2-10 quiz
On a fully loaded 25 KVA transformer the drop leads would normally be __?__ stranded copper
#2
If more than one popsicle stick connector is to be installed in a basket type transformer terminal __?__ leads should be brought out to connect the services
Copper
Aluminum triplex itself can be inserted in the transformer lugs (T/F)
False
If the secondary voltage is listed on a transformer as 120/240 or 240/120, it makes no difference as both internal secondary coils can be connected in parallel or series. (T/F)
False
In order for a single phase transformer to produce any secondary voltage the X2 grounding strap must be in place (T/F)
False
It is good practice to leave an extra length of copper or to curl primary risers from the transformer to the live line incase the lead breaks (T/F)
False
Osha has no requirements concerning how to hook up and lift a load (T/F)
False
Transformers on the loading dock can be relied on so checking the winding continuity of a transformer is not important (T/F)
False
One requirement of the 1996 Migratory Bird Treaty Act regarding new transformer installations to protect birds from electrocution is to __?__
Install bushing covers.
A CSP transformer contains a __?__ and a __?__ breaker
Internal HV fuse and secondary
A popsicle stick connector is a __?__ terminal connector that is squeezed onto the end of the wire and inserted into the secondary terminals of a transformer
Pin
If a transfomer was ordered 24940 Grd Y / 14400 the transformer would have __?__ insulation at the H2 end
Reduced
According to industry standards all distribution transformers above 200 KVA and or 8600 volts are
Subtractive
A transformer with reduced insulation at H2 must have H2 tied to the __?__
System neutral
On a transformer with basket terminals copper leads should be inserted from the __?__
Top
If a transformer nameplate shows 14400/24940 Y it is suitable for a delta connection because it has full insulation __?__
at the H2
One factor that affects the mass that may be attached to a pole is the __?__
class of the pole
Another requirement of the 1996 Migratory Bird Treaty Act regarding new transformer installations to protect birds from electrocution is to install __?__
insulated transformer leads
While conducting a pre installation check on a transformer do not __?__ unless permission is granted by the employer
remove the lid
The proper way to hang a small distribution transformer when power equipment is not available is __?__
to use rope blocks, a pole jib, and a sling