NEC 230.71 permits not more than ____ disconnects to serve as the building disconnecting means

6

In the United States, ____ Hz is standard or the fundamental frequency

60

If the selected OCPD has a rating greater than 100-amperes, the conductors to be installed shall be selected from either the 75 degrees Celsius or ___ degree Celsius column of NEC table 310.15(b)(16)

90

____ wire is seldom used to branch circuits, but because of weight and cost factors, it is frequently selected for feeders and services

Aluminum

Most fluorescent lamps with energy savings ballasts, compact fluorescent lamps (CFLs), LEDs, and halogen lamps meet the high-efficacy requirement. ______ do not.

Conventional incandescent lamps

A Toxicity Characteristic Leaching Procedure rating means that the lamp has passed ____ tests regarding the toxicity of the lamp

EPA

The ___ program includes such things as replacing old style magnetic ballasts with high-efficiency electronics ballasts, controlling lighting with timers and occupation sensors, and replacing low-efficiency appliances with high efficiency appliances

Energy Star

On a transformer the primary connections are done to the ____

The H termination points

____ is the ability of the lamp to portray objects as normally as possible

The color rendering probability

Recessed luminaires are usually supported by ____ that are attached to the luminaires' rough-in box

adjustable rails

The feeder overcurrent protection is sized for the ____ of the feeder conductor

ampacity

The photocell control device of a light-sensitive cell and a(n) ____ that increases the signal until it is sufficient to operate a relay that controls the light

amplifier

NEC 110.16 has requirement for placing a notice on certain equipment to warn qualified persons of the serious hazard of ____ flash events

arc

On lighting controlled by timers, an ____ feature is extremely desirable because it provides sunset ON and sunrise OFF that change automatically day by day as the sunrise and sunset times change every day.

astronomic

For fluorescent and HID luminaires, the volt-ampere allowance is based on the rating of the ____

ballast

On a three phase 208/120v panel circuit 37 would be what color

black

In an inductive circuit with an uncorrected power factor of 40 percent to 60 percent, the power factor can be corrected to within 5 percent of unity by the addition of a(n) ____

capacitor

In the insurance office, a reception area is provided with a(n) ____ to provide a different "look" for the clients

combination lighting system

NEC 422.13 requires that the branch circuit for a storage-type electric water heater with a capacity of 120 gallons (450 L) or less is considered to be a(n) ____ load

continuous

the ampacity is the allowable ampacity multiplied by the ____ factor

derating

____ fuses are designed to withstand motor-starting inrush currents and will not open needlessly

dual-element, time delay

In the insurance office, a separate, insulated-grounding conductor in installed with the feeder circuit and is connected to the neutral conductor at the service. This grounding system reduces, if not eliminates the ____ that often is (are) present in the conventional grounding system.

electromagnetic interference

The sump pump motor is protected by a manual motor starter and is controlled by a ____

float

Color selection for ungrounded "hot" conductors can be just about any solid color except green, white, gray, or any color conductor(except ___) that has three continuous white stripes.

green

____ are multiples of a fundamental frequency

harmonics

Today's liquid filled transformer have their windings immersed in highly refined mineral oil(combustible), siliconefluid, edible seed oilbased delectric coolant, or other acceptable nontoxic liquids that have ____ properties

high dielectric

For most applications, the motor circuit switch for a motor must be

horsepower rated

The temperatures of an electrical arc, such as might occur on a 480Y/277-volt solidly grounded, wye connected system, are ____

hotter than the surface of the sun

The lower the ____ of the grounding path, the greater the ground-fault current

impedance

The luminaire installed for the stairway to the second floor and hallways of a commercial building are ____ when the building is occupied because those spaces have no windows

in continuous operation

In the plans for the commercial building, high-efficiency energy-saving fluorescent lighting and LED lighting is used.Very few ____ are used

incandescent lamps

The grounding terminal of each of the receptacles in a computer room is connected to a(n)

insulated equipment grounding conductor

Dry-type transformer are widelt used because they are ____ than comparably rated liquid-filled transformers

lighter in weight

To determine reasonable minimum size for a neutral conductors, two types of loads must be considered- ____

linear and nonlinear

The circuit directory gives the "____" in a wording that would be clear for "nonelectrical" people to decipher and identify the circuit number for luminaries, receptacles, appliances, or equipment

load/area

The two basic methods of metering are primary high-voltage metering and ____

low-voltage metering

____ is the amount of light received in a unit of time on a unit area at a unit distance from a point source of one candela

lumen

In general, panelboards are constructed so the ____ run vertically for nearly the height of the panelboard

main feed busbars

For a fluorescent lamp, the inside of the tube is coated with a phosphor (a fluorescing material) air is evacuated, and an inert gas plus a small quantity of ____ is released into the tube

mercury

The reason the code uses the term ____ instead of motor is that, in many instances, the motor is inside an enclosure and is out of sight until an access panel is removed

motor location

A(n) ____ branch circuit must supply only line-to-neutral loads if the luminaires are connected line-to-neutral

multiwire

When you are wiring the primary side of a transformer, do you need to bring a grounded conductor to the transformer.

no

on a 3-phase, 4-wire, wye system, ____ reduction is allowed for nonlinear loads

no

Three separate neutral conductors are installed to reduce the possibility of a conductor overheating from ____ currents

nonlinear

When sizing feeder conductors____ noncoincident loads (loads unlikely to be operated simultaneously such as the air-conditioning and the heating) need be included

only the larger of any

The connection scheme has the advantage of being able to provide either 3-phase or 3-phase and single phase power using only two transformers

open delta

The circuit to the circulating pump will be supplied from the ____ so that the water will continue to circulate if the utility power fails.

