26309 - motor calcuations

Pataasin ang iyong marka sa homework at exams ngayon gamit ang Quizwiz!

A​ three-phase motor with four stator poles has a synchronous speed of​ _____. ​3,600 rpm ​1,200 rpm 900 rpm ​1,800 rpm

1,800 rpm Four poles equal​ 1,800 rpm in synchronous speed

Where an air conditioning unit is supplied with size 6 AWG CU conductors and protected by a 60 ampere circuit​ breaker, where​ required, the MINIMUM​ wire-type size CU equipment grounding conductor permitted for this installation is​ _____. 8 AWG 6 AWG 10 AWG 12 AWG

10 AWG

If we were installing​ dual-element time-delay fuses to protect a motor that has an FLA of 65​ amperes, what is the maximum fuse size we could use without increasing the size to​ 225% because of high starting​ current? 100 amperes 200 amperes 115 amperes 125 amperes

125 amperes ​Dual-element, time-delay fuses may be sized up to​ 175% of the​ motor's full-load current for all standard​ motors: 65 ​´ 1.75​ = 113.75 amperes. The closest fuse size to that is 125​ amperes, because 115 amperes is not a standard fuse size.

What is the minimum feeder conductor ampacity for four​ motors: 50hp,​ 40hp, and two at​ 10hp? (Round off to a whole​ number). 100 amperes 145 amperes 161 amperes

161 amperes Refer to NEC Table 430.250 to find the FLA of each​ motor. 50hp​ = 65A, 40hp​ = 52A, and the two 10hp motors each draw 14A. The largest motor has an FLA of 65A. Now add the​ others: 52A​ + 14A​ + 14A​ = 80A. Multiply the largest motor​ (65A) by 1.25​ = 81.25A. Then add this to the total. 81.25A​ + 80A​ = 161.25A. Rounded off to 161A.

If the current drawn by a​ three-phase motor operating at 480 volts is 10.2​ amperes, what will the current most likely be if the motor is reconnected to run and is operated at 240​ volts, with all conditions remaining the​ same? 20.4 amperes 10.2 amperes 5.1 amperes

20.4 amperes When a motor is operated at​ 240V, the current draw of the motor is double the current draw of a 480V connection

What is the maximum size​ nontime-delay fuse that can be used to protect a motor that has an FLA of 65​ amperes? 200 amperes 60 amperes 70 amperes

200 amperes​ Nontime-delay fuses can be sized at​ 300% of the​ FLA: 65 ​´ 3.00​ = 195. Because 195 is not a standard size​ fuse, NEC Section​ 430.52(C)(1).

For circuits of OVER​ _____ to​ ground, the electrical continuity of rigid metal conduit​ (RMC) or intermediate metal conduit​ (IMC) that contain any conductor other than service conductors shall be ensured with two​ (2) locknuts, one inside and one outside the box or cabinet. 250 volts 125 volts 480 volts 300 volts

250 volts

What is the maximum kVAR capacitor rating that should be applied as a power factor correction in a​ 15-horsepower induction motor with a nominal speed of​ 1,800 rpm? 5 9 4

4

When connecting a​ three-phase, dual-voltage,​ delta-wound motor for​ 480-volt operation, which of the following combinations of lead connections is​ correct? 7 to 6 and​ 1, 8 to 4 and​ 2, 9 to 5 and 3 4 to​ 7, 5 to​ 8, 6 to 9

4 to​ 7, 5 to​ 8, 6 to 9 For higher​ voltages, leads 4 and​ 7, 5 and​ 8, and 6 and 9 are connected together.

A feeder supplying two​ (2) continuous-duty,​ 208-volt, 3-phase​ motors, one 10 hp and one​ 7½ hp shall have a MINIMUM ampacity of​ _____ amperes 68.75 62.70 55.00 38.50

62.70 10​ hp - FLC​ = 30.8 amps x​ 125% = 38.5​ amperes ​ 7½ hp​ - FLC​ = 24.2 amps x​ 100% = 24.2 amperes​ ​ TOTAL = 62.7​ amperes

Rating

A designated limit of operating characteristics based on definite conditions.Such operating characteristics as load, voltage, frequency, etc., may be given in therating.

Torque

A force that produces or tends to produce rotation. Common units ofmeasurement of torque are foot-pounds and inch-pounds.

Circuit interrupter

A non-automatic, manually operated device designed to open acurrent-carrying circuit without injury to itself

Choose the correct statement. ​Three-phase motors are able to start turning because of a start winding. A synchronous motor is a type of AC motor. The rotor is the stationary winding in an AC motor.

A synchronous motor is a type of AC motor.

Under which of the following conditions can three​ 5-horsepower motors be supplied by one branch circuit that has short circuit​ protection? The short circuit protection in the branch circuit does not exceed 20A. Each motor starter is equipped with heaters. The trip setting of the circuit breaker is no greater than 15A in a 120V circuit.

Each motor starter is equipped with heaters. Two or more motors of any​ rating, each having individual overload​ protection, may be connected to a single branch circuit that is protected by a short circuit protective device.

True or False. Branch circuit conductors are sized at​ 100% of the FLA for motors rated as continuous duty.

False NEC Section 430.22 requires that the ampacity of branch circuit conductors supplying a single​ continuous-duty motor must not be less than​ 125% of the motor​ full-load current rating.

True Or False. A​ dual-voltage, delta-connected motor always has nine leads.

False.

True or False. MSCPs can be installed in any fuse holder.

False. MSCPs are designed for use in a special type of​ fusible-switch combination motor starter.

If an instantaneous trip circuit breaker is used in a​ three-phase motor​ circuit, what must be installed in the motor starter to protect the motor from​ overload? Auxiliary contacts Heaters ​Dual-element time-delay fuses

Heaters Heaters in motor starters protect the entire circuit and all equipment against overloads up to and including​ locked-rotor current.

Can a circuit breaker with a current rating of 90A be used as a motor disconnecting means on a motor with an FLA of​ 80A? No Yes Not enough information given to answer

No A circuit breaker suitable for use as a motor disconnecting means must have a current rating of at least​ 115% of the motor​ full-load current.

Terminals

Points at which an electrical component may be connected to anotherelectrical component.

Service factor

The number by which the horsepower rating is multiplied to determinethe maximum safe load that a motor may be expected to carry continuously at its ratedvoltage and frequency

Branch circuit power is supplied to a continuous duty motor using No. 12 AWG wire. Can No. 12 wire be used as the grounding conductor in this​ application? Yes No Not enough information available

Yes In this​ situation, the sizing is not required to be larger than the circuit conductors supplying the equipment.

A motor overload device functions in direct response to​ _____. ambient temperature temperature rise of the motor motor current voltage

motor current

All of the following provide motor overload protection except​ _____. circuit breakers ​time-delay relays fuses overload relays

​time-delay relays A​ time-delay relay does not provide motor overload protection.


Kaugnay na mga set ng pag-aaral

MS-100: Managing Microsoft 365 Identity and Services

View Set

History Flashcards Chapter 17 Section 3

View Set

Chapter 26: The Child with Respiratory Dysfunction

View Set

Chapter 4: Unit 1 - National Ownership: Real Property Characteristics & Rights (Notes)

View Set

Modern Chemistry Ch. 3 Application

View Set