Smoke and heat vents shall be a minimum of ________ feet from fire walls.

20

A fire alarm system is retroactively required in all existing two-story Group R-1 hotels and motels with a minimum of _______ sleeping units.

21 Units

Given: An existing sprinklered building with the fire department connection located on the rear side of building. Which of the following is correct regarding this FDC?

A sign shall be provided indicating the location of the FDC (912.2.2)

Photoelectric smoke alarms shall not be installed less than _____ feet horizontally from a permanetly installed cooking appliance. a. 6 feet b 12 feet c 3 feet d 20 feet

A. 6 feet (907.2.11.3)

The fire code official is not authorized to ________. a. waive requirements specifically provided for in the code b. render interpretations of the code c. adopt policies and procedures d. adopt rules and regulations

A. waive requirements specifically provided for in the code (104.1)

What is the minimum number of sleeping units in a 180 unit R-1 occupancy that require visible alarms? a. 12 b. 14 c. 17 d. 5 percent of the total number of units

B. 14 (907.5.2.3.2)

Smoke alarms shall be installed not less than ____ feet horizontally from the door or opening of a bathroom that contains a bathtub or shower a. 8 feet b. 3 feet c. 15 feet d 12 feet

B. 3 Feet (907.2.11.4)

Given: A 19,000-square-foot one-story Group B office building. The building is not equipped with an automatic sprinkler system. At what occupant load is a manual fire alarm system required? a. 300 b. 500 c. 750 d. 1,000

B. 500 or more (907.2..2)

In a Group R occupancy, which of the following is incorrect about the placement of smoke alarms? a. Smoke alarms must be at least 3 feet from the door into a bathroom with a tub or shower. b. Ionization smoke alarms can only be installed in bedrooms. c. Photoelectric smoke alarms must be at least 6 feet from permanently installed cooking appliances. d. A smoke alarm must be installed in each room used for sleeping purposes.

B. Ionization smoke alarms can only be installed in bedrooms. (907.2.11.2)

In order to determine the acceptability of technologies, processes, products or other features of a building subject to inspection by the fire code official, the fire code official is authorized to require the owner or agent to provide ________ at no cost to the jurisdiction. a. additional copies of the IFC and needed standards b. a technical opinion and report c. a cost estimate for the construction d. additional fire apparatus

B. a technical opinion and report (104.8.2)

What is the maximum internal pressure allowed for a deflagration relief panel or venting device? a. 10 lb/ft b. 15 lb/ft c. 20 lb/ft d. 25 lb/ft

C 20lb/ft (911.2 S5)

What is the minimum internal pressure requirement for the walls and ceiling of a room that houses a deflagration hazard? a. 100 pounds per square inch b. 20 pounds per square foot c. 100 pounds per square foot d. 20 pounds per square inch

C. 100 lbs/sqft (911.2)

An operational permit is required to store, transport on site, dispense, use or handle a solid Class 2 oxidizer when the quantity exceeds ________. a. 10 pounds b. 20 pounds c. 100 pounds d. 500 pounds

C. 100 pounds (105.5.22)

Ionization Smoke Alarms shall not be installed less than ________ feet horizontally from a permanently installed cooking appliance. a. 5 feet b 3 feet c 20 feet d 30 feet

C. 20 feet (907.2.11.3)

What is the maximum travel distance to a portable fire extinguisher used to protect flammable liquids with an estimated spill depth of 0.25 inches inside of a light hazard occupancy? The extinguisher has a rating of 10-B. a. 20 feet b. 30 feet c. 50 feet d. 75 feet

C. 50 feet (906.3(2))

Which of the following is not a method for designing a smoke control system? a. pressurization method b. airflow design method c. smoke barrier method d. exhaust method

C. Smoke Barrier Method (909.5)

Activation of a duct smoke detector initiates a ________ signal at a constantly attended location. a. trouble b. audible occupant notification c. supervisory d. visual occupant notification

C. Supervisory (907.3.1)

Given: A 30,000-square-foot, two-story Group B occupancy. The building is sprinklered in all areas, except in the computer room on the first story. The computer room is protected with a clean agent fire-extinguishing system. Which of the following is correct when referring to the sprinkler protection in the building? a. the building is considered sprinklered throughout, and all code modifications based on sprinklers are applicable b. the building is considered sprinklered throughout, and all cod

C. The building is not considered sprinklered throughout since there are no sprinklers in the computer room; therefore, no code modifications based on sprinklers are allowed. (904.2.1)

