DXR Hardware Devices - DXR2.E17C(X)

¡Supera tus tareas y exámenes ahora con Quizwiz!

Maximum Ethernet wire length (segment) is ___?

330 ft (100 m)

DXR2.E17CX has the capacity to support ___ Data Points

60

LED - SCOM, Green, Steady ON

Application configured, no devices connected or communicating

LED - SCOM, Green, Flashing

Communication with at least one device

LED - RUN, Green/Red, Regular Flashing

Device is in an unconfigured state (factory default)

LED - RUN, Green, Steady OFF

Device is not powered

LED - RUN, Green, Steady ON

Device is ready for operation

The top LED is for ____, or Field Communications. It is reserved for the planned release of the MS/TP variant of the lab DXR.

FCOM

LED - SCOM, OFF

No application configured

LED - RUN, Green, Blinking per wink command

Physical device identification

LED - RUN, Red, Steady ON

Program error, Communications error (KNX PL-Link), Hardware fault

LED - RUN, Green, Regular Flashing

Start-up or the program is stopped

This extra capacity is needed in ___ jobs requiring lighting and shading actuators.

TRA

Ethernet DXR supports BACnet over ____.

UDP/IP

Service pin (SVC) located below the Run light can be used for unit identification ____ and system configuration ____.

Wink and Reset

LED - RUN, Red, Rapid Flashing

Wrong or corrupt software, No application loaded


Conjuntos de estudio relacionados

Introduction to Biology and Characteristics of Life Study Guide

View Set

MKTG 480: Chapter 13 - Promotional essentials: digital and social media marketing

View Set

List of Common Ions: Polyatomic Cations and Anions

View Set

American Government - Graded Exam #3

View Set

CHM 114 Spectrometric Analysis of Iron: Application of Beer's Law

View Set