WEEK 4 CHAPTER TEST REVIEW 20/22
1amp of current is equal to
1 coulomb
In a paralled circuit with a voltage drop of 120 v what would be the voltage drop of the circuit
120 v
The pickup voltage require to operate a potential relay is generated when a motor reaches around ____ percentage of its operating speed?
75% or 3/4
The main purpose of a metering device's orifice is to produce
A Pressure Drop
Which of following statements regarding stepper motor EEV's is not true?
A stepper motor regulates flow as it responds to a PWM signal by opening and closing rapidly.
When two substance are mixed and become one substance what occurs
Absorbtion
Checkvalve that open insuffuciently will allow what.
Act as a throttling device create and unanticiapated pressure drop
When a thin layer of fluid adheres to a solid but the two substances are not mixed together ______ occurs
Adsorption
Some HVACR systems require special TXVs to accomodate
All of the Above
When high head pressure in a hermitc system causes a oil and refrigerant breakdown the pressence of moisture or dirt can result in what being formed
All of the Above (sluge, acids, carbon)
Capillary tube failure will most likely occur when it is
Bent or Crimped
What is valve that premit fluid flow in one direction
Check Valve
The four major components of a mechanical refrigeration system are
Compressor, Condenser, Evaporator and Refrigeration metering device
A move heat through a solid object
Conduction
A movent of heat by means of fluid.
Convecition
An EEV controls its orfice using an
Electric Operator
Solenoid valves are controlled by an
Electric Signal
When used TXV valve the term superheat refers to the difference in temperature between
Evaporator inlet and sensing bulb
If the pressure in a sensing bulb is ______ the combined pressure from the evaporator and the spring a TXV's valve is forced open
Greater Than
When capillary tube systems cycle off
High side and low side pressures equalize
How do you calculate current
I=V/R
When heat is added to substance without a rise in temperature the process is called?
Latent Heat of Vaporazation
In a capillary tube system if there is too much refrigerant in the system (overchage) what could happen
Liquid refrigerant could be drawn into the compressor damaging
The minimum ___ setting is the point that casuses the least sensing bulb temperature change while the system is running
Minimum Stable Signal
A TXV is operating properly when the evaporator is filled
Mostly with Liquid
What do ladder diagram show.
None of the Above
What changes inside the sensing element with temerpature.
Pressure
In a HVACR system can be design to use lower torque compressor motor if a TXV is equipped with
Pressure Limiter
During normal operation many EEV controllers are able to use as inputs to govern valve position and operations
Pressure Measurements and Temperature
Whats the primary purpose of the metering device.
Pressure drop
This type of metering device varies refrigerant flow by varying the speed by which a solenoid valves opens and closes
Pulse width Modulation Signal
A PWM solenoid EEV controls its valve operating by___
Rapidly opening and closing its solenoid valve
Capillary tubes are used extensively in _____ system
Refrigerator and window ac unit
During the offcycle as the sensing bulb pressure and lowside pressure cancels each other out the ____ pressure is enough to force the txv firmly into its seat
Spring pressure
The condition in which liquid refrigerant is present in only of the evaporator is called
Starving
For increased system efficiency a capillary tube is usually positioned so that a portion of it is in contact with the ______
Suction Line
After a compressor burnout what will you installed temporaily to protect the compressor for the duration of clean up
Suction Line Filter Drier
A controller modulates the EEV through the use of an algorithm to maintain the desired
Super Heat
For a TXV adjusted to its MSS point, increasing spring tension on a TXV's adjustment screw will result in an increase of
Super Heat
The main value that influences the operation of a TXV is
Super Heat
What is function of an EEV design to maintain
Super Heat
Increasing _____ this adjustment will starve the evaporator.
