Except as permitted for two-wire replacements, receptacles installed on _____ branch circuits shall be of the grounding type. 15 and 20A up to 30A 125V 250V
15 and 20A
Receptacles _____, 125V and 250V installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. 15A and 20A 30A and less up to 50A up to 100A
15A and 20A
In bathrooms with less than the required zone required by 406.9(C), the receptacle(s) can be installed opposite the bathtub rim or shower stall threshold on the farthest wall within the room. True False
True
Where a grounding means exists in the receptacle enclosure a(an) _____-type receptacle shall be used. isolated ground grounding GFCI dedicated
grounding
Receptacles shall not be installed within a zone measured _____ ft horizontally and 8 ft vertically from the top of the bathtub rim or shower stall threshold. 3 4 5 6
3
Receptacles shall not be grouped or ganged in enclosures unless the voltage between adjacent devices does not exceed _____. 100V 200V 300V 400V
300V
Where tamper resistance receptacles are required, receptacles located more than _____ above the floor shall not be required to be tamper resistant. 4 ft 5 ft 5 1/2 ft 6 ft 7 in.
5 1/2 ft
A childcare facility is a building or structure, or portion thereof, used for educational, supervision, or personal care services for more than four children _____ years in age or less. 3 5 7 9
7
Receptacles shall not be installed within a zone measured 3 ft horizontally and _____ vertically from the top of the bathtub rim or shower stall threshold. 6 ft 6 ft 7 in. 7 ft 8 ft
8 ft
Nongrounding, nonlocking-type, 15A and 20A, 125V and 250V receptacles used for replacements in a dwelling unit shall not be required to be listed as tamper resistant. True False
True
Receptacles mounted to and supported by a cover shall be secured by more than one screw unless listed and identified for securing by a single screw. True False
True
Receptacles incorporating an isolated grounding conductor connection intended for the reduction of electromagnetic interference shall be identified by _____ on the face of the receptacle. an orange triangle a green triangle the color orange the engraved word "ISOLATED"
an orange triangle
Listed tamper-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required to be tamper-resistant elsewhere in this Code except where a non-grounding receptacle is replaced with _____ receptacle. an isolated a GFCI-type another non-grounding any of these
another non-grounding
A receptacle is considered to be in a location protected from the weather when located under roofed open porches, canopies, marquees, and the like, where it will not be subjected to _____. spray from a hose a direct lightning hit beating rain or water runoff falling or wind-blown debris
beating rain or water runoff
Receptacles mounted in boxes flush with the finished surface or projecting beyond it shall be installed so that the mounting yoke or strap of the receptacle is held rigidly against the _____. box or box cover faceplate finished surface bonding connection
box or box cover
Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a nongrounding-type receptacle shall be permitted to be replaced with a GFCI-type receptacle; however, some equipment or appliance manufacturers require that the _____ to the equipment or appliance includes an equipment grounding conductor. feeder branch circuit small-appliance circuit power cord
branch circuit
A housing shield intended to fit over a faceplate for flush-mounted wiring devices, or an integral component of an outlet box or of a faceplate for flush-mounted wiring devices is an "outlet box _____." cover protector in-use cover hood
hood
When 15A and 20A receptacles are installed in a wet location, the outlet box _____ shall be listed for extra-duty use. sleeve hood threaded entry mounting
hood
In dwelling units, all nonlocking type 125V and 250V, 15A and 20A receptacles installed _____ shall be listed as tamper resistant. in bedrooms outdoors, at grade level above counter tops in all areas specified in 210.52 and 550.13
in all areas specified in 210.52 and 550.13
Where a receptacle outlet is supplied by a branch circuit that requires arc-fault circuit-interrupter protection [210.12(A) or 210.12(B)], a replacement receptacle at this outlet shall be a _____. listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter receptacle receptacle protected by a listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter type receptacle receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker any of these
listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter receptacle receptacle protected by a listed (receptacle) outlet branch-circuit type arc-fault circuit-interrupter type receptacle receptacle protected by a listed combination type arc-fault circuit-interrupter type circuit breaker any of these
Attachment plugs and cord connectors shall be listed and marked with the _____. manufacturer's name or identification voltage rating amperage rating all of these
manufacturer's name or identification voltage rating amperage rating all of these
Receptacles mounted in boxes set back from the finished surface shall be installed so that the mounting _____ of the receptacle is held rigidly at the finished surface. screws yoke or strap cover plate grounding clip
yoke or strap
Where installed in a wet location, all _____ receptacle(s) shall be listed and identified as weather resistant. 125V, 30A nonlocking 250V, 15A nonlocking 125V, 30A locking 250V, 15A locking
250V, 15A nonlocking
Article _____ covers the rating, type, and installation of receptacles, cord connectors, and attachment plugs (cord caps). 400 404 406 408
406
Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a nongrounding-type receptacle(s) shall be permitted to be replaced with a GFCI-type receptacle(s) where supplied through a ground-fault circuit interrupter; however, some cord-and-plug-connected equipment or appliances require an equipment grounding conductor and are listed in 250.114. True False
True
All nonlocking-type, 125V, 15A and 20A receptacles that are controlled by _____, or that incorporate control features that remove power from the receptacle for the purpose of energy management or building automation, shall be permanently marked with the word "controlled." wall switches remote control wireless communication an automatic control device
an automatic control device
Receptacle assemblies for installation in countertop surfaces shall be _____ for countertop applications. identified labeled listed approved
listed
Nonlocking-type 15A and 20A, 125V and 250V receptacles in a dwelling unit shall be listed as tamper resistant except _____. receptacles located more than 5 1/2 ft above the floor receptacles that are part of a luminaire or appliance a receptacle located within the dedicated space for an appliance that, in normal use, is not easily moved from one place to another all of these
receptacles located more than 5 1/2 ft above the floor receptacles that are part of a luminaire or appliance a receptacle located within the dedicated space for an appliance that, in normal use, is not easily moved from one place to another all of these
Automatically controlled receptacles shall be replaced with _____ controlled receptacles. listed suitably equivalently identified
equivalently
Receptacles in or on countertop surfaces or work surfaces shall not be installed _____, unless listed for countertop or work surface applications. in the sides of cabinets in a face-up position on GFCI circuits on the kitchen small-appliance circuit
in a face-up position
Nonlocking-type 125V and 250V, 15A and 20A receptacles installed in _____ shall be listed as tamper resistant. guest rooms and guest suites of hotels and motels childcare facilities preschools and elementary education facilities all of these
guest rooms and guest suites of hotels and motels childcare facilities preschools and elementary education facilities all of these
Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a nongrounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter and _____ shall be marked "GFCI Protected" and "No Equipment Ground," visible after installation. the receptacle(s) their cover plates the branch circuit the receptacle(s) or their cover plates
the receptacle(s) or their cover plates
When replacing automatically controlled receptacles, if automatic control is no longer required, the receptacle and any associated receptacles marked in accordance with 406.3(E) shall be replaced with a receptacle and faceplate marked in accordance with 406.3(E). True False
False
Receptacle assemblies and _____ receptacle assemblies listed for work surface or countertop applications shall be permitted to be installed in work surfaces. AFCI GFCI current-limiting all of these
GFCI
When replacing receptacles in locations that would require GFCI protection under the current NEC, _____ receptacles shall be installed. dedicated isolated ground GFCI-protected grounding
GFCI-protected
A 30A, 208V receptacle installed in a wet location, where the product intended to be plugged into it is not attended while in use, shall have an enclosure that is weatherproof with the attachment plug cap inserted or removed. True False
True
A receptacle shall not be installed within, or directly over, a bathtub or shower space. True False
True
An outdoor receptacle in a location protected from the weather, or in another damp location, shall be installed in an enclosure that is weatherproof when the receptacle is _____. covered enclosed protected recessed in the finished surface
covered
Nonlocking-type 125V and 250V, 15A and 20A receptacles installed _____ shall be listed as tamper resistant. in business offices, corridors, waiting rooms and the like in clinics, medical and dental offices, and outpatient facilities as a subset of assembly occupancies described in 518.2 to include places of awaiting transportation, gymnasiums, skating rinks, and auditoriums in dormitory units all of these
in business offices, corridors, waiting rooms and the like in clinics, medical and dental offices, and outpatient facilities as a subset of assembly occupancies described in 518.2 to include places of awaiting transportation, gymnasiums, skating rinks, and auditoriums in dormitory units all of these
When replacing a nongrounding-type receptacle where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a _____ can be used as the replacement. nongrounding-type receptacle grounding receptacle GFCI-type receptacle marked "No Equipment Ground" nongrounding-type receptacle or a GFCI-type receptacle marked "No Equipment Ground"
nongrounding-type receptacle or a GFCI-type receptacle marked "No Equipment Ground"
Weather-resistant receptacles _____ where replacements are made at receptacle outlets that are required to be so protected elsewhere in the Code. shall be provided are not required are optional are not allowed
shall be provided
When nongrounding-type receptacles are replaced by GFCI-type receptacles where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, _____ shall be marked "No Equipment Ground." the receptacle the protective device the branch circuit these receptacles or their cover plates
these receptacles or their cover plates
Metal faceplates for receptacles shall be grounded. True False
true
Nonlocking 15A and 20A, 125V and 250V receptacles installed in damp locations shall be listed as _____. raintight watertight weatherproof weather resistant
weather resistant