Turner rmo
Water pressure
1 foot of water = 0.433 psi 1 psi 2.31 ft of water.
Tons of cooling
1lb of ice will absorb 144 BTU's as it melts. 1 ton of ice (2000 lbs) will absorb 144 x 2000 = 288,000 BTU's. 24 hours = 288,000 BTU's a day. 60 mins = 12,000 BTU's an hour. 1 min = 200 BTU's a day.
Refrigerant type high pressure
A refrigerant which must be used in a vessel above atmospheric pressure.
Refrigerant type low pressure
A refrigerant which must be used in a vessel below atmospheric pressure. A refrigerant which must be used in a vacuum.
Types of condensers
Air-cooled condenser and water-cooled condenser
Water cooled condenser
Capable of achieving lower head pressures. Can be used on medium to large-sized machines
Non mechanical metering device
Capillary tube. Orifice plate.
Types of non positive displacement compressors
Centrifical
Air-cooled condenser
Cheaper. Less cleaning. Can be used on small to medium-sized machines
Compound gauge
Combination of a vacuum gauge and a pressure gauge. Measures vacuum in inches of mercury. Measures pressure above atmospheric in psig.
Subcooling
Cooling the liquid refrigerant below its saturation point temperature at which it is condensed 211 degrees Fahrenheit water is 1 degrees subcooled
Water-cooled condenser types
Cross flow period. parallel flow. Counterflow
Fouling water tubes
Depositing of sediment from condenser water onto condenser tubes or coil insulation. Results in less heat transfer between cooling condenser water and refrigerant. Causes high head pressure
Red litmus paper
Detects ammonia leaks. Turns blue
Nessler solution
Detects ammonia leaks. Turns yellow
bromothymol Blue
Detects carbon dioxide leaks. Turns yellow
Evaporator high side system
Discharge pressure. Condenser pressure. Head pressure
Flash gas
Evaporation of a small amount of liquid refrigerant as it passes through the metering device. Cause of liquid refrigerants temperature drop from the high temperature in the liquid line to the low temperature in the evaporator
Reciprocating system components major components
Evaporator. Compressor. Condenser. Metering device. Piping.
Evaporator function
Exchange heat between the refrigerant and the load
Disadvantages of a flooded evaporator
Far greater amount of refrigerant required. Leaks are harder to find
Heat
Form of energy. Transferred from one place to another. Can't be seen. Is measured by its effects on substances.
Frost
Frozen condensation. Frost insulates DX coils and prevents proper heat transfer. Frost can result in low suction pressure
New York City refrigerant classifications
Group one non-toxic non flammable CO2, r - 11, r - 12. Group 2 toxic ammonia. Group 3 flammable butane , Ethylene
Evaporator
Heat exchanger which absorbs heat to evaporate or boil low pressure liquid refrigerant into low-pressure vapor.
Sensible heat
Heat that can be measured with a thermometer. Change in temperature, not change in state.
Latent heat
Heat which causes a change in physical state. Solid to liquid.(fusion/melting) Liquid to vapor.(vaporization) Vapor to liquid.(condensation)
Superheat
Heating Vapor refrigerant above its saturation point temperature at which it is evaporated. 213 degrees Fahrenheit steam is one degree superheated
Ashrae refrigerant classifications
High flammability A3 , B3. Low flammability A2, B2. No flammability A1, B1.
Refrigerant qualities
How much heat does it absorb per pound. How much heat can it absorb after it passes through the metering device. Is it toxic. Is it flammable. How easy is it to detect leaks. At what temperature will it break down. At what pressures must it be used at.
1 lb of ice
Ice = 0 °F - 32°F. Water= 32 °F - 212 °F. Steam= 212 °F - 220 °F.
Automatic expansion valve disadvantages
If load increases, evaporator will starve. If load decreases, evaporator will be flooded
Tev problems
If opening force ( bulb pressure) is lost; evaporator will be starved. If closing force (spring or back pressure) is lost; evaporator will be flooded. If sending bulb insulation falls off; evaporator will be flooded. If sensing bulb is installed in wrong location; evaporator will be starved.
Low side float disadvantages
If the float is punctured the evaporator will flood. If the vapor connection is blocked it will not properly feed the evaporator
High side float disadvantages
If the float is punctured the evaporator will starve. If too much refrigerant is in the system this valve will not close flooding the evaporator
Charles law
If the temperature of a gas or vapor goes up and the gas or vapor cannot expand, the pressure will go up. If The volume of a gas or vapor is reduced the pressure and temperature will go up.