optional standby power panel

What color is the hi leg in a delta transformer hook up

orange

in a commercial building, it is the ____ responsibility to provide power for the elevator; illumination for the public areas such as hallways, stairways, and publics toilet rooms; and heat for the common areas of the building.

owner's

separate feeders are to be run from the main service equipment to each of the area of the commercial building. Each feeder will terminate in a ____, which generally will be installed in the area to be served.

panelboard

In lamp designations PAR means

parabolic reflector

NEc 310.8 set forth requirement for installing ____ conductors. there requirements intended to ensure the conductors will share the current equally to prevent overloading individual conductors

parallel

Incandescent, open, or ____ lamps in lampholders; and pendant lampholders are not permitted in clothes closets

partially open

GFPE monitors are designed to sense ____ faults only.

phase-to-ground

GFCI protection can be attained using GFCI circuit breakers or GFCI ____

receptacles

Recessed luminaries have to be securely fastened to the ceiling framing members using bolts, screws, or ____.

rivets

The installation of luminaries, lighting outlets. and supports is covered in Article 410 of the NEC Article 410 set forth the basic requirements for the installation, commonly referred to as the "____".

rough-in

The reasoning for identifying the system voltage(s) and phases is ____

safety

A motor may be loaded continuously up to the horsepower obtained by multiplying the rated horsepower by the ____

service factor

The ____ is defined in NEC Article 100 as the point of connection between the facilities of the utility and the premises wiring

service point

LED lighting could be called "____ lighting"

solid-state

NEC 250.64(C) states that grounding electrode conductors generally are not permitted to be____

spliced

The ____ is an example of equipment that is operated by an automatic control system

sump pump

____ that have the light source completely enclosed are permitted in clothes closet

surface-mounted or recessed fluorescent luminaires

The ____ feature of the receptacle provides protection from lightning and other severe electrical surges that may occur in the electrical system

surge protection

____ means the difference between motor winding temperature and the ambient temperature

temperature rise

Throughout this country, and for that matter, throughout the world, ____ is(are) the common reference point for all electrical systems

the earth

If the ampacity of a feeder does not match a standard OCPD rating, then ____ be used.

the next higher standard rating may

Currents of the 3rd harmonic and odd multiples of the 3rd harmonic(9th, 15th, 21st, etc.) add together in the common neutral conductors of a 3-phase system,instead of cancelling each other. These odd multiples are referred to as

triplens

To get accurate current readings where harmonics are involved, ammeters referred to as "____"

true rms

The light-producing element in the incandescent lamp is a ____ wire called the filament

tungsten

____ is the most common cause of motor failure

unbalanced voltage

For every ____ degree Celsius rise above the motor's rated temperature, the motor's insulation life is cut in half

10

In three-phase motors ,each phase is ___ degrees out of phase (symmetrical) with the other phases.

120

NEC 430.24 requires that the conductors supplying several motors, or a motor(s) and other load(s), shall have an ampacity not less than ____ percent of the full-load current rating of the highest rated motor

125

What is the minimum starting current for a 240 volt, 3-phase, Code letter J, 7-1/2 horsepower motor.

128 amperes

A washer-dryer rated for 4000 VA at 208Y/120 volts single-phase must have a branch-circuit ampacity of at least ____ amperes

20

NEC 408.36(A) stipulates that if the panelboard contains snap switches with a rating of ____ amperes or less, the panelboard overcurrent protection is not permitted to exceed 200 amperes.

30

An appliance is rated at 4500 volt-ampere, 240 volts. What is the maximum size fuse permitted?

30-ampere

A fluorescent lamp with a 30 in its nomenclature indicates it produces light with a color temperature of ____ K, which would provide good rendition to warm colors.

3000

The minimum size conductors, if all terminals are rated 75 degrees Celsius or higher, is ____ AWG as the allowable ampacity in NEC Table 310.16(B)(16) is 85 amperes

4

Often the load is such that parallel conductors should be considered. This usually occurs with loads over ____ amperes

400

____ occur when an ungrounded "hot" conductor comes in contact with a grounded surface or grounded equipment.

Ground faults

____ lamps have the lowest efficacy of the HID family, which ranges from 30 lumens per watt for the smaller wattage lamps to 65 lumens per watt for the larger-wattage lamps

Mercury vapor

Utilities make up the connections on the line side and load side of their transformers according to the ____ requirements

NESC

On a three phase 480Y/277 panel, circuit 22 would be what color?

Red (purple)

Multiwire branch circuits are defined in NEC Article 100 as a branch circuit that consists of two or more ____ conductors that have a voltage between them, and a grounded conductors that has equal voltage between it and each ungrounded conductor of the circuit and that is connected to the neutral or grounded conductor of the system.

ungrounded

When tabulating materials, take special note of long runs of raceway or cable and determine whether ____ is a problem. this can mean an increase in conductors and/or raceway size.

voltage drop

It is necessary that the illumination of a building comply with energy codes. These codes usually evaluate the illumination on the basis of the average ____ per square foot (meter) of illumination load.

watts

Conductors for 4800Y/277- volt systems are generally brown, orange, ____ for the ungrounded conductors and gray for the grounded conductor

yellow


Conjuntos de estudio relacionados

Economics - 4.1.2, 4.1.3, 4.1.4 - Trade - A Level

View Set

Physci 167- Chapter 6: obesity-associated common diseases of western civilization, diabetes, heart disease and cancer// chapter 7- biology of food choice and addition, hidden clues.

View Set

Computer Worms and Viruses / Internet Basics

View Set

Unit 2: Airplane Instruments, Engines, and Systems

View Set

SCM Forecasting & Demand Planning

View Set