when installing control cables in a sub trench care should be taken that they

do not cross each other

when splicing a medium voltage cable the tape that is used on the conductor and over the insulation is

semi conducting

the ground grid in a distribution sub is typically made with_copper wire

1/0

Minimum clearance between energized lines and a crane or other equipment in a substation is

10'

the ground grid for a transmission sub is typically made from bare copper in a grid pattern with conductors spaced about_apart

10'

in outdoor subs the grid is buried_below subgrade

12-24"

the number of cap and pin units required in a string of suspension insulators for a 240kv line is typically

14

OSHA regulation part_covers construction in energized substations

1926

when bolting sub steel structures together the bolts are long enough when at least _threads are seen protruding

2

Hard hats worn by electrical workers are tested at

20kv

safety regulations require unqualified workers to add an additional_for every 10kv above MAD

4"

on the grout pouring side of a form a slanted delivery board at approximately_

45"

upon completions a concrete pour you should re check the

Anchor bolts for correct location

When building a collection pit for spill prevention in a sub the pit can be lined with

Bentonite clay

when assembling a sub structure al surfaces that will be in permanent contact with each other after assembly should be

Cleaned

The first most effective action after a spill is to

Contain the fluid before it seeps into water or soil

the most common bolted connection in a substation joins a conductor to an

Equipment terminal

in substations drawings letter are added to substation device numbers to

Further define the device

The size of a sub located at a generating plant is proportional to the

Generator output voltage

The part of the OSHA regulations that mandate each employee complies withal rules

Genral duty clause

OSHA initiates publice-private partnerships which identify_

Hazerd mitigations

if the electric field becomes concentrated in any one point of a cable_

Insulation

the following drawing is of_

Loadbreak switch

in order to properly torque aluminum bolts in a substation, the bolts must be properly

Lubricated

Any oiled full equipment stores within the sub fence must have a

Plastic container

To aid the curing process of a freshly poured concrete pad a

Plastic sheet that acts as a vapor barrier should be used

sub superstructure can be made of aluminum allow steel or

Precast concrete

the two functions of the glaze on a porcelain insulator are to help ead water and_

Shed dirt

To verify that the concrete being used on a substation foundation meets the Required consistency a ______ test should be performed

Slump

the type of insulator used in subs to support conductors and switch gear is the_type

Solid

At subs high voltage surges appear on the electrical strayed are shunted to ground by

Surge arresters

Sub stations without xfmr are called

Switchyard

aluminum substation buseds are welded using MIG or

TIG

A _________ is used to ensure that the anchor bolts are accurate

Template

install a_in each relay to isolate it from the test circuit

Test plug

when building a form around an area to be grouted the form for the grout can be made_

Water tight

A low resistant well designed and well constructed ground grid is necessary to provide improved

Worker Saftey

the bolts of a steel structure in a sub yard should be torqued

after all the bolts are set in place

when doing masonry work in a sub you should not let any grout touchyour skin grout can cause

alkali burns

the symbol below is used for a

bushing type current transformer

to determine size type and start point of a control cable run you should refer to the

cable schedule

after a high voltage test a cable is dangerous because it basically becomes

capacitor