Where a premises wiring system contains feeders supplied from more than one nominal voltage system, each ungrounded conductor of a feeder shall be identified by phase or line and system by _____, or other approved means.
marking tape tagging color coding 215.12(C)(1)(a)
Ground-fault protection of equipment shall be required for a feeder disconnect if the disconnect is rated _____.
1,000A, 480V 215.10
Feeder grounded conductors shall be permitted to be sized at _____ percent of the continuous and noncontinuous load where a portion of the feeder is connected at both its supply and load ends to separately installed pressure connections.
100 215.2(A)(1)(a) Ex 2
The minimum feeder conductor ampacity shall be no less than the noncontinuous load plus _____ percent of the continuous load, and not less than the maximum load after the application of adjustment and correction factors.
125 100
When a feeder supplies _____ in which equipment grounding conductors are required, the feeder shall include or provide an equipment grounding conductor.
branch circuits 215.6
Where a portion of a feeder is connected at both its supply and load ends to separately installed pressure connections in accordance with 110.14(C)(2), it shall be permitted to have an allowable ampacity _____ the sum of the continuous load plus the noncontinuous load.
not less than 215.2(A)(1)(a) Ex 2
Ground-fault protection of equipment shall not be required at a feeder disconnect if ground-fault protection of equipment is provided on the _____ side of the feeder and on the load side of any transformer supplying the feeder.
supply 215.10 Ex 2