Dalton's law of partial pressures
If two separate vapors are contained in the same vessel their separate pressure will accumulate.
High head pressure
In extreme cases can cause the condenser vessel to rupture or explode. More often will cause Refrigeration machine control to turn compressor off which will leave the building with no Cooling. Can cause pressure relief valve to open which releases refrigerant outside of machine which is bad
Non positive displacement compressor
Increases the pressure of the refrigerant Vapor by rapidly accelerating then decelerating it. Also called Dynamic compression
Positive displacement compressor
Increases the pressure of the refrigerant Vapor by reducing its volume
Mechanical metering device
Manuel metering device. Low side float. High side float. Automatic expansion valve. Thermostatic expansion valve (txv).
Measuring sensible heat
Measured with thermometers Fahrenheit or celsius. Fahrenheit - 32 °F ÷ 1.8 = Celsius. Celsius × 1.8 + 32 °F = Fahrenheit.
Pressure gauge
Measures pressure above atmospheric pressure (14.7 psi). Readings are in psig instead of PSIA. Psig + 14.7 psi = PSIA.
Barometer
Measures pressure in inches of mercury.
Pressure gauge
Measures pressure in pounds per square inch.
Starving the evaporator
Metering device sending inadequate amount of refrigerant to the evaporator to cool load
Flooding the evaporator
Metering device sending too much refrigerant to the evaporator endangering the compressor float comparison.
Feeding the evaporator
Metering device supplying liquid refrigerant to the evaporator in response to the load
Feeding the evaporator
Metering device supplying low pressure liquid refrigerant to the evaporator in response to the load. The load increases if there is more refrigerant sent to the evaporator. Low decreases if there is less refrigerant sent to the evaporator
Low side system
Metering device to Inlet of compressor. Suction pressure. Evaporator pressure. Back pressure.
Humidity
Moisture in ambient air. Air temperature determines the amount of moisture it can hold. Warmer air holds more moisture colder air holds less
Condensation
Moisture that has condensed from ambient air
Condenser Water Supplies
Natural bodies of water which are rivers lakes Wells and water regulating valve. Recirculated water. Cooling towers in water recirculating condensers
Refrigerant safety
Never handle refrigerant or equipment with bare hands. Always make sure equipment is leak checked. Toxic or flammable refrigerants can be detected by a refrigerant monitor. Machine rooms must have mechanical ventilation which removes refrigerant paper if there is a leak.
Halide torch
No leak turns blue. Small leak turns green. Big leak turns dark blue. Restriction inline turns yellow
Two types of metering device
Non mechanical and mechanical
Dry type evaporator
Only contains enough refrigerant to satisfy the load. When the load increases more refrigerant is needed. When the load decreases less refrigerant is needed. Example direct expansion DX coil
Thermostatic expansion valve
Opening force = bulb pressure. Closing force = spring pressure. Closing force = evaporator pressure
Automatic expansion valve (constant pressure valve)
Opening force = spring pressure. Closing force = evaporator pressure
High side system
Outlet of compressor to Inlet of metering device. Discharge pressure. Condenser pressure. Head pressure.
Chapter 2
Pressure
Engineer tools
Pressure / temperature conversion chart. Standard ton conditions chart. Refrigerant classifications.
Vacuum
Pressure inside vessel which is below atmospheric pressure. Pressure below 14.7 PSIA.
Barometric pressure
Pressure measured with a barometer. Also an absolute pressure. 1 hg barometric = 0.491 psia. 1 psi = 2 hg barometric.
Atmospheric pressure
Pressure of the air around us. Equal to 14.7 pounds per square inch(psi) at sea level. Equal to 29.92 inches of mercury(30hg).
