UNEC 215

Ace your homework & exams now with Quizwiz!

Where a premises wiring system contains feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feeder shall be identified by phase or line and system by _____, or other approved means.

marking tape tagging color coding 215.12(C)(1)(a)

Ground-fault protection of equipment shall be required for a feeder disconnect if the disconnect is rated _____.

1,000A, 480V 215.10

Feeder grounded conductors shall be permitted to be sized at _____ percent of the continuous and noncontinuous load where a portion of the feeder is connected at both its supply and load ends to separately installed pressure connections.

100 215.2(A)(1)(a) Ex 2

The minimum feeder conductor ampacity shall be no less than the noncontinuous load plus _____ percent of the continuous load, and not less than the maximum load after the application of adjustment and correction factors.

125 100

When a feeder supplies _____ in which equipment grounding conductors are required, the feeder shall include or provide an equipment grounding conductor.

branch circuits 215.6

Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections in accordance with 110.14(C)(2), it shall be permitted to have an allowable ampacity _____ the sum of the continuous load plus the noncontinuous load.

not less than 215.2(A)(1)(a) Ex 2

Ground-fault protection of equipment shall not be required at a feeder disconnect if ground-fault protection of equipment is provided on the _____ side of the feeder and on the load side of any transformer supplying the feeder.

supply 215.10 Ex 2


Related study sets

Lesson 7 Reduction of Risk Potential

View Set

Intermediate Accounting 2 Ch 13-15

View Set

GS MKT 306 CH 16 SOCIAL RESPONSIBILITY AND SUSTAINABILITY

View Set

我今年学十门课 Sentence structures

View Set

해커스 토익 왕기초 RC 24 DAYS - DAY2

View Set

Lecture 5: Two Coordinate Systems

View Set