DXR Hardware Devices - DXR2.E17C(X)
Maximum Ethernet wire length (segment) is ___?
330 ft (100 m)
DXR2.E17CX has the capacity to support ___ Data Points
60
LED - SCOM, Green, Steady ON
Application configured, no devices connected or communicating
LED - SCOM, Green, Flashing
Communication with at least one device
LED - RUN, Green/Red, Regular Flashing
Device is in an unconfigured state (factory default)
LED - RUN, Green, Steady OFF
Device is not powered
LED - RUN, Green, Steady ON
Device is ready for operation
The top LED is for ____, or Field Communications. It is reserved for the planned release of the MS/TP variant of the lab DXR.
FCOM
LED - SCOM, OFF
No application configured
LED - RUN, Green, Blinking per wink command
Physical device identification
LED - RUN, Red, Steady ON
Program error, Communications error (KNX PL-Link), Hardware fault
LED - RUN, Green, Regular Flashing
Start-up or the program is stopped
This extra capacity is needed in ___ jobs requiring lighting and shading actuators.
TRA
Ethernet DXR supports BACnet over ____.
UDP/IP
Service pin (SVC) located below the Run light can be used for unit identification ____ and system configuration ____.
Wink and Reset
LED - RUN, Red, Rapid Flashing
Wrong or corrupt software, No application loaded