NEC 320, 330, 334, 336, 338
Type SE cables shall be permitted to be used for branch circuits or feeders where the insulated conductors are used for circuit wiring and the uninsulated conductor is used only for _____ purposes.
(none) >WRONG<
Type NM and Type NMC cables shall be permitted in _____, except as prohibited in 334.12.
1 and 2 family dwellings & garages/storage buildings, Structures and multifamily dwellings permitted to be of types III, IV and V construction
For interior installations of Type SE cable with ungrounded conductor sizes _____ AWG and smaller, where installed in thermal insulation, the ampacity shall be in accordance with 60°C (140°F) conductor temperature rating.
10
Where Type TC-ER cable is used to connect a generator and associated equipment having terminals rated _____ or higher, the cable shall not be limited in ampacity by 334.80 or 340.80.
75 degrees celcius
Type _____ cable is a fabricated assembly of insulated conductors in a flexible interlocked metallic armor.
AC
Type SE cable shall be permitted to be used as _____ in wiring systems where all of the circuit conductors of the cable are of the thermoset or thermoplastic type.
Branch Circuits or Feeders (or neither?)
Type AC cable is permitted in _____.
Cable trays and exposed installations
True or False: Type NM cables shall not be used in one- and two-family dwellings exceeding three floors above grade.
False
Type USE cable is not permitted for _____ wiring.
Interior
Type _____ cable is a factory assembly of insulated circuit conductors within an armor of interlocking metal tape, or a smooth or corrugated metallic sheath.
MC
Type _____ cable is a factory assembly that encloses two or more insulated conductors within a nonmetallic jacket.
NM
Type _____ cable is an assembly primarily used for services.
SE
Type _____ cable is a factory assembly of two or more insulated conductors, with or without associated bare of covered grounding conductors, under a nonmetallic jacket.
TC
True or False: Type SE cable can be used for interior wiring as long as it complies with the installation requirements of Part II of Article 334, excluding 334.80.
True
True or False: Type TC cable can be used in one- and two-family dwelling units.
True
True or False: Type TC-ER cable used for interior wiring in one- and two-family dwelling units that is suitable for pulling through structural members is marked "TC-ER-JP."
True
True or False: Type USE cable used for service laterals shall be permitted to emerge from the ground if terminated in an enclosure at an outside location and protected in accordance with 300.5(D).
True
True or False: Where Type TC cable is installed in one- and two-family dwelling units, 725.136 provides rules for limitations on Class 2 or 3 circuits contained within the same cable with conductors of electric light, power, or Class 1 circuits.
True
Type _____ cable is a multiconductor assembly identified for use as underground service-entrance cable.
USE
Armored cable shall not be installed _____.
Where subject to damage, Damp or wet locations, and Corrosive conditions
Type MC cable shall not be used under which of the following conditions?
direct buried unless identified for the purpose, exposed to corrosive conditions, and where subject to physical damage
Type TC cable can be used _____.
for power, lighting, control, and signal circuits,for Class 1 control circuits as permitted in Parts II and III of Article 725, and in cable trays including those with mechanically discontinuous segments up to 1 ft
Type TC cable shall be permitted to be direct buried, where _____ for such use.
identified
Type TC cable shall not be _____.
used where exposed to direct rays of the sun, unless identified as sunlight resistant, installed where it will be exposed to physical damage, or installed outside of a raceway or cable tray system, unless permitted in 336.10(4), 336.10(7), 336.10(9), and 336.10(10)