S-95 SUPERVISION OF FIRE ALARM SYSTEMS
__________ HEAT DETECTORS DO NOT HAVE TO BE REPLACED AFTER IT HAS ACTIVATED THE FIRE ALARM.
RATE OF RISE
THE ______________ ALARM METHOD ACTIVATES AUDIO/VISUAL DEVICES ONLY ON THE FLOOR OF ALARM AS WELL THE FLOORS IMMEDIATELY ABOVE AND BELOW.
SELECTIVE
IN LARGE BUILDINGS, THE FIRE ANNUNCIATOR MAY BE ASSOCIATED WITH ____________ CONTROL AND _____________ SYSTEMS.
SMOKE PURGE, COMMUNICATIONS
A _________ SIGNAL INDICATES THAT A SYSTEM OR DEVICE BEING MONITORED IS IN AN ABNORMAL STATE.
SUPERVISORY
WHEN A ____________ CONDITION IS INDICATED, THE COF HOLDER SHOULD CHECK THE SYSTEM IN ORDER TO IDENTIFY THE PART OF THE SYSTEM THAT CAUSED THE SIGNAL.
SUPERVISORY
A __________ SIGNAL INDICATES THAT THE ALARM SYSTEM, TRANSMITTER, OR COMMUNICATIONS PATH IS WHOLLY OR PARTIALLY OUT OF SERVICE.
TROUBLE
AIR-SAMPLING DETECTORS SHALL GIVE A ____________ SIGNAL IF THE AIRFLOW IS OUTSIDE THE MANUFACURERS SPECIFIED RANGE.
TROUBLE
THE __________ SHOULD BE MAINTAINED AT THE BUILDINGS FACP.
ALARM LOG BOOK
MONITORED FIRE COMMAND CENTERS MUST BE CONDUCTED AT LEAST ___________.
ANNUALLY
DO NOT SILENCE THE BUILDING ___________ AND ________ DEVICE UNTIL THE FIRE ALARM CONDITION IS VERIFIED BY FDNY PERSONNEL.
AUDIBLE, VISUAL
SMOKE DETECTORS MUST BE CLEANED AT LEAST ONCE EVERY ______________.
6 MONTHS.
________ HEAT DETECTORS ACTIVATE THE ALARM WHEN THE DETECTOR COMPONENTS MELT AT A PRESET TEMPERATURE.
FIXED-TEMPERATURE HEAT DETECTORS
SINGLE ACTION STATIONS ARE USUALLY FOUND __________.
INDOORS
IONIZATION SMOKE DETECTORS MONITOR ___________, OR ELECTRICALLY CHARGED PARTICLES IN THE AIR.
IONS
A _________ IS THE OPEN SPACE THAT CARRIES AIR BETWEEN THE CEILINGS AND FLOOR ABOVE.
PLENUM
___________ DETECTORS ARE REQUIRED IN ANY BUILDING THAT HAS FOSSIL FUEL BURNING EQUIPMENT.
CARBON MONOXIDE
____________ DETECTORS EMPLOY MORE THAN ONE OPERATING PRINCIPLE AND OPERATE INDEPENDENT OF EACH OTHER.
COMBINATION
_________ VISUAL INSPECTION IS HIGHLY RECOMMENDED BY THE FDNY.
DAILY
THE FOUR SECTIONS IN THE ALARM BOOK SHOULD CONTAIN THE FOLLOWING:
DAILY ENTRIES, SYSTEM OFF-LINE ENTRIES, ACTIVATED ALARM ENTRIES, AND NOTIFICATION ENTRIES.
___________ DETECTORS SHUT DOWN A BUILDINGS HVAC SYSTEM AND RE-DIRECT AIRFLOW.
DUST SMOKE
THE _______________ ALARM METHOD ACTIVATES ALL AUDIO/VISUAL DEVICES THROUGHOUT THE BUILDING WHEN A FIRE IS DETECTED.
GENERAL
THE NEW FIRE CODE WAS ADOPTED IN __________ AND VASTLY CHANGED THE REQUIREMENTS FOR SUPERVISION OF ALL FIRE ALARM SYSTEMS.
JULY 2008
THE NFPA DEFINES ACCESSIBILITY AS __________________.
"ADMITTING CLOSE APPROACH: NOT GUARDED BY LOCKED DOORS, ELEVATION, AND OTHER EFFECTIVE MEANS."
AN _________ ALARM IS ONE WHICH FUNCTIONED AS DESIGNED, BUT WHICH DEPARTMENT RESPONSE IS UNNECCESSARY.
UNNECESSARY
AN _________ ALARM IS THE RESULT OF IMPROPER INSTALLATION, OR MAINTENANCE.
UNWARRANTED
DUTIES THAT CAN BE PERFORMED BY AN S-95 COF HOLDER INCLUDE ___________ ONLY.
VISUAL INSPECTIONS ONLY
ALL SUBSYSTEMS ARE SUBJECT TO FDNY INSPECTION AND TEST FOR ISSUANCE OF _______________.