What UL standard governs the listing of a fire-extinguishing system installed to protect the domestic cooking facilities in a Group R-2 college dormitory? a. UL 142 b. UL 300 c. UL 300A d. UL 2085

C. UL 300A (907.14.1.1)

When is an emergency voice/alarm communication system required in Group A occupancies? a. when the occupant load exceeds 300 b. when the fire area is greater than 5,000 ft c. when the occupant load is 1,000 or more d. when the fire area is greater than 12,000 ft

C. When the occupant load is 1,000 or more (907.2.1.1)

Where there is a conflict between a general requirement and a specific requirement in the code, the ________ requirement shall apply. a. most restrictive b. most general c. more specific d. least restrictive

C. more specific (102.10)

Which of the following activities does not require an operational permit? a. An outdoor assembly event featuring a monster truck race with 2,500 attendees b. A fireworks display after the monster truck race c. The tire changing and repair area for the monster trucks d. The refueling operation for the monster truck vehicles

C. the tire changing and repair area for the monster trucks (105.5)

When is an emergency voice/alarm communication system required in Group A occupancies? a. when the occupant load exceeds 300 b. when the fire area is greater than 5,000 ft c. when the occupant load is 1,000 or more d. when the fire area is greater than 12,000 ft2

C. when the occupant load is 1,000 or more (907.2.1.1)

Based on the commodity classification, which of the following does not require smoke and heat removal?

Class 1 and 2 Commodities that are frozen foods (910.2 E)

The minimum sound pressure level for audible notification appliances is ________. a. 60 dBA b. 75 dBA c. 90 dBA d. 15 dBA above the ambient sound level or 5 dBA above the maximum sound level

D. 15 dBA above the ambient sound level or 5dBA above the maximum sound level. (907.5.2.1.1)

What is the system air flow rate that requires the installation of duct smoke detectors in air conditioning systems in a high-rise building? a. 500 CFM b. 1,200 CFM c. 1,500 CFM d. 2,000 CFM

D. 2000 CFM (907.2.13.1.2)

What is the minimum rating required for a portable fire extinguisher designed for use against Class A fire hazards in an Extra Hazard Occupancy? a. 1-A b. 2-A c. 3-A d. 4-A

D. 4-A (906.3(1))

What is the maximum installed height above a finished floor to the top of a portable fire extinguisher with a weight of 25 pounds? a. 2 feet b. 3 feet c. 4 feet d. 5 feet

D. 5 feet (906.9.1)

Which of the following require a mass notification system? a. a university building with an occupant load of 1,000 or more b. a university with multiple buildings c. a university with multiple buildings and an aggregate occupant load of 1,000 or more d. a university with multiple buildings and an aggregate occupant load of 1,000 or more and a risk analysis in accordance with NFP 72 determines that mass notification is needed

D. A university with multiple buildings and an aggregate occupant load of 1,000 or more and a risk analysis in accordance with NFPA 72 determines that mass notification is needed. (917.1)

When are carbon monoxide alarms required in Group I-1 buildings? a. When the building contains a fuel-burning appliance. b. When the building has an attached garage. c. When the building contains a fuel-burning forced-air furnace. d. all of the above

D. All of the above (915.1.1)

Which of the following are required for a CO automatic fire-extinguishing system predischarge alarm? a. a warning sign b. an audible and visual signal c. notification when a door does not shut properly d. both a and b

D. Both A and B (904.3.4)

A secondary water supply for the sprinkler system is required on the property when the building is ________. a. a high-rise building b. an underground building c. a covered mall building d. a high-rise building in Seismic Design Category C, D, E or F

D. High-rise building in seismic design category c,d,e,or f per the IBC. (914.3.2)

Which of the following require a mass notification system? a. a university building with an occupant load of 1,000 or more b. a university with multiple buildings c. a university with multiple buildings and an aggregate occupant load of 1,000 or more d. a university with multiple buildings and an aggregate occupant load of 1,000 or more and a risk analysis in accordance with NFP 72 determines that mass notification is needed

D. a university with multiple buildings and an aggregate occupant load of 1,000 or more and a risk analysis in accordance with NFP 72 determines that mass notification is needed (917.1)

The construction provisions of the IFC apply to ________. a. structures, facilities and conditions arising after the adoption of the code b. existing structures, facilities and conditions not legally in existence at the time of adoption of the code c. existing structures, facilities and conditions when specifically required in Chapter 11 d. all of the above

