Electrical Journeyman Test

Ace your homework & exams now with Quizwiz!

What dimension defines a wall countertop or work surface in a kitchen ______inches wide or wider .

12

What is the maximum distance that a receptacle outlet can be mounted below the basin or basin countertop in a dwelling unit bathroom , ________inches

12

What is the maximum distance below the edge of a countertop that a receptacle can be mounted ? ______and shall not be located where the countertop or work surface extends more than _____ins beyond it's support base ?

12, 6. 210.52(C)(5)

Receptacles shall be installed such that no point measured horizontally along the floor line of any wall space is more than ____feet from the receptacle outline.

6. 210.65

Receptacle outlets located within ______ft of the top inside edge of the bowl of the sink shall be GFCI protected .

6. 210.8 (A)(7)

Receptacle outlets installed within ____ft of the inside edge of the bathtub or shower shall be GFCI protected ?

6. 210.8(A)(a)

In dwelling units receptacle outlets are required in a foyer if the foyer is at least ____sq ft and on every wall that is at least _____ ft wide ?

60, 3 210.52(I)

In a show window , at least ____125 volt , single - phase , 15 or 20 amp rated receptacle outlet shall be installed within ____inches of the top of the show window for each ______linear ft of show window area measured horizontally at its maximum width.

1, 18, 2. 210.62

In dwelling units , hallways of ____ ft or more in length shall have at least one receptacle .

10

What three items mentioned in the code defined a separation of a kitchen countertop space if the distance between these items that are orientated parallel to the wall and the wall is less than ______inches ?

12, range, counter-mounted cooking unit, sink

Is the lighting outlet required for crawl spaces not exceeding _____volts required to be GFCI protected?

120, yes. 210.8(E)

Receptacle outlets in or on the floors shall not be counted as part of the required number of receptacle outlets unless located within _____inches of the wall .

18 inches 210.52(A)(3)

Receptacles mounted along the wall space shall include any space ____feet or more in width (including floor line measured around corners ) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets that do not have _______or similar _______

2, countertops, work surfaces. (210.52(A)(2)(1)

A person has to be how many years old to obtain a Journeymans license?

20 PA 407 Art 339.5715 pg 22

In a kitchen , receptacle outlets shall be located on or above, but not more than_____inches above , the countertop or worksurface .

20. 210.52(C)(5)

What is the long dimension ( length ) and short dimension ( width ) that defines a peninsular countertop in a kitchen ? ______long _____short : Measured from the _____________?

24 inches, 12 inches, connected perpendicular wall. 210.52(C)(3)

What dimensions define an island countertop space ? At least ____long _____wide

24, 12 210.52(C)(2)

GFCI protection for outlets not exceeding _____volts that supply boat hoists installed in dwelling units shall be GFCI protected ?

240. 210.8(C)

A service receptacle used for maintenance on an air conditioner is to be installed a maximum of how many feet from the equipment and on the same level

25

Heating , Air - Conditioning and Refrigeration Equipment shall have a 125 - volt , single phase 15 or 20 amp receptacle outlet installed at an accessible location for servicing, said equipment and shall be located on the same level and within ____ft of the equipment? This receptacle outlet shall not be connected to the _______of the equipment disconnecting equipment means

25, load side. 210.63

At least one receptacle outlet shall be installed in bathrooms within 900 mm ______of the outside edge of each basin. The receptacle outlet shall be located on a wall or partition that is adjacent to the basin or basin countertop, located on the countertop, or installed on the side or face of the basin cabinet. And no case Shall the receptacle be located more than _____inches below the top of the basin or the basin countertop.

3 feet, 12 210.52(D)

A 400 amp ear service for a dwelling unit has what size wire?

400 kcmil. >100A use 75 <60 Art 310.15(7)(1)&310.15(B)(1)

Dedicated space above electrical panel, extends a distance of how many feet?

6 Art 110.26(E)(1)(a)

The highest point for an operating handle of a circuit breaker shall be how many feet in above the floor or working platform?

6 feet 7 inches 240.24(A)

The minimum, bending radius, for a one shot bend in 2 inch EMT conduit is?

9 1/2 inches C9T2

If a circle has a load of 40 A in a supply of 240 V, what is the power consumed?

9.6 kW. P=I*E

Holiday decorative lighting, cannot be installed for more than how many days?

90 Art 590.3(B)

Grounding Electrode

A conducting object through which a direct connection to earth is established.

Grounding Electrode Conductor

A conductor used to connect the system grounded conductor or the equipment to a grounding electrode or to a point on the grounding electrode system. GEC

Bonding conductor or jumper

A reliable conductor to ensure the required electrical conductivity between metal parts required to be electrically connected.