Absolute pressure
Pressure which starts at 0
Types of positive displacement compressor
Reciprocated. Rotary. Screw. Scroll
Indirect refrigeration system
Refrigerant in the evaporator coils a secondary refrigerant such as chilled water or brine which then cools the load. Disadvantages. Requires more system components and piping
Direct refrigeration system
Refrigerant in the evaporator coils the load directly. Direct expansion coil DX coil. Disadvantages. Far greater health hazard when leaking
Horizontal Shell & tube evaporators
Refrigerant is in the shell chilled water is in the tubes. Liquid enters the bottom Vapor exits the top. Eliminators prevent liquid from entering compressor. Chilled water return from building is usually 55 degrees Fahrenheit. Chilled water supply to building is usually 45 degrees Fahrenheit
Compressor function
Remove Vapor refrigerant from the evaporator. Maintain the pressure on the low side of the system so that refrigerant in the evaporator can boil at a low temperature. Maintain the pressure on the high side of the system so that the refrigerant in the condenser can condense at a high temperature
Condenser function
Remove the heat of compression added by the compressor
Lower head pressure
Results in less pressure differential which is the difference between high and low side of machine. Low pressure differential will cause an adequate amount of liquid to be supplied to low side of machine which is the evaporator
Three types of direct expansion coils
Single row coil Multi-role coil. Finned multi-role coil
Evaporator low side system
Suction pressure. Evaporator pressure. Back pressure
Saturation point
Temperature at which a liquid or vapor will change state. Water boils at 212 °F at atmospheric pressure (14.7 PSIA). Water will boil at a higher temperature if The pressure is greater than 14.7 PSIA. Water in a pressure cooker boils at temperatures above 212 °F due to the higher pressure.
Condenser
The heat exchanger in which the removal of heat causes high pressure Vapor to condense and liquify into a high pressure liquid
Dew point
The temperature below which moisture in ambient air will condense. Cold DX coils dehumidify and remove moisture from ambient air
Refrigeration
Transfer of heat. Heat is removed from load. Heat is transferred to a space.
Btu
Unit of measuring heat. Amount of heat that will change the temperature of 1 pound of water 1 degree Fahrenheit.
Water regulating valve
Used to maintain a constant head pressure. Used when the condenser water is taken from a natural water supply such as Lake Pond or well when a constant water temperature is unattainable. Varies amount of water and response to head pressure
Vacuum gauge
Vacuum to PSIA: vaccum - 30 = PSIA. Reads like barometer in reverse
Flooding the evaporator
When a metering device said too much refrigerant to the evaporator for the load to boil. Can be caused by the metering device being stuck open
Starving the evaporator
When a metering device sends too little refrigerant to the evaporator to cool load. Can be caused by restriction blocking flow through the metering device or liquid line
Saturated
When a substance while changing State exist as both liquid and vapor. Water boiling at 212 degrees Fahrenheit is saturated
Disadvantages of dry evaporators
When flooded there is a high risk of liquid refrigerant entering the compressor. Far lower cooling capacity
Liquid seal
When the level of liquid refrigerant in the condenser or receiver is high enough to ensure that only high pressure liquid is entering the liquid line
Loss of liquid seal
When the level of liquid refrigerant is in the condenser or receiver to allow high-pressure Vapor to enter the liquid line
How cooling tower works
971 pounds of 90 degrees Fahrenheit water are sprayed into the cooling tower. One pound of water evaporate which absorbs 970 BTU's here another 1 BTU per pound is 1 degree Fahrenheit when the water leaves the cooling tower it is 89 degrees Fahrenheit
How cooling tower works again
98 pounds of 90 degree Fahrenheit water are sprayed into the cooling tower. One pound of water evaporates which absorbed 970 BTU's. 970 BTUs divided by 97 pounds equals 10 BTU's per pound 10 BTUs per pound equals 10 degrees Fahrenheit temperature drop. Water leaves the cooling tower at 80 degrees
Refrigerant
A fluid which is used for the transfer of heat inside a refrigeration machine. Most refrigerants behave similarly to water in that: They have a freezing and boiling point. They're boiling point changes depending on the pressure applied to it.
Pressure
A force which is applied to a surface or object.
Flooded type evaporators
Always contains a large amount of liquid refrigerant regardless of load. As the load increases more liquid is boiled. As the load decreases less liquid is boiled. Example horizontal Shell & tube evaporator
Latent heat of evaporation
Amount of BTU's a pound of liquid refrigerant can absorb while evaporating.
Refrigerating effect
Amount of BTU's a pound of refrigerant can absorb after passing through the metering device.
Specific heat
Amount of BTU's needed to change to temp of 1 lb of water to 1 °F. Specific heat of water = 1. Specific heat of ice =0.5. Specific heat of steam = .5
Restriction
An obstruction which slows the flow of fluid. Restricting the flow of liquid refrigerant causes a decrease in pressure.
High side float
Attached to condenser. Supplies more refrigerant as it is liquefied in the condenser
Low side float
Attached to the evaporator. Supplies more refrigerant as it is boiled in the evaporator.
Metering device
The component which returns the high pressure/high temperature liquid to a low pressure/low temperature liquid for reuse in the evaporator.