Hydronic heating midterm

Pataasin ang iyong marka sa homework at exams ngayon gamit ang Quizwiz!

How much pressure exerted at the bottom of a 28" tall column of water

1 psI

Secondary aquastats should be set.....

10 degrees F over primary no higher than 210

How do we find the required GPM for a hot water system

10 gpm per 10,000 btu output

A PVR is usually factory set to close one pressure rises to......

12 PSI

How much pressure is required to lift water 21 feet

13 pounds Height of system divided by 2.31 ft Plus 4

The aquastat should be set to open it

180-200 degrees F

Backflow preventers should be installed on any boiler installed after.....

1974

How many circuits are usually controlled by the circulator relay

2

At what pressure does a relief valve open on a hot water boiler

30 psi

Static pressure is caused by.....

Gravity

What type of motor is used in the taco zone valves we studied

Heat motor

Which type of thermostat is most commonly used for a boiler

Heating only T-Stat

Fill pressure is determined by

Height of the system

What is the purpose of the flux

Helps solder flow into the joint and seal joint up. helps keep copper clean

What is the required delta T

Hot water boilers 20 degrees F (on test) In real world 20 degrees F plus or minus 5 degrees F

Water is pulled into the eye of the....?

Impeller

Where is a QuickFill bypass installed

In fill line around the PRV

Where is a flue damper located

In the flue pipe above draft diverter

Turning the adjusting screw of a PRV clockwise will...

Increase the fill pressure

What is the purpose of the vent on some backflow preventers

It vents the water out of the boiler

Where is the best location to install a circulator

Just after the expansion tank "pumping away"

One possible disadvantage of a wet rotor circulator is

Limited capacity

What device protects a boiler against dry firing

Low water cut off

What device closes a white Rodgers three wire zone valve

Motor

Wet rotor circulators use water to lubricate the...

Motor bearings

A spring coupler is used to connect the...

Motor shaft to the pump input shaft of an oil lubricated circulator

What must be done to maintain a float type LWCO

Must be blown down regularly

What must be done before soldering copper tubing

Must be deburred, cleaned with plumber sanding cloth, and fluxed

What are two code requirements regarding a paddle type flow switch

Must be used on hot water systems. Must be used on a system where pump operates intermittently

Does the pump effect pressure at the point the expansion tank attaches to the system

No

What is the result of a waterlogged expansion tank

No room for expansion, system pressure rises, relief valve opens, water let out, cold water let in

Air circulating through a hot water hydronic system causes

Noise in the system

The contacts of a circulator relay are

Normally open

Which type of circulator is a B&G 100

Oil lubricated

Which type of circulator is physically larger

Oil lubricated

Name 2 common types of circulators used in hydronic heating systems

Oil lubricated and water lubricated "wet rotor pumps"

Where is the secondary aquastat installed

On the supply line from the boiler as close to the boiler as possible

Where can we find the direction of flow through the system

On the volute

Where is the best place to install an automatic air vent

On top of air separator

What is the advantage of pumping away

Overall system pressure rises the air bubble in the system are smaller this makes the task of removing dissolved air easier

Name two materials used to seal the threads of a pipe joint

Pipe dope , Teflon tape

Which device allows water to feed into the boiler if the boiler pressure drops

Pressure reducing valve

What is the purpose of the expansion tank

Prevents system pressure from rising as water is heated, provides extra space in system for expanding water

Which LWCO feeds electricity into the water

Probe type

What is the preferred method of testing a relief valve

Raise the system pressure above the relief set

Wet rotor circulators do not require

Regular maintenance, a coupling, no bearing assembly, do not need to be oiled

Which device is used to protect the boiler against high-pressure

Relief valve

What should be done with a leaking relief valve

Replace it

What causes an aquastat to open

Rise in temperature

What device is used as a back up to the aquastat

Secondary aquastat

The diaphragm expansion tank uses a flexible membrane to

Separate the air and water

What does the code book say "shall be done" to a relief valve

Shall be tested once a year

A white Rodgers three wire zone valve uses a

Single pole double throw

Why must the probe be kept clean

So it is functioning properly

Which type of flux should be used

Soldering flux

What is the purpose of the hole in the damper

Standing pilot systems

What is the purpose of the backflow preventer

Stop water in the boiler from flowing into potable water supply

Secondary aquastats are.....

