Motors 2 Level 9

¡Supera tus tareas y exámenes ahora con Quizwiz!

What is the minimum horsepower motor-circuit switch rating for a 40-horsepower, 460-volt, 3-phase motor marked with a code letter F using the maximum locked-rotor rating?

40HP

What is the minimum current rating of the motor disconnecting means for a 40-horsepower, 208-volt, 3-phase squirrel-cage motor?

131A

What is the minimum horsepower rating for a motor disconnecting means for a 50-horsepower, 440-volt, 3-phase motor marked with a code letter S using the maximum locked-rotor rating?

200HP

Calculate the minimum horsepower rating of the switch from the previous question.

20HP

A motor disconnect switch is to be installed for a 40-horsepower, 3-phase, 460-volt, Design C motor with a code letter L. Calculate the minimum ampacity for the disconnect switch.

59.8A

What is the minimum current rating of a motor disconnecting means for a 50-horsepower, 3-phase, 440-volt, synchronous motor?

59.8A

A circuit breaker is listed for use as a disconnecting means because it is tested for an interrupting rating of ? times the current rating of the breaker.

6

What is the minimum horsepower rating for a motor disconnecting means for a 50-horsepower, 440-volt, 3-phase motor marked with a code letter F using the maximum locked-rotor rating?

60HP

Calculate the minimum horsepower rating of the motor disconnect switch from the previous question.

7.5HP

What is the minimum horsepower rating of the motor circuit switch for a single-phase, 240-volt 5-horsepower motor marked with code letter M using maximum locked-rotor kVA (kilovolt-ampere)?

7.5HP

A 12-kilowatt, 240-volt, single-phase heater and a 5-horsepower, 240-volt, single-phase motor are to be controlled by the same motor circuit switch. The motors can be started simultaneously.

89.7A

One 5-horsepower motor and one 10-horsepower motor, both continuous-duty, 460-volt, 3-phase, are to be installed on the same 480-volt motor circuit. The motors can be started simultaneously.

24.84A

What is the average locked-rotor current for a 20-horsepower, 240-volt, single-phase motor with code letter H?

557.9A

What is the minimum horsepower rating of the motor circuit switch for a 3-horsepower, 115-volt, single-phase motor marked with code letter G using maximum locked-rotor kilovolt-ampere?

3HP

What is the minimum standard size inverse-time circuit breaker that can be used as a disconnecting means for a 25-horsepower, 240-volt, 3-phase motor?

80A

What is the minimum horsepower rating of the motor circuit switch for a 3-phase, 240-volt, 5-horsepower motors marked with code letter M using maximum locked-rotor kVA (kilovolt-ampere)?

10HP

What is the maximum locked-rotor current for a 15-horsepower, 208-volt, 3-phase motor with code letter D?

187.17

What is the maximum locked-rotor current of a 125-horsepower, 460-volt, 3-phase motor with code letter R?

2511.62A

What is the minimum horsepower rating for a motor disconnecting means for a 50-horsepower, 440-volt, 3-phase motor marked with a code letter B using the maximum locked-rotor rating?

40HP

A 40-horsepower, 3-phase, 60-hertz, 460-volt motor is installed with a motor nameplate full-load current rating of 60 amperes, a temperature rise of 40°C, the locked rotor code letter F, and a service factor of 1.15. The motor is a continuous-duty squirrel-cage motor and starting current is not a problem. Calculate the maximum branch-circuit short-circuit and ground-fault protection using time-delay fuses for this motor. Calculate the maximum overload relay protection for this 40-horsepower, 460-volt, 3-phase motor. Calculate the minimum current rating of the motor disconnect switch controlling this motor.

65A 100A 75A 59.8A

A motor switch is to be installed for a 40-horsepower, 3-phase, 460-volt, Design C motor with code letter L. Calculate the minimum horsepower rating of the switch using the maximum locked rotor kVA (kilovolt-ampere).

75HP

What is the minimum current rating of the motor disconnecting means for a 7.5-horsepower, 115-volt, single-phase motor?

92A