3-3 test
When cleaning live-line tools, __?__ should be used to remove foreign matter from the tools
acidtone
OSHA law mandates that rubber-insulating blankets be tested
before the first issue and every 12 month thereafter
A wire tong __?__ is a device fitted to a wire tong that provides an attachment point for a rope block to be used for an in-line pull and eliminates the bending strain on the tong
block clamp
A spliced wire tong has a maximum working load rating __?__ an unjointed wire tong of the same dimensions
equal to
In the manufacture of hot stick fittings and parts, __?__ is the basic metal used
heat-treated aluminum alloy
If a vertical, 3-phase, dead end has a branch line. temporary jumpers are held to the side with a __?__ while the phases are being transferred to the new pole
hold tong
A trench is dug alongside a damaged pole. This is part of the job when replacing a pole uses the__?__ pole method.
leaning
When replacing a cross arm on a 3-phase line one method requires the auxiliary arm to be used in conjunction with the __?__ to rise a three conductors vertically to provide a safe clearance.
lifting wire tongs
Double cross arms can be replaced on an angle structure by using a 3-phase circuit lifting assembly if __?__ are used to remove the side thrust from the lifting arm.
link sticks and ropes
I order to spread out conductors at mid-span to set a new pole, __?__ sticks should be used
roller link
if a wire tongs saddle is fitted with a __?__ type pole attachment device. It must be "cocked" before placing the chain in the hook
wheel tightener
The minimum approach distance for 12,470 volts phase-to-phane is __?__
2'1"
A 25 kilovolt circuat has a 14,4-kilovolt potential to ground. The OSHA 1910.269 law states that the minimum approach distance is __?__ to these lines
2'4"
when using an auxiliary arm to hold two phrases on the same side of a pole, the wire holders are placed __?__ apart on the arm.
24"
The highest-rated rubber gloves are suitable for AC hot line work up to
36 kv
ridged plastic protective covers with a Class 4 rating are suitable for use on lines with a phase-to-ground potential of 21.1 kilovolts, and if both phases are covered a phase-to-phase potential of _____ will be present
36.6 kv
According to OSHA Guidelines, electrical testing of rubber-insulating gloves must be done before every issue and every __?__ thereafter
6 months