Milk Holt 210 B
A meeting room measuring 12 ft x 18 ft requires _____ floor receptacle outlet(s). 1 2 3
1
Each meeting room of not more than _____ sq ft in other than dwelling units shall have outlets for nonlocking-type, 125V, 15A or 20A receptacles installed in accordance with 210.65(B). 500 1,000 1,500 2,000
1,000
Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets for dwelling unit wall spaces, unless they are located within _____ in. of the wall. 6 12 18 24
18
The recommended maximum total voltage drop on branch-circuit conductors is _____ percent. 2 3 4 6
3
All outdoor outlets for dwellings, other than those covered in 210.8(A)(3), Ex to (3), that are supplied by single-phase branch circuits rated 150 volts-to-ground or less, _____, shall have ground-fault circuit- interrupter protection for personnel. 15A or more 20A or less 30A or less 50A or less
50A or less
In other than dwelling units, GFCI protection shall be provided for all 125V through 250V receptacles supplied by single-phase branch circuits rated 150V or less to ground, 50A or less, where receptacles are installed within _____ ft from the top inside edge of the bowl of a sink. 3 4 5 6
6
Receptacles installed below a countertop or work surface shall not be located where the countertop or work surface extends more than _____ in. beyond its support base. 3 6 9 12
6
Foyers with an area greater than _____ sq ft shall have a receptacle located in each wall space 3 ft or more in width unbroken by doorways, windows next to doors that extend to the floor, and similar openings. 40 60 80 100
60
For an island or peninsular countertop, at least one receptacle outlet shall be provided for the first _____ sq ft or fraction thereof, of the countertop or work surface. 9 10 12 15
9
Lighting outlets in guest rooms or guest suites shall be permitted to be controlled by occupancy sensors that are located at a customary wall switch location and equipped with a manual override that allows the sensor to function as a wall switch. True False
False
A single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit. True False
True
All 15A and 20A, 125V, single-phase receptacles installed in _____ of dwelling units shall have GFCI protection. laundry areas finished basements unfinished basements all of these
all of these
In other than dwelling locations, GFCI protection is required for all single-phase receptacles rated 150V to ground or less, 50A or less and three-phase receptacles rated 150V to ground or less, 100A or less in _____. indoor damp and wet locations locker rooms with associated showering facilities garages, service bays, and similar areas other than vehicle exhibition halls and showrooms all of these
all of these
Receptacles installed in bathrooms within six feet of the outside edge of a _____ shall have GFCI protection. bathtub or shower stall bidet toilet window opening
bathtub or shower stall
120V, single-phase, 15A and 20A branch circuits supplying outlets and devices installed in _____ of hotels and motels shall be protected by any of the means described in 210.12(A)(1) through (6). guest rooms conference rooms lobbies and common hallways game rooms
guest rooms
In dwelling units, when determining the spacing of receptacle outlets, _____ on exterior walls shall not be considered wall space. fixed panels fixed glass sliding panels all of these
sliding panels
The number of receptacle outlets for guest rooms in hotels and motels shall not be less than that required for a dwelling unit. These receptacles can be located to be convenient for permanent furniture layout, but at least _____ receptacle outlet(s) shall be readily accessible. one two three four
two
Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all _____ conductors at the point where the branch circuit originates. circuit grounded grounding ungrounded
ungrounded
Where more than one nominal voltage system supplies branch circuits in a building, each _____ conductor of a branch circuit shall be identified by phase or line and system voltage class at all termination, connection, and splice points in compliance with 210.5(C)(1)(a) and (b). neutral ungrounded grounding all of these
ungrounded
All single-phase receptacles rated 150V to ground or less, 50A or less and three-phase receptacles rated 150V to ground or less, 100A or less installed in locker rooms with associated showering facilities shall be GFCI protected. True False
True
An individual 20A branch circuit can supply a single dwelling unit bathroom for receptacle outlet(s) and other equipment within the same bathroom. True False
True
Where two or more branch circuits supply devices or equipment on the same yoke or mounting strap, a means to disconnect simultaneously the ungrounded supply conductors shall be provided _____. at the point where the branch circuits originate at the location of the device or equipment at the point where the feeder originates within sight of the device or equipment
at the point where the branch circuits originate
In addition to the number of branch circuits required by other parts of 210.11, at least one 120V, 20A branch circuit shall be installed to supply receptacle outlets in _____ garages with electric power. attached detached unfinished attached and detached
attached and detached
