What size copper feeder 90 degrees Celsius do you need for the following multiple motors 3 phase, 460 volt, 15HP-25HP-40HP?

#2

What size copper 75 degrees Celsius THHW wire do you need for the following multiple motors on 1 feeder 3 phase, 230 volt, 1 HP-5HP-10HP?

#6

What size copper 75 degrees Celsius THWN wire do you need for a 3 phase 208 volt 10 HP motor?

#8

What size copper 75 degrees Celsius XHHW wire do you need for a 3 phase 460 volt 25 HP motor?

#8

What size dual element fuse do you need for a 3 phase, 208 volt, 20 HP squirrel cage design B motor short circuit, ground fault protection?

100 amp

What size copper wire do you need for a 1 phase, 1 1/2 horsepower, 115 volt motor using 75 degrees Celsius XHHW insulation?

12

A continuous duty motor rated at more than 1 horsepower with a marked service factor 1.15 or greater, shall have an overload device rated at _________________.

125%

A single motor used in continuous duty shall have branch circuit conductors rated at not less than _____________________ motor full load current.

125%

Conductors supplying several motors shall have an ampacity of not less than ____________.

125% of largest motor full load amps plus all other motor full load amps

A thermal protector integral with the motor, that will prevent dangerous overheating, will be set at a trip value of ____________ for a motor full load current of 9 amps or less.

170%

The maximum rating or setting of a motor branch circuit, short circuit, and ground fault protective device for a single phase motor using time delay fuses.

175%

What size non time delay fuse do you need for a 40 amp wound rotor motor short circuit, ground fault protection.

60 amp

Conductors supplying a freight elevator with a duty cycle service of 15 minutes shall have an ampacity of ______________ motor full load current rating.

85%

Motors shall be located in an area so that _____________________.

adequate ventilation is provided lubrication of bearings can be accomplished replacing of brushes and belts can be accomplished

The power supply for a programmable logic computer must _________________.

charge internal batteries in case of power loss

In motor controls the letters - NO/NC are associated with ___________________.

contacts

A phase monitoring relay that shuts down a 3 phase motor if incoming power loses a phase is connected to ___________________.

control voltage

PLC's have push buttons, selector switches, joysticks, relay and starter contacts, pressure-flow-level-limit-photoelectric switches which are called ____________________.

discrete inputs

PLC's have lights, relays, solenoids, starters, alarms, valves, heating elements and motor which are called ___________________.

discrete outputs

A solenoid valve contains _______________.

electromagnet plunger with flow regulator valve

Which of the following is not a part of the four basic parts of a PLC?

machine section

Motor overload devices are intended to protect ___________________.

motors motor control apparatus motor branch circuit conductors

In motor controls, multiple start buttons are wired in __________________.

parallel

In motor controls, multiple stop buttons are wired in _________________.

series


Conjuntos de estudio relacionados

M9 Lectures (Healthcare Financing)

View Set

A6 Az emberi jogok nemzetközi védelme (források, intézmények) univerzális és regionális szinten

View Set

Krugman's Economics for AP Module 10-15

View Set

Riders Covering Additional Insureds

View Set

PrepU's Ch 32: Management of Patients with Immune Deficiency Disorders

View Set

Romeo + Juliet - key quotations & screenshots

View Set

RQ Chapter 8 - Quiz - commercial ref - 7/16/17

View Set