MODULE 3 EXAM REVIEW

Réussis tes devoirs et examens dès maintenant avec Quizwiz!

HFC-410A

A 50-50 blend of HFC-32 and HFC-125 produce ________.

Zeotropic

A ________ blended refrigerant never fully mixes chemically, and are not true compounds.

P-T chart

A _________ shows the pressure and temperature relationships at saturation for a specific refrigerant.

total loss of refrigerant

A leak in an evaporator coil, of a unit using a zeotropic blend, usually results in a _________.

CFC

A lot of ______ refrigerants are azeotropes, azeotropes are not compounds.

fully blended refrigerant / no harm

A small leak on the liquid line of a unit that operates around the clock, using a zeotropic blend, usually results in a loss of ________, and ________ is done to the remaining refrigerant.

temperature range / constant pressure

A zeotropic blended refrigerant evaporates and condenses over a ______, called the glide, and at a _________.

hygroscopic

All refrigerant oils are _______ to some degree, meaning that they can absorb moisture from the air.

HFC

An _______ refrigerant has an ODP of 0.

Azeotropic

An ________ refrigerant blend behaves like a pure refrigerant.

superheat

Any vapor temperature measured above the dew point would indicate ________

binary blends

Blends containing 2 refrigerants are called ______.

ternary bends

Blends of 3 refrigerants are called ________.

azeotrope

Charging charts and P-T charts that one equipment manufacturer uses for R-410A, a near-azeotrope, look identical (except for pressures) to charging charts for similar equipment using HCFC-22, an _________.

added

For a system using a fixed restrictor metering device, if the superheat calculated is higher than the required superheat for the system, refrigerant would have to be ________.

recovered

For a system using a fixed restrictor metering device, if the superheat calculated is lower than the required superheat for the system, refrigerant would have to be ________.

leak

Fractionation becomes a problem if a _______ occurs in the system.

Zeotropic

Fractionation is a problem with what classification of blended refrigerants?

pure refrigerant compound

From a technicians standpoint working with an azeotrope is like working with a _________.

Zeotropic

HFC-407C is an example of a _________ blended refrigerant.

near-azeotropic

HFC-410A is an example of what classification of blended refrigerants?

higher

HFC-410A operates at ________ pressures than HCFC-22, therefore it cannot be used in equipment designed for HCFC-22.

charged properly

If the system temperature, humidity, and required superheat are known for the equipment, then superheat can determine if a system is _________.

Fractionation

In a leaking system using a zeotropic blend of refrigerants; When the different refrigerants in the blend boil off at different rates, and leak at different rates, upsetting the blend proportions in the remaining refrigerant it is referred to as ________.

evaporates / condences

In an azeotropic refrigerant blend, the refrigerant ________ and _______at one given pressure and temperature

liquid

Like zeotrope blends, near-azeotropic blends should be charged into a system as a ________.

glide

Near-azeotropes have ________ characteristics, like zeotropes, but they are usually minimal and not a factor to technicians servicing the system.

pumped

Oil should always be _______ into a system to avoid the contamination from the air.

Vapor / liquid

On P-T charts for zeotropic blends that do not have a bubble point or dew point listed, the ______ column should be used for the dew point, and the ______ column should be used for the bubble point.

hygroscopic

PVE oil is not ________ giving it an advantage over POE and PAG oils.

temperature / subcooling

Subcooling can only determine if a system is charged properly if the __________ and required _________ of the equipment are known.

fixed metering device

Superheat can only be used to tell if a system is charged properly if the system uses a __________.

expansion valves

Systems with ________ must be charged based on subcooling values.

refrigerant gauge manifold

The __________ can serve as an expansion device during during the charging of a zeotropic blend.

compressor oil

The __________ must have a dielectric strength high enough so that it doesn't break down or arc under normal operating voltage conditions.

bubble point

The point at which refrigerant starts evaporating when heat is added to the refrigerant.

dew point

The point at which refrigerants ends evaporating when heat is added to the refrigerant.

HFC-410A

The refrigerant __________ is an example of a near-azeotrope.

liquid line pressure / liquid line temperature

The second step to calculate subcooling is to record the _________.

suction pressure / suction line temperature

The second step to calculating superheat is to record the _________ after the system has been turned on and ran for at least 10 minutes.

glide

The temperature range in which a zeotropic refrigerant blend evaporates and condenses is called the ________.

saturated temperature

The third step to calculate subcooling is to find the liquid line pressure on the P-T chart and record the corresponding _________.

suction pressure

The third step to finding superheat is to find the ________ on the P-T chart and record the corresponding saturated temperature.

leak location / volume lost / how much time the unit operates

To determine if a system using a zeotropic blend should be evacuated and recharged with new refrigerant after a leak has occured depends on what three things?

azeotropes / zeotropes / near-azeotropes

What are the 3 categories blended refrigerants fall into?

temperature at which the evaporator operates

What determines the type of refrigerant used in a system?

Refrigerant finishes condensing

What happens at the bubble point when heat is removed from the refrigerant?

