AFCI protection shall not be required for optional, dedicated outlets that supply equipment known to cause unwanted _____________ of AFCI devices.

Tripping

An insulated grounded conductor of 6 AWG or smaller shall be of a continuous white or gray outer finish.

True

Circuits for lighting and power shall not be connected to any system that contains trolley wires with a ground return.

True

Conductor sizes are expressed in American Wire Gage (AWG) or in circular mils.

True

Garages, and also accessory buildings that have a floor located at or below grade level not intended as habitable rooms and limited to storage to storage areas, work areas, and areas of similar use shall have GFCI protection.

True

The minimum number of branch circuits shall be determined from the total calculated _____ and the size or rating of the circuits used.

load

For live parts guarded against accidental contact, a minimum of __ ft. for 50 volts to 300 volts between ungrounded conductors.

8

Illumination of __ foot candles average, measured at the floor, shall be provided for all working spaces about service equipment.

10

GFCI protection shall be provided for lighting outlets not exceeding ___ volts installed in crawl spaces at or below grade level.

120

All ___-volt, single-phase, 15- and 20-ampere receptacles installed in the following locations shall have ground-fault circuit-interrupter protection for personnel.

125

Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity not less than the noncontinuous load plus ______ percent of the continuous load.

125

Decks or porches located at grade level with an area of less than _____ sq. Ft. are not required to have an additional receptacle installed.

20

At least one receptacle outlet shall be installed at each island countertop with a long dimension of _____ in. or greater and a short dimension of 12 in. or greater.

24

A load where the maximum current is expected to continue for __ hours or more.

3

As used in this subsection an Alcove is an area extending from, and returning to, the common wall of hallways, foyers, entries, and landings with a depth of not less than 2 ft. and a length of not less than ___ ft.

3

For ranges of 8 3/4 kW or more rating, the minimum branch-circuit rating shall be ____ amperes.

40

Each branch circuit disconnect rated 1000 A or more and installed on solidly grounded wye electrical systems of more than 150 volts to ground, but not exceeding ____ volts phase-to-phase, shall be provided with ground-fault protection of equipment in accordance with the provisions of 230.95.

600

Where connected to a branch circuit having a rating in excess of 20 amperes, lampholders shall be of the heavy-duty type. A heavy-duty lampholder shall have a rating of not less than ______ watts if of the admedium type, or not less than 750 watts if of any other type.

660

Where equipment rated ____ A or more that contains overcurrent devices, switching devices, or control devices is installed in structures other than one- and two-family dwellings and individual multifamily units.

800

Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. The marking shall be of sufficient durability to withstand the ____________ involved.

Environment

AFCI protection shall not be required for branch circuits that serve an appliance that is easily moved or that is fastened in place.

False

Fault-current values provided by the serving utility may not be used to satisfy the labeling requirements.

False

For available fault current, modifications are adopted by the State of Oregon.

False

For branch circuit extensions or modifications of dwelling units and dormitory units, extensions or modifications of existing circuits shall require the installation of AFCI protection.

False

Guest rooms and suites that are provided with permanent provisions for cooking shall not have branch circuits installed to meet the rules for dwelling units.

False

The permit holder is required to be demonstrate compliance 110.14 (D).

False

Where the load is calculated on the basis of volt-amperes per square meter or per square foot, the wiring system up to and including the branch circuit panelboard(s) shall be provided to serve less than the calculated load.

False

In dwelling units, alcoves shall have at least one receptacle installed. These outlets shall be in addition to the required _______ outlets.

Hallway

AFCI protection shall not be required on branch circuits supplying receptacles located in hallways, __________ or laundry areas and GFCI protected receptacles installed in dining rooms.

Kitchens

Are foyers part of 210.52(E)(I)?

No

Kitchen dishwasher branch circuits require GFCI protection for its outlets.

Not adopted by the State of Oregon

If a disconnecting means is required to be lockable _____ elsewhere in this Code, it shall be capable of being locked in the open position.

Open

For mounting and cooling of electrical equipment, wooden plugs driven into holes in masonry, concrete, ______, or similar materials shall not be used.

Plaster

Branch circuits recognized by this article shall be permitted as multiwire circuits. A multiwire branch circuit shall be permitted to be considered as multiple circuits. All conductors of a multiwire branch circuit shall originate from the _____ panelboard or similar distribution equipment.

Same

In existing electrical installations, when a service change or upgrade occurs, an existing metal underground water pipe shall not be used unless the metal underground water pipe has been verified as ______ for continued use as a grounding electrode.

Suitable

Fault-current values provided by the serving ______ may be used to satisfy the labeling requirements.

Utility

Is GFCI protection required for a single receptacle serving an appliance if the appliance is located within a dedicated space, in normal use the appliance is not easily moved or is fastened in place, the appliance is cord-and-plug connected, and if the receptacle is labeled as "not GFCI protected."

Yes


संबंधित स्टडी सेट्स

Bio 2 FINAL exam review (mastering)

View Set

ACC 131 Exam (Chapters 7, 8, 9) Thomas

View Set

AP Econ Fall Final Review Unit 1

View Set

Principles Of Biology Midterm Practice

View Set

Chapter 5: Activity-Based Costing and Activity-Based Management

View Set

World History; 1945-Present Timeline

View Set

Measuring Techniques/6 Parts of a Well Written Recipe

View Set