UNIT 28-3 PHASE TRANSFORMERS

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

Which of the following are considered "triplen" harmonics?

3rd, 9th, 15, 21st

Three phase vs single phase loads

3 phase transformer connections (ideal conditions occur when connecting to a well balanced 3 phase load)

A 3-phase transformer bank has the secondary connected in a wye configuration. The center-tap is used as a neutral conductor. If the voltage across any phase conductor and the neutral is 120 volts, how much voltage would be applied to the 3-phase load connected to the secondary of this transformer bank?

208

A 3-phase transformer connection has a delta-connected secondary, and one of the transformers has been center-tapped to form a neutral conductor. The phase-to-neutral value of the center-tapped secondary winding is 120 volts. If the high leg is connected to a single-phase load, how much voltage will be applied to that load?

208

A 3-phase transformer connection has a delta-connected primary and a wye-connected secondary. The center tap of the wye is used as a neutral conductor. If the line-to-line voltage is 480 volts, what is the voltage between any one phase conductor and the neutral conductor?

277

What is the frequency of the 2nd harmonic?

120 hertz

A 3-phase transformer bank has the primary and secondary windings connected in a wye configuration. The secondary center tap is being used as a neutral to supply single-phase loads. Will connecting the center-tap connection of the secondary to the center-tap connection of the primary permit the secondary voltage to stay in balance when a single-phase load is added to the secondary?

yes

A positive-rotating harmonic is more harmful to an induction motor than a negative-rotating harmonic.

False

An open-delta 3-phase transformer system has one transformer center-tapped to provide a neutral for single phase voltages. The voltage from the line to center tap is 277 volts. If a single phase load is connected across the two line conductors and a neutral of the transformer, and one of the lines has a current of 80 amps the other line has 68 amps, The total current flowing in the neutral is 148 amps.

False

Construction of a 3 phase transformer

Three single phase transformers wound on a single core.

Scott connection

Used to convert 3 phase power to 2 phase. Using two single phase transformers

A 22.5 kVA single phase transformer is tested with a true-RMS ammeter and an ammeter that indicates the peak value. The true-RMS reading is 94 amps.The peak reading is 204 amps. Should this transformer be derated?

Yes


संबंधित स्टडी सेट्स

BIO201 Exam 2: Practice Questions

View Set

Developmental Psychology Final - NYU UG Psychology (Aalai, Fall 2022)

View Set

power point questions foundations

View Set

A The nature of management, B Strategic management & planning, C Organizational structure and design, D Culture, E Networking, F Motivation, G Individual decision making, H Group DM, I Leadership, J Organizational Change, K Issue/selling, Team group...

View Set

Maternity Chapter 10: Complications of Pregnancy

View Set