SuperHeat
If an AXV is undercapacity for its application, what will happen
The evaporator will be starved
On system with small-diameter horizontal suction lines the sensing bulb should be mounted on the_____of the suction line
Top
A normally open contact is between L and S True or False
True
A relay coil is between the L and M terminal
True
True or False Terminal M is connected to the motor running winding
True
When should a TXV reduce the flow rate through an evporator
as it Evporator Cools
A compressor must start while under load if an automatic expansion valve does not have
bleed or by pass
The sizing of a filter drier is primarily based on a system
capacity rating
What do pictorial diagram show.
color of wires
To maintain a constant pressure in the evaporator when the system is running an AXV______ when evaporator pressure begins to increase
decrease refrigerant flow
A hot-gas defrost valve directs refrigerant into the low side from the______
discharge line
When a TXV is feeding refrigerant into an evaporator with multiple circuits a(n) ________ should be installed
distributor
A current relay is wired by connecting an ungrounded wired connected to the m terminal
false
To help prevent contamintat from entering capilalry tube what is usually installed in its inlet
filter drier
The inefficient operation of a check valve may cause a(n) _____ noise
hammering
Piston-type metering orifice are most often used on___ system
heat pump
What is movement of heat by way of fluid flow called
hot to cool
How do scroll compressor move refrigerent
involute sprials
When a capillary tube has a large diameter what must be done to the length of the cap to have the same affect of the smaller diameter
it must be shorter
To maintain constant pressure in the evaporator when a system is running AXV does what to refirgerant flow when the evporator pressure drops
it will Increase
A system equipped with a pilot-controlled thermostatic expansion valve is likely to be a _____________
larger, (50 tons and over)
The orifice size of the metering device may need to be change for units for long ____ sets to account for extra refrigerant charge
line sets
When a capillary tube is replace it is good practice to also replace the
liquid line filter drier
This is condition in which to much refirgerant is in the evaporator and can be drawn into the the compressor
liquid slugging
The primary purpose of an AXV is to maintain constant_______
low side pressure
Metering devices that change there orfice size to account for changes in cooling loads are refered to as
modulating
A color changing element in a moisture indicator is design to change color based on?
moisture
Liquid line filter drier needs to be replace when?
moisture indicator indicates too much moisture and there is a pressure drop across the filter drier.
An advantage of capillary tubes over modulating metering devices is that capillary tubes have no
moving parts
A difference from set point and control point is
offset
Where will a TXV sensing bulb be mounted
on the outlet
The adjusting nut or screw on a thermostatic expansion valve is sensitive and should not be turned more than _____ while the unit is running.
one-quarter (1/4)
On a capilary tube system severe frosting on the suction line during compressor start up will be an indication of what
overcharge
An HVACR system can be designed to use a lower torque compressor motor if the TXV is equipped with a(n) _______
pressure limiter
Pressure reading in system using an EXV is supplied from a ____ connected to the suction line
pressure transduce
Heat that cause a change in temperature in a substance is called
sensible heat
Bubbles in a sight glass can indicate?
shortage of refrigerant/partially clog filter drier.
A small viewport installed in a refrigerant line describes a_____
sight glass
If the superheat setting is increased to correct for an oversized TXV orifice, the evaporator will be______ much of the time
starved
An AXV that is overcapacity may allow too much refrigerant into the evaporator and may cause condensation on the_______
suction line
A sensing bulb must not be affected by the air or liquid being cooled. It should be wrapped in insulation so that only ______ affects the bulb
suction line temperature
A controller modulated the EEV through the use of an algorithm to maintain the desired
superheat
If the orifice of a TXV is oversized, too much refrigerant will pass into the evaporator and cause the suction line to________ before the sensing bulb can close the valve
sweat or frost
When a capilary serves the function as both liquid line and metering device where is it connected between?
the evaporator and condenser
What is adsorbtion
the process by which a solid holds molecules of a gas or liquid or solute as a thin film
Before a sensing bulb is installed, use steel wool to clean
the sensing bulb and suction line
To prevent a TXV from opening intermittenly during the off cylce, a(n) _____ can most easily be used to automatically divert high side pressure to underside of the TXV's diaphragm during Off cycle
three way solenoid valve
The pilot valve on a four-way solenoid valve
uses high pressure vapor to operate the four way valve