by a bank of batteries when there is substation outage
continues
What osha standard requires water facilities to be provided within the work area for immediate emergency use when working with substation batteries
1910.151 C
The regulation that osha refers to for personal protective equipment that shall be available to employees performing battery maintenance is N FPA 70E what
320.8
Common nominal voltages for a bank of substation batteries are a hunderd 20 V DC, 240 V DC, and what
48 V DC
The industry standard for substation battery States that they must have a duty cycle of how long when no recharging is available?
8 hours
A good neutralizer for battery acid is what
Baking soda
95% of the complete storage capacity of a substation battery bank should be replaced by its charger in not more than how many hours
Eight
April detective apron is not required when working with nickel cadmium substation batteries. True or false
False
The substation battery charger is connected to the negative terminal of the 1st cell. True or false
False
A battery Room ventilation system is an example of what type of load that the batteries must be able to support in case of an outage
Non continuous
All tools used to work on a bank of batteries must be what and equipped with handles insulated from max volt
Non sparking
Substation batteries are charged by direct current using an AC to DC what
Rectifier
If a battery has a crazed container, it means it has what which usually occurs in the corners of the battery
Small spiderweb fractures
Spent batteries must be sent to a battery manufacturer or approved recycler, according to who
rcra