Determine the maximum overload protection, using overload relays, for a 25-horsepower, 240-volt, 3-phase continuous-duty motor with a motor nameplate full-load current rating of 65 amperes, a temperature rise of 40°C, and a service factor of 1.15.

430.32(A)(1), Separate Overload Device40°C rise, 1.15 service factorMax. overload rating = 125%Max. overload = motor nameplate FLC rating × 125%= 65 × 1.25= 81.25 AThe correct answer is: 81.25 A

Determine the maximum overload protection by using separate overload protective devices to protect a 20-horsepower, 460-volt, 3-phase continuous-duty motor marked with a temperature rise of 50°C and a motor nameplate full-load current rating of 13 amperes.

430.32(A)(1), Separate Overload DeviceAll other motors, Max. overload rating = 115%Max. overload = motor nameplate FLC rating × 115%= 13 × 1.15= 14.95 AThe correct answer is: 14.95 A

Overload relays are used for the overload protection of a 100-horsepower, 440-volt, 3-phase, continuous-duty motor marked with a service factor of 1.15, a temperature rise of 40°C, and a motor nameplate full-load current rating of 132 amperes. Calculate the maximum overload protection.

430.32(A)(1), Separate Overload DeviceMax. overload rating = 125%Max. overload = motor nameplate FLC rating × 125%= 132 × 1.25= 165 AThe correct answer is: 165 A

Overload relays are used for the overload protection of a 7.5-horsepower, 208-volt, single-phase, continuous-duty motor with a motor nameplate full-load current rating of 46 amperes, a service factor of 1.10, and a temperature rise of 50°C. Calculate the maximum overload protection.

430.32(A)(1), Separate overload deviceAll other motors,Max. overload rating = 115%Max. overload = motor nameplate FLC rating × 115%= 46 × 1.15= 52.9 AThe correct answer is: 52.9 A

Overload relays are used for the overload protection of a five-horsepower, 240-volt, single-phase motor with a 1.15 service factor and a motor nameplate full-load current rating of 31.5 amperes. Calculate the maximum overload protection.

430.32(A)(1), Separate overload deviceMax. overload rating = 125%Max. overload = motor nameplate FLC rating × 125%= 31.5 × 1.25= 39.375 AThe correct answer is: 39.375 A

Determine the maximum overload protection permitted for this 75-horsepower motor when starting current is not a problem.

430.32(A)(1)Max. overload rating = 125%Max. overload = motor nameplate FLC rating × 125%= 188 × 1.25= 235 AThe correct answer is: 235 A

What is the maximum rating of a thermal protector, built integral with the motor, when used for the motor overload protection of a 20-horsepower, 460-volt, 3-phase, continuous-duty motor with a motor nameplate full-load current rating of 30 amperes?

430.32(A)(2), Thermal Protector, Use NEC table value for FLC Table 430.250, 3-phase, 20 hp, 460 V = 27 A FLC430.32(A)(2), FLC greater than 20 AMax. thermal protector rating = 140%Max. thermal protector = FLC × 140%= 27 × 1.40= 37.8 ANote: Review Informational Note following 430.32(C).The correct answer is: 37.8 A

Determine the maximum overload protection when starting current is a problem by using separate overload protective devices to protect a 20-horsepower, 460-volt, 3-phase, continuous-duty motor marked with a temperature rise of 50°C and a motor nameplate full-load current rating of 13 amperes.

430.32(C), Starting current a problem50°C temperature rise, Max. overload rating = 130%Max. overload = motor nameplateFLC rating × 130%= 13 × 1.30= 16.9 AThe correct answer is: 16.9 A

Overload relays are used for the overload protection of a 100-horsepower, 440-volt, 3-phase, continuous-duty motor marked with a service factor of 1.15, a temperature rise of 40°C, and a motor nameplate full-load current rating of 132 amperes. Calculate the maximum overload protection when starting current is a problem.

430.32(C), Starting current a problemMax. overload rating = 140%Max. overload = motor nameplate FLC rating × 140%= 132 × 1.40= 184.8 AThe correct answer is: 184.8 A

What is the maximum size time-delay fuse permitted to be used for the overload protection for a 5-horsepower, 240-volt, single-phase motor with a motor nameplate full-load current rating of 30 amperes, a service factor of 1.15, and a temperature rise of 40°C, when starting current is a problem? Fuse sizes must be selected from the NEC standard sizes.

430.32(C), Starting current a problemMax. overload rating = 140%Max. overload = motor nameplate FLC rating × 140%= 30 × 1.40= 42 ANext smaller size fuse, use 240.6(A) standard sizes42 A → 40 A fuse selectionThe correct answer is: 40 A

Overload relays are used for the overload protection of a five-horsepower, 240-volt, single-phase motor with a 1.15 service factor and a motor nameplate full-load current rating of 31.5 amperes. Calculate the maximum overload protection when starting current is a problem.