Two or more _____ small-appliance branch circuits shall be provided to supply power for receptacle outlets in the dwelling unit kitchen, dining room, breakfast room, pantry, or similar dining areas. 15A 20A auxiliary supplemental
20A
Receptacle outlets in meeting room fixed walls shall be installed in accordance with _____. 210.52(A)(1) 210.52(A)(1) and (A)(2) 210.52(A)(1) through (A)(3) 210.52(A)(1) through (A)(4)
210.52(A)(1) through (A)(4)
A receptacle outlet shall be installed at each dwelling unit kitchen wall countertop and work surface space that is 12 in. or wider and receptacle outlets shall be installed so that no point along the wall line is more than _____ in., measured horizontally from a receptacle outlet in that space. 10 12 16 24
24
Additional requirements for installing receptacles in dwelling unit countertops and work surfaces can be found in Article _____. 402 404 406 410
406
In dwelling units, GFCI protection shall be provided for all 125V through 250V receptacles supplied by single-phase branch circuits rated 150V or less to ground where receptacles are installed within _____ ft from the top inside edge of the bowl of a sink. 3 4 5 6
6
Appliance receptacle outlets installed for a specific appliance in a dwelling unit, such as laundry equipment, shall be located within _____ of the intended location of the appliance. sight 3 ft 6 ft the length of the cord
6 ft
In dwelling units, outdoor receptacles can be connected to one of the 20A small-appliance branch circuits. True False
False
In existing installations where a voltage system(s) already exists and a different voltage system is being added, it shall be permissible to mark only the old system voltage. True False
False
All 125V through 250V receptacles supplied by single-phase branch circuits rated 150V or less to ground installed in dwelling unit boathouses shall have _____ protection for personnel. GFCI AFCI
GFCI
For one- and two-family dwellings, at least one receptacle outlet shall be installed in each _____. separate unfinished portion of a basement attached or detached garage with electric power accessory building with electric power all of these
all of these
In all occupancies for attics and underfloor spaces, utility rooms, and basements where a lighting outlet is installed for equipment requiring service, the lighting outlet shall be _____. installed at the entrance to such spaces installed at or near the equipment of the motion sensor type GFCI protected
installed at or near the equipment
Receptacle outlets installed below the countertop or work surface in dwelling units, shall be located not more than _____ in. below the countertop or work surface. 6 12 20 36
12
In a dwelling unit, a receptacle is required in any space _____ ft or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets that do not have countertops or similar work surfaces. 2 3 4 5
2
At least one wall switch-controlled lighting outlet shall be installed in every habitable room and bathroom of a guest room or guest suite of hotels, motels, and similar occupancies. A receptacle outlet controlled by a wall switch may be used to meet this requirement in other than _____. bathrooms kitchens sleeping areas bathrooms and kitchens
bathrooms and kitchens
The receptacle outlet for a dwelling unit bathroom shall be located on a(an) _____ adjacent to the basin or basin countertop, on the countertop, or on the side or face of the basin cabinet, and never more than 12 in. below the top of the basin or basin countertop. wall or partition base cabinet light fixture interior wall
wall or partition
For attics and underfloor spaces, utility rooms, and basements in all occupancies, at least _____ lighting outlet(s) containing a switch or controlled by a wall switch shall be installed where these spaces are used for storage or contain equipment requiring servicing. one two three four
one
In other than dwelling units, GFCI protection is required for receptacles installed in _____. kitchens unfinished areas of basements laundry areas all of these
all of these
Hallways in dwelling units that are _____ ft long or longer require a receptacle outlet. 6 8 10 12
10
GFCI protection shall be provided for all 15A and 20A, 125V, single-phase receptacles installed in a dwelling unit _____. attic garage and laundry area utility room den
garage and laundry area
The maximum rating of a single fixed in place utilization equipment supplied by a 20A multiple outlet branch circuit shall be no greater than _____. 7.50A 10A 16A 20A
10A ??
A meeting room with any floor dimension that is _____ ft or greater in any direction and that has a floor area of at least 215 sq ft shall have at least one floor receptacle outlet. 8 10 12 15
12
Kitchen and dining room countertop receptacle outlets in dwelling units shall be installed on or above the countertop or work surface, but not more than _____ in. above the countertop or work surface. 12 18 20 24
20
A laundry receptacle outlet shall not be required in each dwelling unit of a multifamily building, if laundry facilities are provided on the premises for all building occupants. True False
True
In other than dwelling locations, GFCI protection is required for all single-phase receptacles rated 150V to ground or less, 50A or less and three-phase receptacles rated 150V to ground or less, 100A or less in unfinished portions or areas of the basement. True False
True