Electrical Level Three -Mod one

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

NEC Article 210.19

Branch circuit conductors are required to be sized with an ampacity rating that is no less than the Max. load to be carried

Per NEC Article 240.4

Branch circuit overcurrent protection is required to have a rating or setting not exceeding the rating in this code for Conductors,

NEC Article 210.3

Branch circuits are rated by the maximum rating or setting of thr overcurrent devices

NEC Section 210.14

Provides 2 options for calculating branch circuit loads for show window lighting; either using the computed receptacle old of 180VA per receptacle, or computing the load at 200VA per linear foot of show window

NEC Article 210.2

Provides a listing of other code articles for specific-purpose branch circuits.

NEC Sections 210.11(C) and 210.52(F)

Require the installation of at least one receptacle to supply laundry equipment

NEC Sections 210.11(C)(1) and 210.52(B)

Requires at least 2 20A small appliance branch circuits to be installed to supply receptacles installed in kitchen, pantry, breakfast rooms, and dining rooms

NEC Section 210.62

Requires that at least one 125 V single phase, 15A or 20A receptacle outlet be installed directly above a show window for 12 linear feet of window, or major fraction thereof

NEC Section 220.52(A)

Requires that the feeder load be computed at 1,500VA for each required small appliance branch circuit

NEC Sections 220.52(B)

Requires that the feeder load be computed at 1,Load1= Length x Load Amp500VA for each laundry circuit

NEC Chapter 9 Table

Resistance table for Solid Conductors

180VA

Per NEC Section 220.14(I), each outlet is assigned a load of _______.

Noncontinuous Load

Ampacity is 125% of the continuous load before the application of any adjustment or correction factor per NEC Section 210.19(A)

NEC Article 430

Applies to branch circuit supplying only motor load

NEC Article 440

Applies to branch circuits supplying only air conditioning equipment, refrigerating equipment, or both

Continuous load

Are loads that are calculated at 125% of the maximum current rating of the load

125%

Branch Circuits may supply noncontinuous loads, continuous loads, or both. Per NEC Section 210.20(A), the branch circuit rating shall not be less than the noncontinuous load plus ______ of the continuous load

NEC Article 210

Covers branch circuits ( except for branch circuits that supplies only motor loads).

NEC Article 240.3

For Equipment, and

NEC Article 210.21

For Outlet devices including lampholders and receptacles

VD Derating for 3-Phase Circuits

Formula1 VD =(1.732 x L x R x I)/1000 Formula2 VD =(1.732 x L x K x I)/ CM

Continuous load

Is a load whose max current is expected to continue for 3 hours or more

Utilization Equipment

Is defined by NEC as an equipment that utilizes electrical energy.

Single-Phase Branch Circuit Max Load

Is determined by multiplying the rating or setting of the overcurrent protection device (circuit breaker or fuse) by the circuit voltage MaxLoad =Amperage x Voltage

Load Center Length (L)

Load1= Length1 x Load Amp1 Load2= Length2 x Load Amp2 Load3= Length3 x Load Amp3 Total Load = Load1 + Load2 + Load3 Total Load Amp = Load Amp1 + Load Amp2 + Load Amp3 Load Center Length(L)= Total Load / Total Load Amp

Three-Phase Branch Circuit Max Load

Max Load =Amperage x Voltage x 1.732 (Square Root of 3)

3VA/sq ft

The unit lighting load for a barber shop, and a store also

1/4 VA/sq ft

The unit lightng load for a warehouse

NEC Table 310.15(B)

To check on THWN and THHN conductors @ 75 deg C

NEC Chapter 9 Table 8

To look up resistance for # 8 Conductor

Voltage Drop

VD = (2 x L x K x I) /CM

None (0)

What is the number of small appliance branch circuit may serve more than one kitchen?


संबंधित स्टडी सेट्स

Digital App: Binary Numbers, Bits and Bytes

View Set

Delgado-Econ 201 Chapter 1 Questions

View Set

Pharmacology Ch. 19 Introduction to Nerves and the Nervous System

View Set