Separately Derived System

An electrical source, other than a service, having no direct connection(s) to circuit conductors of any other electrical source other than those established by grounding and bonding connections.

Separately Derived System

An electrical source, other than a service, having no direct connection(s) to circuit conductors of any other electrical source other than those established by grounding and bonding connections. (Ex. Generators batteries converter windings transformers.)

Can a baseboard heater be mounted below an existing receptacle outlet ? a . No b . Yes c . No , only if there inches of clearance d . Yes , only if the unit is has instructions that would permit that installation

D

Which article contains installation and other requirements for generators.

Article 445

Receptacles in crawl spaces of dwelling units shall be GFCI protected if the space is_____or ____grade level ?

At, below. 210.8(A)(4)

Outdoor outlets ; Balconies , decks and porches that are _________to the dwelling unit and are ________ from inside the dwelling unit shall have at least ____receptacle outlet accessible from the balcony , deck or porch . The receptacle outlet shall not be located more than _____ft above said surfaces .

Attached, accessible, one, 6 1/2. 210.52 (E)(3)

Service lateral

The underground conductors between the utility electric supply system and the service point.

In each attached garage and in each detached garage with electric power , at least one receptacle outlet shall be installed in_______and not more than _____ ft above the floor ?

Each vehicle bay, 5 1/2

When is a receptacle outlet required in a accessory building , if it has ______

Electric power. 210.52 (G)(2)

EGC

Equipment grounding conductor

In Art 210.8 ( A ) ( 5 ) the exception refers to what two systems not required to have GFCI protection _______and _______

Fire alarm, burglar alarm 210.8(A)(5)

How many receptacles a peninsular countertop referred to in the previous question ?

One at least. 210.52(C)(3)

Kitchen receptacle requirements , No small appliance branch circuit shall supply more than ________

One kitchen (210.52(B)(3)

Where two or more branch circuits supply devices or equipment on the_____or _________means to __________disconnect the . ungrounded conductors shall be provided at the point at which the branch circuits _______.

Scene yoke, mounting strap, simultaneously, originate. 210.7

Main bonding jumper

The connection between the grounded circuit conductor and the equipment grounding conductor at the service. (Wire or bus at)

Unlike the grounding electrode conductor which carries current to the ground through the grounding electrode, the main and system bonding jumpers, are placed directly in the——?

Supply side, ground fault current return path.

service

The Conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served

Grounding Conductor, Equipment (EGC)

The conductive path(s) that provides a ground-fault current path and connects normally non-current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.

Service Conductors

The conductors from the service point to the service disconnecting means.

Bonding Jumper, System

The connection between the grounded circuit conductor and the supply-side bonding jumper, or the equipment grounding conductor, or both, at a separately derived system.

Bonding Jumper, Equipment

The connection between two or more portions of the equipment grounding conductor. (Ex expansion joint ) Equipment bonding jumpers are also used to connect the grounding terminal of a receptacle to a metal box. That in turn is grounded via an equipment grounding conductor (raceway system)

What is the difference between a main bonding jumper and a systems bonding jumper?

The main bonding jumper is installed at the incoming service equipment. The system bonding jumper is any bonding jumper in a downstream separately derived system (transformer).

Service equipment

The necessary equipment, usually consisting of a circuit breaker(s) or switch(es) and fuse(s) and their accessories, connected to the load end of service conductors to a building or other structure, or an otherwise designated area, and intended to constitute the main control and cutoff of the supply.

Service Conductors, Overhead

The overhead conductors between the service point and the first point of connection to the service-entrance conductors at the building or other structure.

Service drop

The overhead conductors between the utility electric supply system and the service point.

Service Point

The point of connection between the facilities of the serving utility and the premises wiring.

Service point

The point of connection between the facilities of the serving utility and the premises wiring.

Service Conductors, Underground

The underground conductors between the service point and the first point of connection to the service-entrance conductors in a terminal box, meter, or other enclosure, inside or outside the building wall.

Service Lateral

The underground conductors between the utility electric supply system and the service point.

What is the primary function of the main bonding jumper and the system bonding jumper in a grounded system?

To create the link for the ground, fault current between the EGC's, and the grounded conductor.

Are receptacle outlets required in dwelling unit basements ?

Yes 210.52 (G)(3)

Can a permanently installed electric baseboard heater equipped with factory installed receptacle outlets be permitted to meet the requirements for outlets for that wall space ?

Yes. 210.52 part 4


Related study sets

Chapter 36, 37, 43, 44, 46 Questions

View Set

STUDY GUIDE Mendelian Genetics --- Chapter 6 & 7

View Set