D. all of the above (102.1)

An operational permit is required for a liquid Class 3 water-reactive material when the quantity exceeds ________. a. 5 gallons b. 10 gallons c. 55 gallons d. any amount

D. any amount (105.5.22 cont)

Which components must be interlocked with a fire-extinguishing system in a commercial kitchen hood? a. fuel supply to the cooking equipment b. ventilation system c. electric power to the cooking equipment d. both a and c

D. both a and c (904.14.1.1)

24. The fire code official has the authority to authorize disconnection of utility services to a building under what conditions? a. To encourage compliance with a correction notice b. As part of emergency operations c. To eliminate an immediate hazard in the building d. Both B and C

D. both b and c (110.1)

If the owner refuses to allow the fire code official to enter an occupied building or premises to conduct an inspection to enforce the code, the fire code official may a. enter the building and conduct the inspection without permission b. shut down the business c. post an order to vacate d. obtain an inspection warrant

D. obtain an inspection warrant (104.3.1)

Which of the following is not considered part of the code's intent and purpose? a. provide a reasonable level of life safety b. establish a minimum set of requirements c. address dangerous conditions in new and existing buildings d. punish those who intentionally set fires

D. punish those who intentionally set fires

Provisions in the appendices of the IFC shall not apply unless ________. a. they are specifically applicable to the individual situation b. the jurisdiction contains structures, facilities and conditions that are appropriate to the provisions of the appendices c. they are more restrictive than other provisions in the code d. the appendix is specifically adopted

D. the appendix is specifically adopted ([A] 101.2.1)

Given: A one-story building with a floor area of 11,200 square feet that is used for woodworking operations. The manufacturing process will produce finely divided combustible waste. What is the occupancy classification of the building, and is an automatic sprinkler system required?

F-1; Yes (903.2.4.1) Woodworking operations require a sprinkler system when fire area is in excess of 2500 sqft

What is the required condition to allow Fire Codes Official to Approve the removal of occupany used hoselines

Hoselines would not be used by FD or On-site Employees (901.8.2)

What is NFPA 72

National Fire Alarm and Signaling Code

Which of the following is a method to protect the riser and laterals for a Class I stand-pipe in a seven-story sprinklered building?

No protection is required for the laterals if the risers are located in interior exit stairways. (905.4.1)

Does A Group M Grocery Store of 18,200 sqft divided into equal fire areas with a protected barrier require a sprinkler system?

No unless there is high-piled storage (903.2.7

What is the minimum automatic sprinkler system design criterion for the exit corridors in a semiconductor fabrication facility storing and handling hazardous product materials in excess of the maximum allowable quantities?

Ordinary Hazard Group 2 (903.2.5.2)

What section is regarding Automatic Sprinklers?

Section 903

Section regarding alternative automatic fire extinguishing systems

Section 904

What section regards Standpipe Systems?

Section 905

What section regards Portable Fire Extinguishers?

Section 906

Section Regarding Smoke and Heat Removal

Section 910

Section Regarding Explosion Control

Section 911

Section regarding Fire Department Connections (FDCs)

Section 912

Section Regarding Fire Pumps

Section 913

What section regards Mass Notification Systems?

Section 917

What sprinkler control component requires electronic monitoring

Sprinkler control valve on the 2nd floor of a 3 story structure (903.4)

What is the requirement for an automatic sprinkler system in a mechanical-access enclosed parking garage classified as a Group S-2 occupancy?

Sprinklers throughout the building containing the mechanical-access parking garage. (903.2.10.2)

Whenever there are practical difficulties in carrying out the provisions of the IFC, the fire code official shall have the authority to grant modifications for ________. a. individual cases b. identical situations c. all similar cases d. individual persons

a. individual cases (104.9)

When the fire code official finds a structure that constitutes a clear threat to human life, safety or health, which of the following actions cannot be taken? a. Evacuate the building b. If the owner is not available on site, the fire code official shall order the immediate destruction of the building c. Serve notice on the owner identifying the unsafe conditions and required repairs d. Refer the building to the building code official for repair, alteration or remodeling

b. If the owner is not available on site, the fire code official shall order the immediate destruction of the building (114)

When does a construction permit issued under the authority of the IFC become invalid? a. after the construction commences b. after a period of 180 days when work is abandoned or suspended c. end of calendar year d. when the next edition of the code is adopted

b. after a period of 180 days when work is abandoned or suspended. (105.3.1)

