S-13 AND S-14 STANDPIPE SYSTEM
RECORDS SHALL BE ________ AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPARTMENT.
READILY
THE HOSE HOUSE SHOULD BE PAINTED ___________.
RED
WHEN POST INDICATOR VALVES (PIV) ARE INSTALLED, THE SHOULD BE PAINTED ____________.
RED
INTERIOR SIGNAGE SHALL HAVE A ________ BACKGROUND WITH 1 INCH HIGH __________ LETTERS.
RED, WHITE
VERTICAL PIPING IN STANDPIPE SYSTEMS ARE CALLED ____________.
RISERS
A FIRE DEPT. CONNECTION WAS FORMERLY KNOWN AS A ______________ CONNECTION.
SIAMESE
THE MEASUREMENT OF SYSTEM PRESSURE UNDER NON-FLOW CONDITIONS IS __________ PRESSURE.
STATIC
INTERIORS OF _________ TANKS SHALL BE INSPECTED EVERY 3 YEARS.
STEEL
QUICK OPENING DEVICES CONTAIN AN ___________ AND AN EXHAUSTER.
ACCELERATOR
QUICK OPENING DEVICES ARE AUTOMATICALLY ACTIVATED WHEN A DROP OF _________ PSI IN AIR PRESSURE IS DETECTED.
2
IF ENCLOSED IN A CABINET, THE HOSE RACK SHALL SWING OUT AT LEAST ____________.
90 DEGREES
A ____________ TEST REQUIRES AT LEAST TWO INDIVIDUALS.
FULL FLOW TRIP
__________ VALVES ARE USED TO SHUT DOWN PART OF THE SYSTEM WHEN CONDUCTING REPAIRS OR MAINTENANCE.
POST INDICATOR
HOSE MARKES "SUPPLY HOSE" SHALL NOT EXCEED __________ PSI.
185
THE DRY TYPE VALVE IS DESIGNED TO OPEN WHEN THERE IS A _________ OF AIR PRESSURE IN THE STANDPIPE.
DROP
__________ IS A DESIGNED SERIES OF BEAMS USED TO SUPPORT MECHANICAL EQUIPMENT.
DUNNAGE
THE WATER IN A WET STANDPIPE SYSTEM IS ALWAYS ___________.
UNDER PRESSURE
IT IS __________ TO INSTALL OR MAINTAIN FIRE PROTECTION SYSTEMS THAT HAVE THE PHYSICAL APPEARANCE OF FIRE EQUIPMENT BUT THAT DON'T PERFORM A FUNCTION.
UNLAWFUL
ONLY FDNY, OWNER, _________ OR __________ MAY PLACE A WHITE OR BLUE DISC ON A SYSTEM
MFSPC, MLP
__________ CHECK VALVES ARE NORMALLY USED IN SYSTEMS USING A GATE VALVE.
SWING
STANDPIPE SYSTEMS DESIGNED TO BE USED BY PROFESSIONAL FIRE FIGHTERS USING 2 1/2 INCH HOSE ARE CLASS __________.
1
THE DRY PIPE VALVE IS USUALLY SET TO TRIP AT _________ PSI ABOVE THE NORMAL TRIP LEVEL.
15-20
ACCEPTABLE AIR PRESSURE INSIDE AIR TANKS MAY VARY FROM ____________ PSI.
15-80
TO MAXIMIZE LIFE OF HOSE, IT SHOULD BE KEPT AT TEMPERATURES BETWEEN ________ AND ________.
32 DEGREES FAHRENEIT, 100 FAHRENHEIT
A PRESSURE RESTRICTING DEVICE SHALL BE INSTALLED AT HOSE OUTLETS WHERE STATIC PRESS. EXCEEDS ___________ PSI.
80
ROOF MANIFOLD HOSE OUTLETS MUST BE SET BETWEEN _________ INCHES ABOVE THE ROOF LEVEL.
18-60
STANDPIPE SYSTEMS DESIGNED TO BE USED BY OCCUPANTS USING 1 1/2 INCH HOSE ARE CLASS __________.
2
PRESSURE REDUCING DEVICES SHALL BE FLOW TESTED WITH A MINIMUM FLOWING DISCHARGE OF ___________ GPM
250
STANDPIPE SYSTEMS IN WHICH THE HOSE DIAMETER MAY BE ADJUSTED USING REDUCTER VALVES ARE CLASS ________.
3
FOR 1938-1968 HOSE OUTLET AND RELEASE RACKS, THE HOSE SHOULD BE KEPT BETWEEN __________ FT AND ___________ FT ABOVE THE FLOOR OR LANDING.
5, 6
SYSTEMS PARTIALLY OUT OF SERVICE ARE INDICATED BY A _________ DISC ON FDNY CONNECTIONS.
BLUE
STANDPIPE SYSTEMS ARE PIPES INSTALLED IN A BUILDING TO TRANSFER WATER TO ________________ CONNECTIONS LOCATED IN A BUILDING.
HOSE
PRIOR TO RETURNING A SYSTEM TO SERVICE, THE ____________ SHALL ENSURE THAT THE NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
IMPAIRMENT COORDINATOR
IN ABSENCE OF A SPECIFIC DESIGNEE, THE BUILDING OWNER SHALL BE CONSIDERED THE _____________.
IMPAIRMNENT COORDINATOR
CHECK VALVES SHALL BE INSPECTED ___________ EVERY 5 YEARS.
INTERNALLY
IN AN OS&Y VALVE, IF THE STEM IS RAISED ABOVE THE CONTROL WHEEL THE VALVE IS ___________.
OPEN
IT IS THE RESPONSIBILITY OF THE ___________ TO MAINTAIN THE STANDPIPE SYSTEM.
OWNER
THE PRESSURE WITH WHICH WATER IS DISCHARGED FROM THE PUMP IS CALLED _____________.
TOTAL HEAD
THE SURGE IN PRESSURE WHEN A HIGH-VELOCITY FLOW OF WATER IS ABRUPTLY SHUT OFF IS KNOWN AS ____________.
WATER HAMMER.
WHEN THE PUMP IS OPERATING, A SMALL ___________ IS NOT CONSIDERED A MALFUNCTION.
WATER LEAK
SYSTEMS FULLY OUT OF SERVICE ARE INDICICATED BY A _________ DISC ON FDNY CONNECTIONS.
WHITE
EXTERIOR SIGNAGE SHALL HAVE A __________ BACKGROUND WITH 1 INCH HIGH ___________ LETTERS.
WHITE, RED