Transformer connections

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

True

A lighter transformer can be found in a bank with a Delta secondary (T/F)

Wye

A service voltage of 120/208 is provided by what transformer connection?

4 WYE-WYE WYE-Delta Delta-WYE Delta-Delta

A three phase transformer can be connected in how many different combinations?

Service voltage of the customer

The secondary connection is determined by the ....

Than the neural to hot leg voltage

The voltage between the neutral and the power leg is 1.73 times greater than what?

Power leg

This can be known as the high leg, wild leg, or stinger leg.

Power transformers

Transformers that share somewhat equal portions of single phase and three phase load and smaller than the lighter transformer

WYE- Delta bank

Transformers with two primary bushings must be used for this type of connection because the Wye point is floated.

- all three transformers can share the single phase load equally - they can be built using single or dual primary bushing transformers

WYE connected banks have two main advantages...

If the primary coil voltage ratings of the transformers match the phase to phase voltage of the system, connect Delta

What is the Delta primary connection rule?

Grounding strap must be removed, x2 must be insulated

When banking pad mounted transformers, what needs to be done?

False

When paralleling the coils connect the AC and BD pair to x1 and x3? (T/F)

Alley Cay Bad Dog The A and C ends connect to one secondary bushing, and the B and D ends connect to another secondary bushing

When paralleling the coils internally, how should it be connected?

Three phase

When supplying three-phase power from underground systems, the transformers used are ____________ transformers

Wye-Delta

Which connection requires the primary WYE point to be floated?

Because it is not grounded

Why is floating the WYE hazardous to the lineworker?

X3

On a WYE-WYE bank which secondary lug is usually left idle?

If the primary coil voltage ratings of the transformer match the phase to neutral voltage of the system, connect WYE

What is the WYE primary connection rule?

Delta

What type of bank is this used for?

False

A lighter transformer can be found in a bank with a Wye secondary (T/F)

Open WYE-Open Delta

Although banking transformers in an underground system is rare, some utilities install __________ -__________ banks using two single phase pad-mounted transformers

Yes With a wye transformer connection Remember: secondary coil arrangement must be parallel

Can a bank of 120/240 volt transformers provide 120/208 volt three phase service? How?

False

Delta secondaries allow all three transformers to share the single load equally (T/F)

True one transformer must provide the majority of the lighting load

Delta secondaries do not allow all three transformers to share the single load equally (T/F)

By comparing the primary coil voltage rating of the transformer with the system voltage

How is the primary connection determined?

Delta only

If a transformer has only one number for a primary coil voltage, how should it be connected?

Yes

If one transformer is damaged in a WYE delta bank can this be connected in a open bank to still provide 3 phase service?

Connected WYE

If the phase to phase voltage of the service needed is 1.73 times the phase to neutral voltage of the service needed, how should the secondary be connected?

Connected Delta

If the phase to phase voltage of the service needed is 2 times the phase to neutral voltage of the service needed, how should the secondary be connected?

Either a turns ratio test or a physical check by taking the lid off

If you don't know the configuration of your coils ( parallel or series) how can you check?

True

Lineworkers who understand transformer banking know that determining the primary connection is a separate consideration that determining the secondary connection (T/F)

120 volts

One a typical 120/240 volt single phase transformer, When the two secondary coils are connected together in parallel inside the tank, the the secondary voltage will be ...

120/240 volts

One a typical 120/240 volt single phase transformer, When the two secondary coils are connected together in series inside the tank, the the secondary voltage will be ...

If there is a primary system disturbance or load imbalance this will subject the transformer to SEVER overloading

What is the danger of grounding the WYE point of a WYE-Delta?

If one transformer fails, the customer is down to one phase until the defective transformer is fixed or replaced

What is the disadvantage of a WYE connected bank?

Corner ground

What is used when customers need only three-phase three-wire services

Corner ground

What is used when the NESC still requires a ground reference on a three phase system without needing to install a neutral conductor

WYE

What type of bank is this used for?

The proper voltage would still be delivered, but the kVA rating of the bank would be cut in half

What would happen if WYE secondaries were connected but the coils were series?

Floated (not grounded)

With a WYE - Delta bank, each transformer is connected to the system and the Wye point is...

One hot leg on the secondary side to deliver three phase power

With a WYE-WYE bank, each of the three transformers provide....

No

With a WYE-WYE bank, will an open bank provide three phase power if the secondary were connected open WYE?

Parallel

_________ the secondary coil when making WYE secondary connections

A ground is attached to the winding midpoint of one of the transformers

A power leg only exists on Delta and open Delta secondaries when .....