electrical Electrical - Conductors !
The square mil area of a conductor that is 0.250" on all sides is ___ square mils. a. 55,000 b. 62,500 c. 75,600 d. 80,200
62,500
All of the following are standard ratings for fuses except: a. 600A b. 601A c. 650A d. 700A
650A
The diameter (in inches) of a conductor with a diameter of 60 mils is a. 0.02" b. 0.04" c. 0.06" d. 0.08"
0.06"
What is the total resistance of a two-wire circuit that spans a distance of 200' each way, if the resistance per 1,000' is 1.21 V? a. 0.245V b. 0.266V c. 0.310V d. 0.484V
0.484V
What is the total resistance of a two-wire circuit that spans a total distance of 1,650 each way, if the conductor resistance is 0.148V per 1,000'? a, 0.3662V b. 0.484V c. 0.5342V d. 0.8764V
0.484V
Which of the following is the U. S. standard for measuring wires? a. NEMA b. NEC c. AWG d. ANSI
AWG
You would find Information on conductor applications and descriptions of insulation types in: a. NEC Table 310.15(B)(2)(a) b. NEC Table 310.13(A) c. NEC Table 310.16 d. NEC Chapter 9, Table 8
NEC Table 310.13(A)
Which of the following is not a consideration when determining the size of the conductor required to connect an electrical load to the source of supply? a. Number of strands b. Permissible voltage drop c. Total length of the conductor d. Type of wire
Number of strands
The constant (K) for the resistance of ordinary copper is____ per mil foot. a. 12.9 ohms b. 21.2 ohms c. 1.732 ohms d. 3.141 ohms
12.9 ohms
Which of the following conductors has the largest diameter? a. No. 1 AWG b. No. 12 AWG c. No. 3/0 AWG d. 250 kcmil
250 kcmil
The recommended maximum voltage drop for power, heating, and lighting loads is ______. a. 1% b. 2% c. 3% d. 4%
3%
To keep the voltage drop of a 120V circuit to a maximum of 3%, the maximum voltage drop allowed would be ? a. 3.6V b. 5.6V c. 6.2V d. 7.2V
3.6V
The recommended maximum voltage drop for conductors, feeders, and branch circuits combined is ____. a. 3% b. 5% c. 7% d. 9%
5%
Each of the following is a standard configuration for stranded wire except: a. 5-strand b. 7-strand c. 19-strand d. 37-strand
5-strand
To keep the voltage drop of a 240V circuit to a maximum of 3%, the maximum voltage drop allowed would b. a. 3V b. 5.4V c. 6.2V d. 7.2V
7.2V
The physical properties of a No. 4/0 copper conductor would be found in ____. a. NEC Table 310.16 b. NEC Chapter 9, Table 8 c. NEC Chapter 9, Table 1 d. NEC Table 310.13(A)
NEC Chapter 9, Table 8
Of the following, the largest standard AWG wire size is: a. No.3 AWG b. No.1 AWG c. No. 1/0 AWG d. No. 4/0 AWG
No. 4/0 AWG
What site wire is approximately double the cross- sectional area of No. 4 AWG? a. No.1 AWG b. No.16 AWG c. No.4 AWG d. No.2 AWG
No.1 AWG
All things considered, the most Ideal conductor is made of: a. bronze b. brass c. aluminum d. copper
copper
A continuous load as best described as one in which the maximum current is expected to continue for_____ hour(s) or more. a. one b. two c. three d. four
three
The normal location to provide overcurrent protection in an electrical circuit is ____. a. at the outlet b. where the conductor receives its supply c. where the conductor terminates d. at the last point in the circuit
where the conductor receives its supply
An acceptable method of identifying grounded conductors larger than No.6 AWG is marking them _____ or tagging them. a. white b. green c. black d. blue
white
A branch circuit is best described as: a. the circuit conductors between the service equipment and the final branch circuit overcurrent device b. the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s) c. a conductor tapped onto another conductor d. two conductors run in parallel
the circuit conductors between the final overcurrent device protecting the circuit and the outlet(s)
Use NEC Table 310.16 to find the maximum ampacity for a No.2 AWG copper wire at 90C (assume THHN insulation). a. 95A b. 110A c. 130A d. 150A
130A
The rating of a branch circuit Is determined by the: a. type and size of the branch circuit conductors b. rating of the branch circuit overcurrent device c. total connected load d. characteristics of the supply circuit
rating of the branch circuit overcurrent device