NEC 310
In general, the minimum size conductor permitted for use in parallel installations is _____ AWG.
1/0
Sectioned equipment grounding conductors smaller than _____ AWG shall be permitted in multiconductor cables, if the combined circular mil area of the sectioned equipment grounding conductors in each cable complies with 250.122.
1/0
The minimum size copper conductor permitted for branch circuits under 600V is _____ AWG.
14
Where installed in raceways, conductors _____ AWG and larger shall be stranded, unless specifically permitted or required elsewhere in the NEC.
8
Parallel conductors shall have the same _____.
Length, material, size in circular mil area, (insulation type, terminated in same manner)
True or False: Conductors shall be permitted for use in any of the wiring methods recognized in Chapter 3 and as permitted in the NEC.
True
True or False: Where conductors in parallel are run in separate raceways, the raceways shall have the same electrical characteristics.
True