Surface mounted switches

Air pressure in the diaphragm tank should be the same as

System pressure

Which terminals in the boiler wire to the end switch

T & T

How does a Honeywell zone valve operate

T-Stat closes calling for heat Zone valve drives the zone open End switch closes

What device can be connected to an air cushion tank to prevent recirculation of cool air saturated water to the system

Tank fitting

Which device in a motorized flue damper proves that the damper is open

The end switch

Which LWCO should never be used on a steam boiler

The flow switch

What device in the boiler is controlled by the flue damper

The gas valve

What component of a circulator moves the water

The impeller

Define pump head

The pumps ability to overcome the system friction and move the water

What device house the impeller

The volute

What device controls the operation of a zone valve

Thermostat

What is the purpose of the QuickFill bypass

To bypass pressure reducing valve

Why is it important to keep the system pressure higher

To keep the air bubbles in the system small doing this allows the air to move through the water instead of lodging in the top of the system. keeping pressure higher improves air separator

What is the purpose of a circulator

To move the water throught the boiler, piping, and radiator. A pump

Why should a tube be installed from the relief valve outlet

To route the water to our safe discharge location

Why should a vent tube be installed on the backflow preventer

To vent the water to a safe discharge location

If delta T is low this indicated that the rate of water flow is

Too fast

What is the lowest permissible water level in a boiler

Top of the lower gauge nut on a steam boiler

And if this cannot be done the valve should be tested by means of the......

Tri lever on top of relief valve

If air is not returned to the tank it will become

Water logged

What type of circulator is a taco 007

Water lubricated

A flow switch type LWCO is a switch that closes when.....

Water starts flowing through the system

When must a flew damper be open

When burners are lit

When does the end switch of a zone valve close

When zone valve is open

When is it recommended to use an automatic air vent

Whenever diaphragm expansion tank is being used

Where is the point of no pressure change

Where expansion tank meets the system

Air enters a hot water hydronic heating system

With the fill water

Can aquastats fail closed

Yes

What part of a zone valve is controlled by a thermostat

Zone valve motor

How can we control the temperature of different zones

Zone valves

What is potable water

drinking water

What type of solder is used primarily for copper tubing

95% tin 5% antim lead free

What is a pump flange

A connection point between the pump and system piping

What type of device is an automatic air vent

A float valve

What is a zone

A portion of building that we wanna heat or cool separately from the rest of the building

What type of switch is a float type LWCO

A switch that closes when water level rises

Code says there shall be no.....

Accumulation of rust or scale that could prevent the free operation of the valve

Installing the tank on the suction side of the circulator ensures that the circulator pressure will be

Added to the static fill pressure

Which expansion tank has the water and air in direct contact

Air cushion

Which expansion tank is the oldest type

Air cushion

Which tank will allow the air in the tank to be dissolved by the water

Air cushion

Which type of expansion tank is hung above the boiler

Air cushion

Name two common types of expansion tanks

Air cushion and diaphragm

What device can be used to return air to an air cushion tank

Air separator

What device controls the maximum temperature of the water in a hot water boiler

Aquastat

List four requirements when installing the tube on a relief valve

it must be routed to floor or a safe discharge. Must be same size as outlet of the relief Has to be installed so cannot be capped Must be made of metal

Where should manual air vents be installed

At the radiators in the highest point of the system

What devices should always be used on a system with a diaphragm tank

Automatic air vent

What is the first device that should be installed in the fill line

Backflow preventer

Name three parts found in a fill line

Backflow preventer Pressure reducing valve Quick Fill bypass

Which of the three parts in the fill line is required by code

Backflow preventer and PRV

Which part of an oil lubricated circulator contains the bearings, seals and pump shaft

Bearing assembly

Why do most residential diaphragm tanks come pre-charged at 12 psig

Because PRV is factory set at 12 psi and PRV and bladder tank work together to maintain system pressure

Why should we never use Teflon tape to seal the threads of the probe

Because Teflon is a insulator

Static pressure in a hydronic system is greatest at the...

Bottom of the system

How would you know if the flow through the system is proper

Check delta T

There should be no water pressure on the diaphragm when

Checking the air pressure

A backflow preventer must be installed on any system that contains

Chemicals

Which 115 VAC load is controlled by the circulator relay

Circulator

What is the first load energized in a hot water boiler on a call for heat

Circulator relay coil

What load in the boiler is controlled by the end switch of a zone valve

Circulator relay coil

Name two loads that may be controlled by the thermostat

Circulator relay coil and zone valve motor

What causes a pressure reducing valve to close

Closes on a rise in pressure

Worn, sagging motor mounts could cause...?

Coupler failure

what type of relay is used as a circulator relay

Double pole single throw with 24 V coil

What is it meant by the term dry fired

Energizing heating source of a boiler with no water in it

How do we find the required pump out for a hot water system

Find longest loop of pipe in the system multiply that length of the longest lose by .06

Name three types of low water cut offs

Float, flow switch, probe type

What path does the electric current take to prove that water is present

From the probe of LWCO, into the water, through the water, to ground

What is meant by G.P.M

Gallons per minute, flow of a system