Refrigerant starts condensing

What happens at the dew point when heat is removed from refrigerant?

red band

What indicates a flammability hazard on a refrigerant cylinder?

measured temperature-saturation temperature=

What is the formula to find superheat?

liquid refrigerants

What kind of refrigerant is a class 1 safety refrigerant?

low-pressure refrigerants

What kind of refrigerant is a class 2 safety refrigerant?

high-pressure refrigerants

What kind of refrigerant is a class 3 safety refrigerant?

flammable refrigerants

What kind of refrigerant is a class 4 safety refrigerant?

bubble point / dew point

What points are given on a P-T chart for a zeotropic refrigerant blend?

gauge manifold, electronic thermometer, P-T chart

What tools or instruments are needed to calculate superheat and subcooling?

POE

What type of oil is compatible with most of the HFC refrigerants, and is widely used in those applications.

mineral oil

What type of oil is required for systems using HCFC-22?

POE/PVE

What type of oil is required for systems using HFC-410A?

liquid state

When adding charge, zeotropic blends must always be in a _______, this ensures that they are in proper proportions to each other.

bubble point

When calculating subcooling with a zeotropic blend use the ______.

bubble point

When calculating subcooling with a zeotropic blend, use the ______.

dew point

When calculating superheat with a zeotropic blend use the _______.

dew point

When calculating superheat with a zeotropic blend, use the _______.

metering orifice / vapor state

When charge is added using a zeotropic blend to an operating system through the suction service port, the liquid must be passed through a ________ before it enters the unit to ensure that it is in a _________.

begins to evaporate

When heat is added to the refrigerant bubble point can be looked at as the point at which refrigerant __________.

Dew point / superheating

When heat is added to the refrigerant, the ________ can be looked at as the point at which the blend is finished evaporating, and _______ of the vapor begins.

condensed to a liquid

When heat is removed from refrigerant the bubble point can can be looked at as the point where all vapor has ________.

condense from vapor

When heat is removed from the refrigerant, the dew point can also be looked at as the point at which liquid refrigerant first begins to _______.

recovering refrigerant

When subcooling, _________ will increase the liquid line temperature

adding refrigerant

When subcooling, _________ will lower the liquid line temperature.

drop-in replacement

When using a ________ in a system, the compressor oil may have to be purged from the system and a new type of oil in its place, the system components such as the filter drier, metering device, and accumulators or receivers may need to be replaced.

liquid line near the exit of the condenser

Where do you attach the temperature probe to calculate subcooling?

suction line near the compressor

Where do you attach the thermometer to calculate the superheat?

liquid pressure

With zeotropic refrigerants, the bubble point is indicated by the ________ column on a P-T chart.

vapor pressure

With zeotropic refrigerants, the dew point is indicated by the ________ column on a P-T chart.

alkylbenzene

_____ oils are widely used in low-temperature applications and are not compatible with synthetic oils.

saturation

________ is the point at which a refrigerant is partially in its liquid state.

acid/oil

________ test kits are used to sample the compressor oil to check for contaminants.

superheat

_________ is the heat added to a refrigerant after it is fully vaporized.

subcooling

_________ is the heat removed from a refrigerant after it has fully condensed into a liquid.

PAG

_________ oil is used in automotive ac systems where HFC-134a is the refrigerant.

glide

_________ only has to be considered when dealing with zeotropic refrigerants.

dielectric strength

___________ is the ability of oil or any material to resist breaking down in the presence of voltages.

voltages

___________ of varying values exist inside shells of operating compressors.

contaminents

___________, such as water can lower the dielectric strength of oil and cause it to break down.

subcooling

any temperature measured below the bubble point would indicate _________.

drums

class 1 refrigerants have a normal boiling point of 68F and are typically packaged in _______, since their pressure is very low at normal temperatures.

3

class _____ refrigerants are compressed gases with a minimum cylinder pressure that exceed 500 psig.

4

class _____ refrigerants have a flammability rating of 2 or 3 in ANSI/ASHRAE standard 34.

2

class ______ refrigerants are compressed gases with a minimum cylinder pressure that does not exceed 500 psig.

saturated temperature-measured temperature=

what is the formula to calculate subcooling?

zeotropic

what type of refrigerant blend is fractation a problem?


Ensembles d'études connexes

Compensation Midterm (Ch. 5-8, 12, 13, 17)

View Set

Chapter 45: Cerebral Dysfunction (Perry) NCLEX Style Qs

View Set

ACG 2021 Ch. 4 Focus Practice Set

View Set

15: Federal Employment Laws That Impact Compensation and Benefits

View Set

RN Nutrition Online Practice 2023 A

View Set

HISTORY - THE NATION SUFFERS GROWING PAINS

View Set

Motor Behavior Chapter 5: Movement Models

View Set

Chapter 11: Curriculum Standards, Assessment, and Student Learning

View Set

Theology of the Church - Test 1 (Goheen)

View Set

Chapter 7 Thinking and Intelligence

View Set