LETTER OF APPROVAL
ANY ABNORMAL CONDITIONS MUST BE INVESTIGATED AND NOTED IN THE ___________.
LOGBOOK
____________ DETECTORS CONTAIN MULTIPLE SENSORS THAT RESPOND SEPERATELY BUT PROVIDE ONLY ONE ALARM SIGNAL.
MULTI-CRITERIA
____________ DETECTORS CONTAIN MULTIPLE SENSORS AND ARE CAPABLE OF GENERATING MULTIPLE ALARMS.
MULTI-SENSOR
THE FDNY IS NOT DISPATCHED TO RESPOND TO _________ OR ________ SIGNALS.
SUPERVISORY, TROUBLE
ONCE ACTIVATED, THE FIRE ALARM SYSTEM CANNOT BE RE-SET AT THE _____________.
FIRE ALARM MANUAL PULL STATION
THE PRIMARY PURPOSE OF A ____________ IS TO WARN OCCUPANTS AND TO TRANSMIT SIGNALS INDICATION FIRE TO THE FDNY.
FIRE ALARM SYSTEM
__________ HEAT DETECTORS ARE THE MOST COMMONLY USED.
FIXED-TEMPERATURE
ROUTINE HANDLING OF TROUBLE SIGNALS SHOULD TAKE A MAXIMUM OF ___________ MINUTES FROM RECEIPT OF TROUBLE SIGNAL BY CENTRAL STATION UNTIL INITIAL INVESTIGATION BY TELEPHONE.
FOUR
FOR AIR SAMPLING TYPE DETECTORS, THE MAXIMUM AIR SAMPLING TRANSPORT TIME FROM THE FARTHES POINT SHALL NOT EXCEED ____________.
120 SECONDS
A MASTER PLUMBER WITH AN S-12 COF IS ALLOWED TO PERFORM MAINTENANCE ON SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES WITH LESS THAN ____________ SPRINKLERS.
30
WHEN SMOKE DETECTORS REPORT THE NEED FOR MAINTENANCE TO THE FACP, IT MUST BE CLEANED WITHIN __________.
1 WEEK
MAXIMUM ALLOWABLE TIME FOR FIRE ALARM OUTPUT FUNCTIONS TO OPERATE ONCE A SMOKE DETECTOR HAS BEEN ACTIVATED IS __________ SECONDS.
10
THE FIRE ALARM PRIMARY POWER SOURCE SHALL BE GENERATED ELECTRIC POWER NOT EXCEEDING ____________ VOLTS.
277/480
TWO-WAY COMMUNICATION SYSTEMS MUST BE TESTED AT LEAST ONCE EVERY ______________ MONTHS.
6
________ SHALL NOT BE A SUBSTITUTE FOR CONNECTION TO A SECONDARY POWER SOURCE.
BATTERIES
____________ DETECTORS ARE USED TO PROTECT LARGE AREAS. IT IS A LIGHT BEAM BROKEN BY COMBUSTIBLE PARTICLES.
BEAM
THE LOG BOOK SHOULD BE A ________ BOOK.
BOUND
AN APPROVED CENTRAL STATION COMPANY IS ONE THAT HAS BEEN ISSUED A VALID CERTIFICATE FROM ____________.
FDNY
A ___________ SIGNAL IS INITIATED WHEN A DEVICE INDICATES THE PRESENCE OF FIRE.
FIRE ALARM
THE PRIMARY PURPOSE OF A ______________ IS TO PROCESS SIGNALS RECEIVED FROM INITIATING DEVICES AND TO ACTIVATE APPROPRIATE SIGNALS.
FIRE ALARM CONTROL PANEL
THE _________ SHALL ONLY BE RESET AT THE DIRECTION OF A FIRE DEPARTMENT REPRESENTATIVE.
FIRE ALARM CONTROL PANEL
FIRE ALARM DEVICES SHALL BE PROTECTED, ESPECIALLY DURING ___________.
INSTALLATION
IONIZATION DETECTORS USE AN _______________ AND A SOURCE OF IONIZING
IONIZATION CHAMBER
PROJECTED BEAMS SHALL BE DESIGNED SO THAT SMALL ANGULAR MOVEMENTS DO NOT CAUSE ______________.
NUISANCE ALARMS
THE TWO TYPES OF PHOTOELECTRIC SMOKE DETECTORS: LIGHT-______________ AND LIGHT- ____________ .
OBSCURATION, SCATTERING
SMOKE DETECTORS MUST BE CLEANED AT LEAST _____________ BY AN S-78, S-97, T-97, OR S-98 COF HOLDER.
ONCE EVERY SIX MONTHS.
PROJECTED BEAM-TYPE DETECTORS SHALL BE KEPT CLEAR OF __________ OBSTACLES.
OPAQUE
_____________ DETECTORS ARE BETTER AT SENSING SMOKY FIRES, SUCH AS THOSE CAUSED BY A SMOLDERING MATTRESS.
PHOTOELECTRIC
UNMONITORED FIRE COMMAND CENTERS MUST BE INPSECTECTED AT LEAST _____________.
WEEKLY