The red light on a CSP ? after the load decreases. Select one: a.blinks b.dims c.goes out d.stays on

D. Stays on

The secondary breaker of a CSP protects it from high voltage surges. Select one: True False

False

The emergency handle is sealed so it cannot be operated unless the seal is cut. Select one: True False

True

The primary fuse link of a CSP will operate at 8 to 14 times the normal current. Select one: True False

True

A broken signal light may be a source of ? . Select one: a.excessive secondary tripping b.radio noise c.reduced kVA capacity d.unnecessary voltage fluctuations

B radio noise

On a 25-kVA CSP carrying 180 amperes, the signal light will be energized after ? . Select one: a.2 hours b.3 hours c.6 hours d.8 hours

B. 3 hours

On a CSP transformer carrying 250 amperes that has tripped, using the emergency handle will give ? of power. Select one: a.3/4 hour b.1 1/4 hours c.1 1/2 hours d.2 hours

C. 1 1/2 hours

Once the emergency handle is used to restore service, the transformer will not have to be replaced as the emergency handle reset the transformer to a higher current value. Select one: True False

False

There is only one main breaker in a CSP transformer. Select one: True False

False

To close a CSP secondary breaker that has tripped, one must move the indicator to R and then back to ? . Select one: a.Clear b.Closed c.Normal d.Open

B. Closed

The primary link will remove a(n) ? faulted transformer from the system. Select one: a.externally b.ground c.internally d.secondary

C. Internally

The red light on a CSP comes on as the transformer ? . Select one: a.has tripped out due to overload b.is operating normally c.is reaching overload d.is shedding load

C. Is Reaching overload

The primary fuse in a CSP protects the ? from an internal fault. Select one: a.customer b.Qualified Electrical Worker c.system d.transformer

C. System

CSP transformers can be equipped with a ? to adjust the secondary voltage. Select one: a.breaker handle b.primary fuse link c.secondary breaker d.tap changer

D. Tap changer

A CSP will not carry the same amperage as a conventional transformer due to the additional internal equipment. Select one: True False

False

A CSP's primary lead should be taken offline before working on the secondary because the secondary might have enough capacitance to shock. Select one: True False

True

During a temporary overload, the signal light will come on but the transformer will remain in service. Select one: True False

True

The most commonly used CSP transformer in the electrical industry has two mounting brackets. Select one: True False

True

Under short circuit conditions, the red light and the secondary breaker will trip at the same time. Select one: True False

True

The emergency control handle on a CSP transformer should be used as a ? . Select one: a.method to permanently upgrade the transformer's capacity b.permanent fix to increased load c.temporary fix to a short circuit situation d.temporary fix to an overload situation

d.temporary fix to an overload situation


Related study sets

Chapter 6 Essentials of Cell Biology

View Set

BIOL-210 Intro to Body Organization

View Set

COJUSD Google Certified Student: Gmail (Espanol)

View Set

Safe State Food handler Certificate Program studyguide

View Set

PLC's-Programmable Logic Controllers Chapter 2

View Set

Religion part 2: Judaism, Christianity, Islam

View Set

Javascript 1: Language Fundamentals (chapter 8)

View Set