S-95 SUPERVISION OF FIRE ALARM SYSTEMS

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

__________ HEAT DETECTORS DO NOT HAVE TO BE REPLACED AFTER IT HAS ACTIVATED THE FIRE ALARM.

RATE OF RISE

THE ______________ ALARM METHOD ACTIVATES AUDIO/VISUAL DEVICES ONLY ON THE FLOOR OF ALARM AS WELL THE FLOORS IMMEDIATELY ABOVE AND BELOW.

SELECTIVE

IN LARGE BUILDINGS, THE FIRE ANNUNCIATOR MAY BE ASSOCIATED WITH ____________ CONTROL AND _____________ SYSTEMS.

SMOKE PURGE, COMMUNICATIONS

A _________ SIGNAL INDICATES THAT A SYSTEM OR DEVICE BEING MONITORED IS IN AN ABNORMAL STATE.

SUPERVISORY

WHEN A ____________ CONDITION IS INDICATED, THE COF HOLDER SHOULD CHECK THE SYSTEM IN ORDER TO IDENTIFY THE PART OF THE SYSTEM THAT CAUSED THE SIGNAL.

SUPERVISORY

A __________ SIGNAL INDICATES THAT THE ALARM SYSTEM, TRANSMITTER, OR COMMUNICATIONS PATH IS WHOLLY OR PARTIALLY OUT OF SERVICE.

TROUBLE

AIR-SAMPLING DETECTORS SHALL GIVE A ____________ SIGNAL IF THE AIRFLOW IS OUTSIDE THE MANUFACURERS SPECIFIED RANGE.

TROUBLE

THE __________ SHOULD BE MAINTAINED AT THE BUILDINGS FACP.

ALARM LOG BOOK

MONITORED FIRE COMMAND CENTERS MUST BE CONDUCTED AT LEAST ___________.

ANNUALLY

DO NOT SILENCE THE BUILDING ___________ AND ________ DEVICE UNTIL THE FIRE ALARM CONDITION IS VERIFIED BY FDNY PERSONNEL.

AUDIBLE, VISUAL

SMOKE DETECTORS MUST BE CLEANED AT LEAST ONCE EVERY ______________.

6 MONTHS.

________ HEAT DETECTORS ACTIVATE THE ALARM WHEN THE DETECTOR COMPONENTS MELT AT A PRESET TEMPERATURE.

FIXED-TEMPERATURE HEAT DETECTORS

SINGLE ACTION STATIONS ARE USUALLY FOUND __________.

INDOORS

IONIZATION SMOKE DETECTORS MONITOR ___________, OR ELECTRICALLY CHARGED PARTICLES IN THE AIR.

IONS

A _________ IS THE OPEN SPACE THAT CARRIES AIR BETWEEN THE CEILINGS AND FLOOR ABOVE.

PLENUM

___________ DETECTORS ARE REQUIRED IN ANY BUILDING THAT HAS FOSSIL FUEL BURNING EQUIPMENT.

CARBON MONOXIDE

____________ DETECTORS EMPLOY MORE THAN ONE OPERATING PRINCIPLE AND OPERATE INDEPENDENT OF EACH OTHER.

COMBINATION

_________ VISUAL INSPECTION IS HIGHLY RECOMMENDED BY THE FDNY.

DAILY

THE FOUR SECTIONS IN THE ALARM BOOK SHOULD CONTAIN THE FOLLOWING:

DAILY ENTRIES, SYSTEM OFF-LINE ENTRIES, ACTIVATED ALARM ENTRIES, AND NOTIFICATION ENTRIES.

___________ DETECTORS SHUT DOWN A BUILDINGS HVAC SYSTEM AND RE-DIRECT AIRFLOW.

DUST SMOKE

THE _______________ ALARM METHOD ACTIVATES ALL AUDIO/VISUAL DEVICES THROUGHOUT THE BUILDING WHEN A FIRE IS DETECTED.

GENERAL

THE NEW FIRE CODE WAS ADOPTED IN __________ AND VASTLY CHANGED THE REQUIREMENTS FOR SUPERVISION OF ALL FIRE ALARM SYSTEMS.

JULY 2008

THE NFPA DEFINES ACCESSIBILITY AS __________________.

"ADMITTING CLOSE APPROACH: NOT GUARDED BY LOCKED DOORS, ELEVATION, AND OTHER EFFECTIVE MEANS."

AN _________ ALARM IS ONE WHICH FUNCTIONED AS DESIGNED, BUT WHICH DEPARTMENT RESPONSE IS UNNECCESSARY.

UNNECESSARY

AN _________ ALARM IS THE RESULT OF IMPROPER INSTALLATION, OR MAINTENANCE.

UNWARRANTED

DUTIES THAT CAN BE PERFORMED BY AN S-95 COF HOLDER INCLUDE ___________ ONLY.

VISUAL INSPECTIONS ONLY

ALL SUBSYSTEMS ARE SUBJECT TO FDNY INSPECTION AND TEST FOR ISSUANCE OF _______________.

LETTER OF APPROVAL

ANY ABNORMAL CONDITIONS MUST BE INVESTIGATED AND NOTED IN THE ___________.

LOGBOOK

____________ DETECTORS CONTAIN MULTIPLE SENSORS THAT RESPOND SEPERATELY BUT PROVIDE ONLY ONE ALARM SIGNAL.

MULTI-CRITERIA

____________ DETECTORS CONTAIN MULTIPLE SENSORS AND ARE CAPABLE OF GENERATING MULTIPLE ALARMS.

MULTI-SENSOR

THE FDNY IS NOT DISPATCHED TO RESPOND TO _________ OR ________ SIGNALS.