The referenced standards in IFC Chapter 80 are organized ________. a. alphabetically, by subject b. alphabetically, by the issuing organization or agency c. by their publication date d. by chapters in the IFC

b. alphabetically, by the issuing organization or agency. (IFC 80)

According to Appendix A, members with a personal, professional or financial interest in a matter before the board shall ________. a. declare such interest before discussion or voting on such matters b. declare such interest and refrain from participating in discussions, deliberations and voting on such matters c. declare such interest, then lead the discussion, but not vote on such matters d. remain silent and refrain from stating a position one way or the other on such matters

b. declare such interest and refrain from participating in discussions, deliberations and voting on such matters (A101.3.6)

7. The fire code official shall retain official records for not less than ________ years or for as long as the structure or activity to which such records regulate remains in existence. a. three b. five c. seven d. ten

b. five (104.6)

According to Appendix A, the Board of Appeals shall consist of _______ voting members. a. three b. five c. six d. seven

b. five (A101.3)

When the fire code official finds a building, premises, vehicle, storage facility or outdoor area that is in violation of the IFC, he or she is authorized to ________. a. order the building vacated b. prepare a written notice of violation c. condemn the building d. issue a stop work order

b. prepare a written notice of violation (112.3)

27. The Board of Appeals, if Appendix A is adopted, is required to meet within ________ days after a notice of appeal has been received. a. five b. ten c. fourteen d. thirty

b. ten days (A101.5)

30. An operational permit is required to manufacture, store or handle an aggregate quantity of Level 2 or 3 aerosol products in excess of ________ pounds net weight. a. 55 b. 100 c. 500 d. 1,000

c 500 lbs (105.5.2)

What is the IFC prescribed frequency for inspection of buildings, facilities and properties? a. Annually b. The IFC does not establish an inspection frequency. c. The fire code official is authorized to perform inspections as needed to determine the extent of compliance with the provisions of the IFC. d. At the owner's request

c. The fire code official is authorized to perform inspections as needed to determine the extent of compliance with the provisions of the IFC. (108.2)

What amount of solid Class V organic peroxides requires an IFC operational permit? a. 10 pounds b. 20 pounds c. any amount d. a permit is not required

d a permit is not required (105.5.22)

Construction documents and design submittals for a permit shall be prepared by a a. professional consultant b. special expert c. licensed contractor, when required by local statutes d. registered design professional, when required by local statutes

d. a registered design professional, when required by local statutes (106.1)

Which one of the following is not included in a required operational permit regulated by the IFC? a. hot work b. organic coatings c. floor finishing d. compressed-gas-powered vehicles

d. compressed-gas-powered vehicles (105.5.9)

Given: Mechanical exhaust fans are being installed for smoke removal in a sprinklered Group S-1 occupancy with high-piled combustible storage. Which of the following is incorrect about the operation of the mechanical smoke removal system?

The exhaust fan shall activate automatically upon smoke detector activation. (910.4.4, mechanical smoke removal system shall be activated by manual controls only).

When is a sprinkler required in Group M Occupancies w/ upholstered furniture or mattresses?

When the area of upholstered furniture or mattresses exceeds 5000 sqft (902.7.2.1)

Is a standpipe required in an existing building

Yes When Fire Department access is 50feet below or above closest point (1103.6.1)

Does a nightclub of 3500sqft w/ fixed seating and an occupant load of 117 require a sprinkler system?

Yes, its an A-2 occupancy with an occupant load over 100) (903.2.1.2)

Given: A stage with an area of 2,800 square feet in a Group A-1 occupancy. Is a standpipe required, and if so, what class of standpipe is required?

Yes; Class III Standpipe (905.3.4)

A construction permit for a 500 square foot, temporary tent that is open on all sides is not required if a minimum clearance of ________ feet to structures and other tents is maintained. a. 12 b. 15 c. 20 d. 26

a. 12 feet (105.5.49)


Ensembles d'études connexes

Chapter 33: Disorders of Renal Function

View Set

Los Ojos de Carmen English Translation Original RE-EDITED

View Set

Chapter 6: Volcanoes and Volcanic Hazards

View Set

module 11 quiz: Community Program Planning, Implementation, and Evaluation

View Set

Healthcare Quality Improvement Act of 1986

View Set

CompTIA Security+ (SY0-601) Practice Exam #4

View Set

Experience Cloud Consultant Exam (V6.21.21)

View Set