NYC MASTER ELECTRICIAN EXAM
Communication circuits shall have a minimum grounding conductors of ____AWG.
#12 AWG
In a healthcare facility, the maximum internal current permitted to flow through a line isolated monitor,when any point of the isolated system is grounded, shall be ____ .
1 milliamperes
In anesthetic,areas health care equipment frequently in contact with bodies of persons shall not exceed ____ volts.
10 Volts
Emergency lighting emergency power or both must be available in the building within a time not exceeding ____seconds
10 seconds
Lighting system operating at 30V or less shall not be installed within ____ feet of pools, spas, fountains, or similar locations.
10'ft
How many receptacle outlet are permitted on a 20A, 120V circuit in a commercial building?
13
The minimum clearance for overhead feeder conductors not exceeding 600V that pass over commercial areas subject to truck traffic is ____ feet.
18" feet
A limited care facility is an area used on a ____hour basis for the housing of four or more persons who are incapable of self-preservation because of age, physical limitation due to accident or illness, or mental limitations, mental illness, or chemical dependency.
24hr
Lighting system covered by Article 411 shall have a power supply rated not more than ——amps and not more than 30V.
25 amps
In the critical care areas of health care centers, each patient bed shall be provided with a minimum of ____ duplex receptacles
3 duplex (6 single)
Service conductors installed as unjacketed multiconductor cable shall have a minimum clearance of ____ windows that are designed to be opened, doors, porches, stairs fire escape or similar locations.
3 ft (36 inches)
Feeder and branch circuit conductors within ____ inches of a Ballast shall have an insulation temperature rating not lower than 90°C (194°F) unless supplying a luminaiere marked as suitable for a different insulation temperature
3 inches
Branch circuit conductors within ____inches of the ballast shall have an insulation temperature rating not lower it 90°C 194°F
3" inches
Fixed in place X-ray equipment properly supplied by a branch circuit rated at not over ____ amperes shall be permitted to be supplied through a suitable attachment plug cap and hard service cable cord.
30 Amps
The working space in front of the electric equipment shall not be less than ____ inches wide, or the width of the equipment, whichever is greater.
30" inches
The maximum voltage drop from service point to the last over-current device in a dwelling unit?
4%
AC or DC general use snap switches may be used for control of inductive loads not exceeding ____of the ampere rating of the switch at the applied voltage.
50%
The demand factor for marina load calculations of 45 shore power receptacles is ____%.
50%
What is the maximum run length of a 18AWG fixture wire that is tapped on to a 20A branch circuit?
50' ft.
The load for household electric clothes dryer's in a dwelling unit(s) shall be either ____ watts (volt-amperes) or the nameplate rating, which ever is larger, for each dryer served ?
5000 watts
Manufactured wiring systems constructed with type MC cable shall be supported and secured at intervals not exceeding ____ ft.
6 ft
Where internal combustion engines are used as the prime motor, an on site fuel supply shall be provided with an on premise fuel supply sufficient for not less than ____ hours full demand operation of the system
6 hours
For equipment rated 1200A or more and over 6ft wide that contains over-current devices, switching devices, or control devices, there shall be one entrance to and egress from the required working space not less than 24inches. Wide and ____ nches high at each end of the working space.
6'foot 6"inches (78" inches)
The minimum radius of a field bend on trade size 1 "1/4 RMC is ____.
8
Service drops Installed over roof shall have a vertical clearance of ____ above the roof surface, and unless a lesser distance is permitted by and exceptions
8'ft
Which of the following statements best describe the grounding requirement for central vacuum outlet
Accessible non current carrying metal parts are required to be connected to an equipment grounding conductor.
In healthcare facilities, patient bed receptacles located in general care areas shall be supplied by at least two branch circuits, which ____permitted to originate from two separate transfer switches on the emergency system
Are permitted
Wiring from an emergency source to emergency loads shall ____ ____ ____ ____ of all other wiring
Be kept entirely independent of all other wiring
Where skin effect exist the ferromagnetic envelope shall be bonded at ____.
