Conduit Installation Requirements

Lakukan tugas rumah & ujian kamu dengan baik sekarang menggunakan Quizwiz!

EMT shall be securely fastened in place at intervals not to exceed _______. In addition, each EMT run between termination points shall be securely fastened within ___________ 0f each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination.

10' - 3' - 358.30 (A)

The minimum radius for 3-1/2" conduit using a one-shot bender is ____________

15"

What code article covers the minimum requirements for the installation of direct buried cable, conduit or other raceways to meet minimum cover requirements?

300.5 (Table)

The NEC specifically states that no more than ______________ may be made in any one conduit run between out let boxes, cabinets, panels, junction boxes, or pull points.

360°

The minimum radius fo MD91 conduit using a one-shot bender is __________

381mm

A cable, raceway, or box, installed in exposed or concealed locations under metal-corrugated sheet roof decking shall be installed and supported so that there is not less than ___________ measured from the lowest surface of the roof decking to the top of the cable, raceway, or box. List your code article _________

38mm - 1-1/2" NEC 300.4 (E)

What is the maximum size of (EMT) conduit? Code Article__________

4" - 358.20 (B)

How much expansion is there on PVC conduit with a 100 degree change in ambient temperature? _________ Code article __________

4.06" - 352.44 (Table)

The law stating that the direct current flowing in a conductor is directly proportional to the potential difference between its ends is?

A. Faraday's Law

Where raceways contain 4 (AWG) or larger insulated circuit conductors, and these conductors enter a cabinet, a box, an enclosure, or a raceway, the conductors shall be protected In accordance with ___________________? What code article?_______

C. 300.4 (G)

The type of bend used where the conduit enters the panelboard is most likely a(n) __________

Offset

______________Are not required to comply with 300.4(E)

Rigid and intermediate metal conduit NEC 300.4(E) (Exception)

The number of conductors shall not exceed the permitted by the percentage fill specified in? ___________ Code Article? _________

Table 1 Chapter 9 - 358.22

Raceways may be used as a means of support.

True 300.11 (C)

Can EMT be used as a grounding conductor?

Yes - 358.60


Set pelajaran terkait

Chapter 18 - Short Term Finance and Planning

View Set

Ch 6: Diagnostic Tests: Medical Office Pro 3rd Edition

View Set

Psychology: Thinking and Intelligence

View Set

PrepU ch.18 assessing mouth, nose, throat, and sinuses

View Set

Unit 3: Chapter 4 Physics 1 Quizzes

View Set

Word Choice, Diction and Language Types

View Set

Income Tax Exam 1 - Smartbook Questions

View Set