SUPERVISORY, TROUBLE

ONCE ACTIVATED, THE FIRE ALARM SYSTEM CANNOT BE RE-SET AT THE _____________.

FIRE ALARM MANUAL PULL STATION

THE PRIMARY PURPOSE OF A ____________ IS TO WARN OCCUPANTS AND TO TRANSMIT SIGNALS INDICATION FIRE TO THE FDNY.

FIRE ALARM SYSTEM

__________ HEAT DETECTORS ARE THE MOST COMMONLY USED.

FIXED-TEMPERATURE

ROUTINE HANDLING OF TROUBLE SIGNALS SHOULD TAKE A MAXIMUM OF ___________ MINUTES FROM RECEIPT OF TROUBLE SIGNAL BY CENTRAL STATION UNTIL INITIAL INVESTIGATION BY TELEPHONE.

FOUR

FOR AIR SAMPLING TYPE DETECTORS, THE MAXIMUM AIR SAMPLING TRANSPORT TIME FROM THE FARTHES POINT SHALL NOT EXCEED ____________.

120 SECONDS

A MASTER PLUMBER WITH AN S-12 COF IS ALLOWED TO PERFORM MAINTENANCE ON SPRINKLER SYSTEMS IN RESIDENTIAL OCCUPANCIES WITH LESS THAN ____________ SPRINKLERS.

30

WHEN SMOKE DETECTORS REPORT THE NEED FOR MAINTENANCE TO THE FACP, IT MUST BE CLEANED WITHIN __________.

1 WEEK

MAXIMUM ALLOWABLE TIME FOR FIRE ALARM OUTPUT FUNCTIONS TO OPERATE ONCE A SMOKE DETECTOR HAS BEEN ACTIVATED IS __________ SECONDS.

10

THE FIRE ALARM PRIMARY POWER SOURCE SHALL BE GENERATED ELECTRIC POWER NOT EXCEEDING ____________ VOLTS.

277/480

TWO-WAY COMMUNICATION SYSTEMS MUST BE TESTED AT LEAST ONCE EVERY ______________ MONTHS.

6

________ SHALL NOT BE A SUBSTITUTE FOR CONNECTION TO A SECONDARY POWER SOURCE.

BATTERIES

____________ DETECTORS ARE USED TO PROTECT LARGE AREAS. IT IS A LIGHT BEAM BROKEN BY COMBUSTIBLE PARTICLES.

BEAM

THE LOG BOOK SHOULD BE A ________ BOOK.

BOUND

AN APPROVED CENTRAL STATION COMPANY IS ONE THAT HAS BEEN ISSUED A VALID CERTIFICATE FROM ____________.

FDNY

A ___________ SIGNAL IS INITIATED WHEN A DEVICE INDICATES THE PRESENCE OF FIRE.

FIRE ALARM

THE PRIMARY PURPOSE OF A ______________ IS TO PROCESS SIGNALS RECEIVED FROM INITIATING DEVICES AND TO ACTIVATE APPROPRIATE SIGNALS.

FIRE ALARM CONTROL PANEL

THE _________ SHALL ONLY BE RESET AT THE DIRECTION OF A FIRE DEPARTMENT REPRESENTATIVE.

FIRE ALARM CONTROL PANEL

FIRE ALARM DEVICES SHALL BE PROTECTED, ESPECIALLY DURING ___________.

INSTALLATION

IONIZATION DETECTORS USE AN _______________ AND A SOURCE OF IONIZING

IONIZATION CHAMBER

PROJECTED BEAMS SHALL BE DESIGNED SO THAT SMALL ANGULAR MOVEMENTS DO NOT CAUSE ______________.

NUISANCE ALARMS

THE TWO TYPES OF PHOTOELECTRIC SMOKE DETECTORS: LIGHT-______________ AND LIGHT- ____________ .

OBSCURATION, SCATTERING

SMOKE DETECTORS MUST BE CLEANED AT LEAST _____________ BY AN S-78, S-97, T-97, OR S-98 COF HOLDER.

ONCE EVERY SIX MONTHS.

PROJECTED BEAM-TYPE DETECTORS SHALL BE KEPT CLEAR OF __________ OBSTACLES.

OPAQUE

_____________ DETECTORS ARE BETTER AT SENSING SMOKY FIRES, SUCH AS THOSE CAUSED BY A SMOLDERING MATTRESS.

PHOTOELECTRIC

UNMONITORED FIRE COMMAND CENTERS MUST BE INPSECTECTED AT LEAST _____________.

WEEKLY


संबंधित स्टडी सेट्स

I (H) unit 4 Personal 9th, 5th amendment privacy Griswold v Connecticut and Roe v Wade

View Set

Bankruptcy, Closed-end credit, Collateral, Collection agency, Creditor, Credit report, Credit score, Debt, Debtor, Down payment, Installment loan, Open-end credit, Payday loan, Predatory lending, Secured loan, Title loan, Unsecured loan, Wage garnishment

View Set

Fundamentals Nursing Chapter 42 Loss, Grief, and Dying

View Set

The Bell Cricket and Monkey See Monkey Do

View Set

Chapter 1 Review Questions True-False Statements

View Set