Each motor used in a continuous duty application and rated more than 1 hp shall be protected against overload by a separate overload device that is responsive to motor current. The overload device for motors with a marked temperature rise 40°C or less, shall be rated at no more than _____ percent of the motor nameplate full-load current rating. 80 115 125 175
125
Branch-circuit conductors supplying a single continuous-duty motor shall have an ampacity not less than _____ rating. 125 percent of the motor's nameplate current 125 percent of the motor's full-load current rating as determined by 430.6(A)(1) 125 percent of the motor's full locked-rotor 80 percent of the motor's full-load current
125 percent of the motor's full-load current rating as determined by 430.6(A)(1)
Conductors supplying several motors shall not be sized smaller than _____ percent of the full-load current rating of the highest rated motor, plus the sum of the full-load current ratings of all other motors in the group, plus the ampacity of other loads. 80% 100% 125% 150%
125%
The maximum dual-element time-delay fuse branch circuit protection for a single-phase motor is _____ percent of the appropriate current rating found in Table 430.248. 125 150 175 225
175
The maximum rating or setting of an inverse time breaker used as the motor branch-circuit short-circuit and ground-fault protective device for a single-phase motor is _____ percent of the full-load current given in Table 430.248. 125 175 250 300
250
Motor control circuit conductors that extend beyond the motor control equipment enclosure shall have short-circuit and ground-fault protection sized not greater than _____ percent of the value specified in Table 310.16 for 60°C conductors. 100 150 300 400
300
Overcurrent protection for motor control circuits shall not exceed _____ percent if the conductor is based on Table 310.17 and does not extend beyond the motor control equipment enclosure. 100 150 300 400
400
Article _____ covers motors, motor branch-circuit and feeder conductors and their protection, motor overload protection, motor control circuits, motor controllers, and motor control centers. 410 430 440 450
430
For stationary motors of 2 hp or less and 300V or less on ac circuits, the controller can be an ac-rated only general-use snap switch where the motor full-load current rating is not more than _____ percent of the rating of the switch. 50 60 70 80
80
The maximum instantaneous trip breaker branch circuit protection for a single-phase motor is _____ percent of the appropriate current rating found in Table 430.52. 175 225 300 800
800
A motor disconnecting means can be a listed _____. molded case circuit breaker motor-circuit switch rated in horsepower molded case switch any of these
ANY OF THESE
Circuit conductors on the output of an adjustable-speed drive system are susceptible to breakdown under certain conditions. Factors affecting the conductors include but are not limited to the output _____. voltage frequency current any of these
ANY OF THESE
Conductors supplying several motors, or a motor(s) and other load(s), shall have an ampacity not less than the sum of 125 percent of the full-load current rating of the highest rated motor plus the sum of the full-load current ratings of all the other motors in the group and 100 percent of the remaining noncontinuous and continuous nonmotor loads. T/F
False
In determining the highest rated motor for purposes of complying with 430.24, 430.53(B), and 430.53(C), the highest rated motor shall be based on the rated full-load current as selected _____. from the motor nameplate from Tables 430.247, 430.248, 430.249, and 430.250 by multiplying the horsepower by 746 watts using the largest horsepower motor
From Tables 430.247, 430.248, 430.249, and 430.250
If a motor disconnecting means is a motor-circuit switch, it shall be rated in _____. horsepower watts amperes locked-rotor current
HORSEPOWER
For general motor applications, the motor branch-circuit short-circuit and ground-fault protection device shall be sized based on the _____ values. motor nameplate NEMA standard NEC Table Factory Mutual
NEC Table
A branch-circuit overcurrent device can serve as the disconnecting means for a stationary motor of 1/8 hp or less. True/False
TRUE
Circuit conductors on the output of an adjustable-speed drive system are susceptible to breakdown under certain conditions due to the characteristics of the output waveform of the drive. True/False
TRUE
Motor control circuits shall be arranged so they will be disconnected from all sources of supply when the disconnecting means is in the open position. True/False
TRUE
Where the motor short-circuit and ground-fault protection devices determined by Table 430.52 do not correspond to the standard sizes or ratings, a higher rating that does not exceed the next higher standard ampere rating shall be permitted. True/False
TRUE
Where more than one motor disconnecting means is provided in the same motor branch circuit, at least one of the disconnecting means shall be readily accessible. True False
True
A motor can be provided with combined overcurrent protection using a single protective device to provide branch-circuit _____ protection where the rating of the device provides the overload protection specified in 430.32. short-circuit ground-fault motor overload all of these
all of these
Part IV of Article 430 specifies devices intended to protect _____ against overcurrent due to short circuits or ground faults. motor branch-circuit conductors motor control apparatus motors all of these
all of these
A horsepower-rated _____ having a horsepower rating not less than the motor rating shall be permitted to serve as the disconnecting means. attachment plug and receptacle flanged surface inlet and cord connector automatic controller attachment plug and receptacle or flanged surface inlet and cord connector
attachment plug and receptacle or flanged surface inlet and cord connector
A _____ rated in amperes shall be permitted as a controller for all motors. branch-circuit inverse time circuit breaker or molded case switch dual-element time-delay fuse snap switch GFCI protected device
branch-circuit inverse time circuit breaker or molded case switch
A _____ shall be located in sight from the motor location and the driven machinery location. controller protection device disconnecting means all of these
disconnecting means
Overload devices are intended to protect motors, motor control apparatus, and motor branch-circuit conductors against _____. excessive heating due to motor overloads excessive heating due to failure to start short circuits and ground faults excessive heating due to motor overloads and excessive heating due to failure to start
excessive heating due to motor overloads and excessive heating due to failure to start
An individual disconnecting means shall be provided for each motor controller and be located _____ from the controller location. in sight within 3 ft within 10 ft within 25 ft
in sight
A feeder supplying fixed motor load(s) shall have a protective device with a rating or setting _____ branch-circuit short-circuit and ground-fault protective device for any motor in the group, plus the sum of the full-load currents of the other motors of the group.
not greater than the largest rating or setting of the
The motor controller shall have horsepower ratings at the application voltage _____ the horsepower rating of the motor. not lower than not higher than equal to six times
not lower than
Motors shall be located so that adequate _____ is provided and so that maintenance, such as lubrication of bearings and replacing of brushes, can be readily accomplished. space ventilation protection all of these
ventilation