Lesson 4: Grounding Electrodes and the Grounding Electrode System

Réussis tes devoirs et examens dès maintenant avec Quizwiz!

The resistance between a grounding electrode (such as a ground rod) and earth can vary depending on which of the following?

-Ambient temperature -Geographical location -Mineral content of the soil

A metal underground water pipe that is in direct contact with the earth for ? or more is a Code-recognized grounding electrode and must be included in the grounding electrode system.

10'

What is the minimum length of contact that must be made with the earth in order for a metal in-ground support structure to qualify as a grounding electrode?

10'

A plate electrode is required to have not less than ? of surface in direct contact with the earth.

2 ft2

A concrete-encased electrode can be installed in either a vertical or horizontal orientation, and it must have not less than ? of one or more conductive rebar or rods, or a 4 AWG bare copper conductor.

20'

A concrete-encased grounding electrode can be in a horizontal or vertical orientation as long as there is a minimum ? of contact with the earth.

20'

A single grounding electrode of the rod, pipe, or plate type is not required to be supplemented by an additional electrode of any type specified in Section 250.52(A)(2) through (8) if the single electrode has a resistance to Earth of ? or less.

25 Ω

The minimum sizing requirements for grounded conductors are provided in which of the following?

250.102

Where bonding jumpers are used to connect grounding electrodes together to form a grounding electrode system, ? points to the NEC reference used to size such bonding jumpers.

250.53(C)

A ground ring electrode must completely encircle a building or structure, be not less than 20 feet in length, and be buried not less than ? below the grade.

30"

A rod or pipe electrode that cannot be driven into the earth because of encountering rock bottom is permitted to be buried at a depth of not less than ? .

30"

A concrete-encased electrode can be created using 20 feet or more of bare copper not smaller than ? .

4 AWG

The NEC generally prohibits the use of an interior metal water piping system to connect grounding electrodes to the grounding electrode conductor beyond a distance of ? from the point of entrance to the building or structure.

5'

Stainless steel rod electrodes generally must not be less than ? in diameter.

5/8"

A distance of not less than ? shall be maintained between an eight-foot ground rod and the next closest ground rod.

6'

A rod or pipe electrode is generally required to be driven to a depth of not less than ? .

8'

A ground rod electrode is always required to be driven into the earth.

False

Foundations and footings that are not in direct contact with the earth qualify as grounding electrodes.

False

If present, the structures and structural reinforcing steel described in Section 680.26(B)(1) and (B)(2) are required to be included in the grounding electrode system for a building or structure.

False

Plate electrodes must be buried not less than 24 inches below grade.

False

The NEC requires that a metal underground water pipe electrode be buried not less than 30 inches below grade level.

False

The grounding electrode network for a lightning protection system is permitted to be used as the grounding electrode system for the electrical service supplying a building or structure only when there are no other electrodes available.

False

A conducting object through which a direct connection to earth is established defines which of the following?

Grounding electrode

Which of the following persons was responsible for the research and development that eventually resulted in the NEC requirements for a concrete-encased electrode?

Herbert G. Ufer

If present at each building or structure served, which of the following shall be bonded together to form the grounding electrode system?

I. Concrete-encased grounding electrode II. Metal in-ground support structures III. Metal underground water pipe electrode IV. Rod and pipe electrodes

What is the maximum resistance to ground permitted for a grounding electrode system consisting of a concrete-encased electrode, a building steel electrode, and a metal water pipe electrodes?

No maximum resistance value is specified in the NEC

Which part of Article 250 provides the requirements for grounding electrodes and the grounding electrode system?

Part III

A single grounding electrode of the rod, pipe, or plate type must generally be supplemented by an additional electrode of any type specified in Section 250.52(A)(2) through (8).

True

A structure is defined as that which is constructed or built and does not include electrical equipment.

True

Section 250.50 requires all grounding electrodes that are present at each building or structure served to be bonded together to form the grounding electrode system.

True

The NEC makes it clear that if any grounding electrodes are present at a building or structure served by electrical power, the electrodes must be bonded together to form a grounding electrode system.

True

The purpose of a grounding electrode is to function as the connection between the ground (earth) and grounded electrical systems and electrical equipment.

True

The supplemental grounding electrode for a metal water pipe electrode is permitted to be bonded to the grounding electrode conductor, the grounded service-entrance conductor, the nonflexible grounded service raceway, or any grounded service enclosure.

True

Where two services are installed on the same building or structure as permitted in 230.2(A), they are required to be connected to the same grounding electrode system.

True

Which of the following is not permitted as a grounding electrode?

Underground metal gas piping

Where an auxiliary grounding electrode is installed for equipment such as parking lot light poles, the connection of the auxiliary electrode is in addition to the required ? .

equipment grounding conductor

The ? provides the essential function of connecting the electrical system, equipment, or both to the earth.

grounding electrode


Ensembles d'études connexes

Patho PrepU Ch. 8: Disorders of Fluid and Electrolyte and Acid Base Balance

View Set

Business law chapter 1,2,3 true or false

View Set

Data Structures Final Study Guide

View Set

acct 2302, quiz 3: cvp & var. costing

View Set

Knoch Physiology Module Note cards Final Exam

View Set

Экономика организации предприятия

View Set