A device that is designed to withstand numerous trip and reset cycles without replacement and can be thermal, magnetic, or solid-state is an

Overload relays

The recommended method of determining short circuit currents is the

Point to point method

All of the following are classifications of medium-voltage fuses except

Proportion fuses

One characteristic of a dual element time delay fuse is that it

Provides back up if protective devices fail to operate

The minimum interrupting rating of branch circuit listed fuses is

10,000 A

The maximum fuse size for a single element non-time delay fuse serving a 10 hp three phase motor is

100 A

500A circuit breaker has a frame size of

1000A

The minimum voltage rating of branch circuit fuses is

125V

A plug fuse with a hexagonal cap has a maximum amperage rating of

15A

If a continuous load on a branch circuit is measured at 12A, the overcurrent protection should be sized at _____.

15A

A feeder circuit with no motor load has a continuous load of 10A and a noncontinuous load of 5A. The feeder overcurrent protective device should be sized at

17.5A

UL Class R fuses have a short circuit interrupting rating of up to ____.

200,000A

A feeder circuit with no motor load has a continuous load of 15Aand a noncontinuous load of 10A. The feeder overcurrent protective device should be sized at

28.75A

A feeder circuit with no motor load has a continuous load of 16A and a noncontinuous load of 10A. The feeder overcurrent protective device should be sized at

30A

The full load current rating of a 300kVa, three phase transformer operating at 480v is

361A

The full load current rating of a 150kVA, three-phase transformer operating at 240V is

362A

A high level short circuit current may exceed

50,000A

If a 120V feeder for nonmotor loads feeds a continuous load rated at 20A and a noncontinuous load at 25A, what size overcurrent protective device should be selected?

50A

For 480V circuits, the arc current seldom exceeds _____.

60% of the available bolted fault current

UL classifies low-voltage fuses at those operating at

600V or less

For proper coordination the total clearing time of any downstream protective device must be below a curve representing which percentage of the minimum melting curve of the fuse being applied

75%

Under normal operation and at currents near its ampere rating, a fuse operates as a

Conductor

One of the first signs of worn motor bearings is most likely to be a(n)

Continuous overloads

Worn motor bearings are most likely to result in a

Continuous overloads

The type of fuse used to prevent nuisance tripping from temporary motor overloads and surge currents is a

Dual element time delay fuse

A conductor with failed insulation contacts the metal edge of a grounded metal wire way. This is known as a

Ground fault

Accidental contact between an electrical conductor and a grounded enclosure is called a

Ground fault

If a circuit breaker has tripped and stays on for a limited time before tripping again after being reset, the problem is least likely to be a

Ground fault

Most arcing faults begin as

Ground fault

A type of fuse with a grooved ring in one ferrule is a Type _____.

R

Which of the following is true with regard to circuit breaker interrupting capacity ratings

UL tests now include NEMA ratings

Which of the following is true with regard to circuit breakers

Under normal conditions, the current flow bypasses the spring and latching mechanism.

An expulsion fuse is best described as a

Vented fuse in which the expulsion effect of the gases produced by the arc and lining of the fuse holder either alone or aided by a spring extinguishes the arc

The interrupting capacity of a circuit breaker is based on its rated

Voltage

A 600V fuse can be used in _____.

a 240V circuit

The voltage rating of a fuse

can be higher than the circuit voltage but never lower

Equipment intended to interrupt current at fault levels must have an interrupting rating at nominal circuit voltage that is ____

equal to the current available at the line terminals of the equipment

When tripped, the circuit breaker handle moves _____.

halfway between the on and off positions

The thermal portion of a standard circuit breaker

protects the circuit from heat damage generated by lower level currents

A 60A circuit breaker has a frame size of _____.

100A

A standard circuit breaker frame size is

100A

What is the frame size of a 30A circuit breaker

100A

The full-load current rating of a 225kVA three-phase transformer operating at 240V

542A

The let-through short circuit current of a 500kVA, 120/208V three-phase transformer is _____.

69,444A

A circuit breaker that trips instantly or fails to reset is most likely the result of

A short circuit

Which of the following best describes the maximum short circuit current that a fuse or circuit breaker will safely interrupt

AIC

When circuit breakers are classified as 100A through 2000A frames, these numbers are normally referred to as the

Frame size

Which of the following is true with regard to fuses

Fuse holder clips that have lost their spring cannot be repaired with pliers, they must be replaced

Overcurrent protection is covered in

NEC Article 240

Types of fault current include overloads, short circuits, ground faults, and

arc faults

A plug fuse is typically used in a

branch circuit

Each of the following is a basic, factor to a consider when applying any fuse except

manufacturer's brand name

When a common circuit breaker trips, the handle is in the _____.

middle position

A single-element fuse

provides an instantaneous trip for high levels of current

The magnetic portion of a standard circuit breaker

provides an instantaneous trip for high levels of current

Which of the following is within the basic scope of Underwriters Laboratories

safety

Which of the following is commonly referred to as motor branch circuit protection

short circuit protection

Circuit breakers are classified by

the largest ampere rating of its range


Conjuntos de estudio relacionados

Chapter 5: FL Statutes, Rules, and Regulations

View Set

NUR 202 Test 3 - Immune, Endocrine, Trauma

View Set

Configuration Management & JSON Encoded Data

View Set

3.2: Given a Scenario, Implement Host or Application Security Solutions

View Set