Basic construction wiring

Pataasin ang iyong marka sa homework at exams ngayon gamit ang Quizwiz!

if replacing a 2-wire receptacle the replacement type may be a GFCI type but it must be marked _____

"no equipment ground"

notches on the top or bottom of joists shall not exceed ___ the depth of the joist and shall not be longer than ___ the width of the joists

1/6 the depth and 1/3 the width

When installing NM cable the cable must be strapped or stapled not more than ____ from a box or fitting

12 inches

branch circuit must be rated to how many amperes when serving two or more outlets

15, 20, 30, 40, or 50

will a GFCI receptacle still properly function without a grounding conductor?

Yes

what is a potential hazard of old knob and tube wiring

brittle rubber conductors from years of heat from luminares and extreme heat in the attic resulting in a potenital fire

what can happen because of Voltage Drop

can cause lights to dim and poor performance of appliances

is celsius or fahrenheit used when referring to the temperature rating of insulation

celsius

an exception to a GFCI requirement in an unfinished basement would be what?

if the receptacle serves a permanently installed fire alarm or burglar alarm system

unless run through horizontal holes or notches in studs and joists, the intervals between straps or staples must not exceed ____

4 1/2 ft

What range of the hot conductor will make the GFCI trip

4 to 6 milliamperes

Cuts or notches in nonbearing partitions shall not exceed ____ of the studs width

40%

Receptacles located more than _____ above the floor are not required to be TR type

5 1/2ft

Bored or drilled holes in any stud shall not be closer than ____ to the edge of the stud

5/8in

Utilization equipmemt fastened in place are not permitted to exceed what percent of the branch-circuit rating

50%

Any receptacle within _____ of a sink is required to have GFCI protection

6 ft

the rating of any one cord-and-plug-connected utilization equipment is not permitted to exceed what of the branch-circuit rating

80%

NM-B is rated to what temperature

90*C

problems arise in equipment when there is a _______

breakdown of insulation

cuts or notches in exterior or bearing partitions shall not exceed ____ of the studs width

25%

What is the maximum allowable voltage drop for feeders

3%

what is the maximum allowable voltage drop for branch circuits

3%

the word bathroom is defined in NEC Article 100 as an area including a

Basin with one or more of the following: A toilet, uringal, tub, shower, bidet, or similar plumbing fixtures.

All 125-volt, 15- and 20-ampere and 30-ampere receptacle outlets that are not part of the permanent wiring of the building and that will be used by the workers on the construction site must be ______

GFCI protected

what can result when the ungrounded conductor in the appliance comes in contact with the metal frame of the appliance

Insulation failure

is it okay to use AFCI and GFCI devices in series?

It is okay

Will a GFCI protect a person when they touch both circuit conductors at the same time

It will not protect them because it doesn't sense an imbalance

Can you staple flat nonmetallic-sheathed cables on edge?

NO never

Ampacity

The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating.

locations exposed to direct sunlight require to be listed or listed and marked as what

being "sunlight resistant"

Locations protected from weather and not subject to saturation with water or other liquids but subject to moderate degrees of moisture.

damp location

A location not normally subject to dampness or wetness. A location classified as dry may be temporarily subject to dampness or wetness, as in the case of a building under construction.

dry location

are AC systems from 50-1000 volts required to be grounded?

duh yes

What does the suffix "b" mean (ex. NM-B)

it means conductors have 90*C insulation

what is kcmil

one thousand circular mils

When arcing occurs between the black ("hot") and white grounded (neutral) circuit conductors, or between the black ("hot") conductor and ground, it is referred to as a "parallel" arc.

parallel arcs

When a conductor that is carrying current breaks or when a loose connection occurs, a "series" arcing fault is created. The current draw of the connected load is trying to jump across the opening created by the break or loose connection.

series arcs

rating of the overcurrent devices determines what

the rating of a branch circuit

All 15 and 20 ampere 125 and 250 volt nonlocking type receptacles installed in a damp or wet location are required to be listed as _____

weather resistant type

Installations underground or in concrete slabs or masonry in direct contact with earth; in locations subject to saturation with water or other liquids; and in unprotected locations exposed to weather.

wet locations

when is GFCI protection not required for an outdoor receptacle?

when it is not readily accessible and supplied by a dedicated branch circuit for snow melting or deicing equipment


Kaugnay na mga set ng pag-aaral

Chapter 21: Caring for Clients with Lower Respiratory Disorders

View Set

Chapter 1. The Cycles of the Sky

View Set

Smooth muscle is nonstriated involuntary muscle

View Set

Unit 3: The Respiratory System (Lesson 10)

View Set

FSE 1080 Funeral Law Chapter 16 study guide

View Set

Fundamentals PrepU Chapter 15: Evaluating

View Set