EEP Unit 7

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

Overcurrent protection for the secondary of a transformer rated 1,000V or less having a secondary current rating of 9A or more must be set at not more than _____ percent of the secondary current rating.

125

The primary overcurrent protection for a transformer rated 1,000V, nominal, or less, having a primary current rating of 9A or more must be set at not more than _____ percent of the primary current when using primary only overcurrent protection.

125

What size secondary conductor can be used for a three-phase, 480V transformer, where the secondary overcurrent protection is sized at 110A?

2 AWG

A 45 kVA, 480V primary to 120/208V secondary, three-phase transformer with a 175A secondary overcurrent device will require at least _____ secondary conductors (the secondary conductors are 10 ft long).

2/0 AWG

What size secondary conductor can be used for a three-phase, 480V transformer, where the secondary overcurrent protection is sized at 175A?

2/0 AWG

The size of the grounding electrode conductor for a single separately derived system must not be smaller than that identified in _____, based on the area of the largest derived ungrounded supply conductor.

250.66

What's the maximum primary overcurrent device rating for a 0.50 kVA, single-phase, 240V transformer?

3 A

A 75 kVA, 480V primary to 120/208V secondary, three-phase transformer with a 300A secondary overcurrent device will require at least _____ secondary conductors (the secondary conductors are 10 ft long).

300 kcmil

In an alternating-current system, the size of the grounding electrode conductor to a concrete-encased electrode isn't required to be larger than a(an) _____ copper conductor.

4 AWG

What's the maximum primary overcurrent device rating for a 2.50 kVA, 480V, single-phase transformer?

6 A

A 45 kVA, 480V primary to 120/208V secondary, three-phase transformer with a 70A primary overcurrent device will require at least _____ primary conductors with terminals rated 75°C.

6 AWG

A 75 kVA, 480V primary to 120/208V secondary, three-phase transformer with a 125A primary overcurrent device will require at least _____ primary conductors with terminals rated 75°C.

6 AWG

What size secondary conductor can be used for a three-phase, 480V transformer, where the secondary overcurrent protection is sized at 50A with terminals rated 75°C?

8 AWG

What's the maximum primary overcurrent device rating for a 25 kVA continuously loaded, three-phase, 240V transformer?

80 A

The connection of the system bonding jumper for a separately derived system must be made _____ on the separately derived system from the source to the first system disconnecting means or overcurrent device.

At any single point

The grounding electrode conductor for a single separately derived system is used to connect the grounded conductor of the derived system to the system bonding jumper.

False


संबंधित स्टडी सेट्स

(Exam 1) Validity and Reliability

View Set

fundamentals of nursing Course Point Quiz- CH. 19

View Set

PSYC 100- LearningCurve 14a- Introduction to Personality and Psychodynamic Theories, Humanistic and Trait Theories

View Set

PATIENT MANAGEMENT: " Very Important File "

View Set