Article 210 ( branch circuits)
Are not
15 and 20 amp 125 V receptacles located in patient bed locations of general care facilities ______ required to be GFCI protected
Wye-connected
A3 phase 4 wire, _____ Power system used to supply power to on-linear loads may necessitate that the power system design allow for the possibility of high harmonic current on the neutral conductor
12 inches
An outlet can be no lower than ____ below the counter to count as a required outlet.
25 feet
An outlet connected to the line side disconnect of heating refrigeration or air-conditioning equipment, shall be installed within ________ .
Alarm system
An unfinished basement outlet feeding an ______ does not require GFCI protection
6 feet
Appliance receptacle outlets must be within _____ of the intended location of the appliance.
Branch circuits
Article 210 deals with the requirements for______.
2 feet
As per the code book the definition of wall space is any space ____ or more in width.
80%
Cord and plug connected equipment not fastened in place must not have an ampere rating more than ____ of the branch circuit rating
Ungrounded
Each MULTIWIRE Branch circuit shall be provided with a means that will simultaneously disconnect all ______ conductors at the point where the branch circuit originates.
Within 6'
Laundry outlets located ____ of a sink require GFCI protection.
6'6"
The maximum height allowed an outdoor outlet can be to be part of the required outlets is ____
5% ( combo of 3%,2% on feeder or branch circuit )
The maximum voltage drop allowed by the NEC is ______.
True
True or false. all 15 and 20 amp 125 volt receptacles installed in crawlspaces at or below grade level of dwelling units shall have GFCI protection
660watts (of the admedium type ), 750 watts for others
A heavy duty lamp holder shall have a rating of not less than ____ we're connected to a branch circuit over 20 Amps.
12 inches
A receptacle outlet on a countertop ,shall be installed at each countertop space that is____ or wider.
Tamper resistant
All 125 volt , 15/20 amp receptacles that are part of a luminaire, located within cabinets, above 5'6", or is controlled by a wall switch must be listed _____
GFCI Protection
All 15 amp and 20 amp 125 V receptacles installed in bathrooms of all occupancies shall have _____ for personnel
GFCI protected
All outlets on kitchen countertops and installed in unfinished basements shall be______
Metal raceway
An arc fault circuit interrupter can be located at the first outlet to provide protection for the remaining portion of the branch circuit if it is installed in a _______
6 AWG or smaller
Equipment grounding conductor's sized _______ must have a continuous outer finish either green or green with one or more yellow stripes
18"
Floor receptacle outlets are not counted as the required receptacle if they are located more than _____ from the wall.
10 feet
Hallways in dwelling units that are _____ long or longer require a receptacle outlet.
Six
If the stairway between floors has ____ risers or more a wall switch must be located at each floor level.
120 volts
In DWELLING units the voltage between conductors that supply the terminals of luminaires and cord and plug connected loads of 1440 VA or less shall not exceed _____ nominal.
None
In NYC, how many receptacles are required on a balcony in a usable area LESS than 20 square feet.
3 feet
In dwelling unit bathrooms, a 125 V receptacle outlet must be installed within _____ from the outside edge of each bathroom basin.
Lighting circuits
In dwelling units , the voltage between conductors must not exceed 120 V when they supply ______ and cord and plug loads of 1440 VA or less.
Line to neutral loads
Multi wire branch circuits shall supply only ______ .
24 inches
On a countertop, receptacle outlets shall be installed so that no point along the wall line is more than_______ from a receptacle outlet in that space.
Countertop surfaces
Receptacles installed for ______ can't be used to meet the receptacle requirements for wall space.
18 inches
Show window outlets are to be installed within _____ of the show window
Branch circuits
The conductors between the final overcurrent device and the receptacle and lighting outlets are_____ .
5'6"
The maximum height allowed an indoor outlet can have to be considered part of required receptacle outlets is _____ .
5%. (4% feeder, 1% branch circuit)
The maximum total voltage drop on branch circuit conductors in a mixed use building in NYC is _______ .
Fire hazard
The purpose of arc fault circuit interruption is to protect against________.
Electrocution (personnel)
The purpose of ground fault circuit interruption is to protect people against ______ .
Branch circuit overcurrent devices
The rating of a branch circuit shall be determined by the rating of the _______ .
Electric clock
The receptacle connected to one of the dwelling unit small appliance branch circuit can be used to supply an ________
Multi wire branch circuit
The ungrounded and grounded conductors of each _____ shall be grouped by wire ties or similar means in at least one location within the panel board or other point of origination
20 amp
There shall be a minimum of one _______ branch circuit for laundry outlets.
3 VA
To determine the number of branch circuits required for general lighting and general use receptacles , multiply square footage times _____ to get total VA.
50%
Utilization equipment fastened in place shall not exceed ______ of the branch circuit rating.
Boathouse ( with boat hoists)
What structure requires all outlets installed to be GFCI protected?
Ungrounded
When more than one nominal voltage system exists in a building ,each _____ conductor of a branch circuit shall be identified by phase and system at all termination ,connection ,and splice points.
the point where the branch circuit originates
Where two or more branch circuits supply devices or equipment on the same yoke ,a means to disconnect simultaneously all ungrounded conductors that supply those devices or equipment shall be provided at _______ .
Two
______ or more 20 amp small appliance outlets shall be provided for a kitchen ,pantry ,or similar dining areas
Equipment grounding conductor
______ sized 4AWG Or larger can be permanently re-identified with green marking at the time of installation
20 inches
An outlet can be no higher than ____ above the counter to count as a required outlet
Manual override
In dwelling units, lighting outlets can be controlled by occupancy sensors that are equipped with a_______ that allows the sensor to act as a switch