430.32(C), Starting current a problemMax. overload rating = 140%Max. overload = motor nameplate FLC rating × 140%= 31.5 × 1.40= 44.1 AThe correct answer is: 44.1 A

Overload relays are used for the overload protection of a 7 1/2-horsepower, 208-volt, single-phase, continuous-duty motor with a motor nameplate full-load current rating of 46 amperes, a service factor of 1.10, and a temperature rise of 50°C. Calculate the maximum overload protection when starting current is a problem.

430.32(C), Starting current is a problemAll other motors,Max. overload rating = 130%Max. overload = motor nameplate FLC rating × 130%= 46 × 1.30= 59.8 AThe correct answer is: 59.8 A

A 40-horsepower, 3-phase, 208-volt, continuous-duty squirrel cage motor is installed using an inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection. The motor nameplate full load current rating is 120 amperes and the overload protection is provided by overload relays. Starting current is a problem for this motor. Calculate the maximum size overload protection.

430.32(C), Starting current is a problemMax. overload rating = 130%Max. overload = motor nameplate FLC rating × 130%= 120 × 1.30= 156 AThe correct answer is: 156 A

Determine the maximum overload protection, using overload relays, when starting current is a problem, for a 50-horsepower, 208-volt, continuous-duty motor with a motor nameplate full-load current rating of 148 amperes and a service factor of 1.15.

430.32(C), Starting current is a problemService factor = 1.15Max. overload rating = 140%Max. overload = motor nameplate FLC rating × 140%= 148 × 1.40= 207.20 AThe correct answer is: 207.2 A

Determine the maximum rating of motor branch-circuit short-circuit and ground-fault protective device using time-delay fuses when starting current is not a problem for this 75-horsepower motor.

430.52(C)(1) Exception No.1Max time-delay fuse = 175%Max. rating = FLC × 175%= 192 × 1.75= 336 ANext higher OCPD permitted240.6(A) standard sizes336 A → 350 A time-delay fusesThe correct answer is: 350 A

What is the maximum overload protection rating of a separate overload device for a 3/4-horsepower, 120-volt, single-phase motor, not automatically started, not permanently installed, not within sight from the controller location, with a motor nameplate full-load current rating of 14.5 amperes and no other nameplate markings? Starting current for this motor is not a problem.

Solution:430.32(D)(2)(b) refers to 430.32(B)(1), and then to 430.32(A)(1)Max. overload rating = 115%Max. overload = motor nameplate FLC rating × 115%= 14.5 × 1.15= 16.675 ANote: The Code requirement path to arrive at the 115% value involves the following key stipulations:(1) less than 1 hp;2) non-automatically started;(3) not permanently installed;(4) not within sight from controller;(5) separate overload devices;(6) no service factor on nameplate; and(7) no temperature rise on nameplate.The correct answer is: 16.675 A

Determine the appropriate minimum THWN copper wire size for this 75-horsepower motor based on the ampacity of the branch-circuit conductors.

Table 310.16240 A = 250 kcmilThe correct answer is: 250 kcmil

A 3-phase, 75-horsepower, 240-volt, continuous-duty motor is installed with a motor nameplate full-load current rating of 188 amperes, a temperature rise of 40°C, and a marked service factor of 1.15. Starting current is not an issue.Determine the ampacity of the branch-circuit conductors for this 75-horsepower motor.

Table 430.250, 3-phase75 hp, 240 V = 192 A FLC430.22(A)Branch circuit ampacity = FLC × 125%= 192 × 1.25= 240 AThe correct answer is: 240 A

A 40-horsepower, 3-phase, 208-volt, continuous-duty squirrel-cage motor is installed using an inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection. The motor nameplate full load current rating is 120 amperes, and the overload protection is provided by overload relays. Starting current is a problem. Using an inverse-time circuit breaker, calculate the maximum branch-circuit short-circuit and ground-fault protection size permitted for this application.

Table 430.250,3-phase40 hp, 208 V = 114 A FLC430.52(C)(1), Exception No. 2(c)Max. inverse-time circuit breaker = 300%Max. rating = FLC × 300%= 114 × 3.00= 342 ANext lower standard OCPD size, 240.6(A) standard sizes342 A→ 300 AThe correct answer is: 300 A

Thermal protective devices for overload protection shall not be used with fractional horsepower motors.

The correct answer is: FalseThe correct answer is: 430.32(B)(2)

A 1/2-horsepower, 120-volt, continuous-duty motor is not permanently installed, is not automatically started, is within sight of the controller, and utilizes a 20-ampere branch-circuit short-circuit and ground-fault protective device as the overload protection. According to the NEC, this is an acceptable installation.

The correct answer is: TrueThe correct answer is: 430.32(D)(2)(a) Exception


Kaugnay na mga set ng pag-aaral

Microeconomics Midterm ch 13, 14, 15

View Set

Case Study: Bissell Brothers Escape - An entrepreneur's story

View Set

Chapter 13 Moral Development, Values, and Religion

View Set

Chapter 40 Management of Patients with Gastric and Duodenal Disorders

View Set

Chapter 5: Using Conversion Functions and Conditional Expressions

View Set

Familia Protocolos TCP/IP Unidad 11

View Set

431 Book Part 2 Single-Letter Consonants

View Set