Both ends
Knife switch rated for more than 1200 Amps at 250Volts or less
Can be used only as isolating switch, shall not be opened under load
—— Cartridge fuses of the renewable type shall be permitted to be used only for replacement in existing installation is where there is no evidence of over-fusing or tampering.
Class H
In a dwelling unit which appliance is allowed to have a 24"inch cord with Attachment ground plug ?
Combination range hood/microwave oven
Patient care areas of healthcare facilities ____ areas such as business offices, corridors, lounges ,day rooms, or similar areas
Do not include
Which flexible cable is Allowed to be used for electric vehicle charging station 300 Volts ?
EVJ
Which flexible cable is allowed to be used for a Electric Vehicle Charging Station?
EVJ
Automatic transfer switches shall be ____ operated and ____ held
Electrically operated and mechanically
The equipment system shall supply major electric ____ necessary for patient care and basic hospital operation
Equipment
The patient care area is any portion of the healthcare facility where patients are intended to be ____or ____.
Examined or treated
A hospital is a building or portion thereof used for medical, psychiatric,obstetrical , or surgical, care on a 24 hour basis of ____ or more patients
Four
Where a main bonding jumper or a system bonding jumper is a screw only the screw shall be identified with a ____ that shall be visible with the screw installed
Green finish
In a healthcare facility receptacles and attachment plugs in a hazardous (classified) location with an anesthizing area shall be listed for use in class I group ____ locations
Group C
Plug fuses a 15 amperes and lower rating shall be identified by a ____ configuration of the window, cap, or other prominent part to distinguish them from fuses of higher ampere rating
Hexagon
Type 3 Surge Protective devices can be installed on the load side of a branch circuit overcurrent device up to the equipment served.if ____ the type 3 SPD connection must be a minimum 30'ft of conductor a distance from the service or separately derived system disconnect
Included in the manufactures instructions
Where installed to reduce electrical noise for electronic equipment, electrical continuity of the metal raceways shall not be required and metal raceway can terminate a (an) ____ nonmetallic fitting or spacer on electronic equipment
Listed fitting
GFCI protection at a carnival is not required for equipment at circuit if the receptacle is of the ____type.
Locking
Class 2 and Class 3 circuits shall not be placed in any enclosure, raceway, cable, or similar fittings with conductors of Class 1 or electric light or power conductors, unless ____.
Separated by barrier
Each general care area patient bed location in a healthcare facility must be provided with four ____ or ____ duplex receptacles
Single or two
Track lighting with outlets in a bathroom is not allowed because ?
Track lighting has receptacle
Emergency circuit wiring shall be permitted to enter which of the following types of equipment with normal circuit wiring?
Transfer switches, exit or emergency luminaries supplied from two sources
Type ____ fuse adapters shall be designed so that once inserted in a fuse holder that cannot be removed
Type S fuse
Type ____ is multiconductor cable identified for use as underground service entrance cable.
Type USE cable
Emergency circuit wiring must be designed and located in such a manner so as to minimize the possibility of failure because of ____, ____, ____.
Vandalism,flood,fire.
Transfer eguipment, including automatic transfer switches,shall be
automatic, identified for emergency use , approved by the authority having jurisdiction
The essential electrical system in a healthcare facility shall be compromised of the
emergency system and the: equipment system
In anesthetic areas, low-voltage equipment that is frequently in contact with the bodies of persons or has exposed current-carrying elements shall
operate on an electrical potential of 10 volts or less,be moistur- resistant, be approved as intrinsically safe or double-insulated equipment.
Audible and visual signal devices for an emergency system shall be provided,where practicable, for the purpose(s) of indicating that
the battery is carrying load, derangement of emergency source, that the battery charger is not functioning
Locations were flammable anesthetics are employed are class I,Division I locations that shall extend
upwards to a level 5'ft above the floor