Electrical Code Calculations Lv2 - NEC 2017

अब Quizwiz के साथ अपने होमवर्क और परीक्षाओं को एस करें!

Calculate the resistance of 150 feet of 14 AWG THWN solid uncoated copper conductor. Calculate the answer to four decimal places.

14 AWG solid uncoated copper = 3.07 Ω/kft R = (DC Res. × L) ÷ 1,000 = (3.07 × 150) ÷ 1,000 = 460.05 ÷ 1,000 = 0.4605 Ω

Calculate the resistance of 175 feet of 14 AWG stranded uncoated copper conductor. Calculate the answer to four decimal places.

14 AWG stranded uncoated copper = 3.14 Ω/kft R = (DC Res. × L) ÷ 1,000 = (3.14 × 175) ÷ 1,000 = 549.5 ÷ 1,000 = 0.5495 Ω

A 10 AWG copper stranded conductor is somewhat larger in diameter than a solid conductor of the same conductor material and size. How much greater is the resistance in ohms per 1,000 feet (ohms/kFT) of an uncoated 10 AWG stranded conductor than that of a 10 AWG solid copper conductor?

0.03 ohms/kFT Chapter 9 Table 8

An 8 AWG stranded conductor is somewhat larger in diameter than a solid conductor of the same size. How much larger is the diameter of an 8 AWG stranded conductor than that of an 8 AWG solid conductor?

0.018" Chapter 9 Table 8

Calculate the resistance of 300 feet of 10 AWG solid aluminum conductor. Calculate the answer to two decimal places.

10 AWG solid aluminum = 2.0 Ω/kft R = (DC Res. × L) ÷ 1,000 = (2.0 × 300) ÷ 1,000 = 600 ÷ 1,000 = 0.60 Ω

What is the voltage drop on a single-phase, 240-volt, branch circuit supplying a 48-ampere load a distance of 88 feet using 4 AWG RHW aluminum conductors? Calculate your answer to two decimal places.

4 AWG aluminum = 0.508 ohms/kFT Vd = (DC res. × I × 2L) ÷ 1,000 = (0.508 × 48 × 2 × 88) ÷ 1,000 = 4,290 ÷ 1,000 = 4.29 volts

What is the voltage drop on a single-phase branch circuit supplying a 42-ampere load a distance of 125 feet with 6 AWG TW uncoated copper conductors? Calculate your answer to two decimal places.

6 AWG uncoated copper = 0.491 ohms/kFT Vd = (DC Res. × I × 2L) ÷ (1,000 × 1.05) = (0.491 × 42 × 2 × 125) ÷ (1,000 × 1.05) = 5,155.5 ÷ 1,050 = 4.91 volts

What is the voltage at the load with a 240-volt supply for a single-phase branch circuit supplying a 40-ampere load at a distance of 72 feet with 8 AWG THW stranded, uncoated copper conductors? Calculate your answer to two decimal places.

Vd = (DC Res. × I × 2L) ÷ 1,000= (0.778 × 40 × 2 × 72) ÷ 1,000= 4,480 ÷ 1,000= 4.48 volts V load = V supply − Vd= 240 − 4.48= 235.52 volts at load

What is the voltage drop on a 3-phase, 480-volt, branch circuit supplying a 120-ampere load a distance of 65 feet with 1 AWG THW uncoated copper conductors? Calculate your answer to two decimal places.

1 AWG uncoated copper = 0.154 ohms/kFT Vd = (DC Res. × I × 1.73L) ÷ 1,000 = (0.154 × 120 × 1.73 × 65) ÷ 1,000 = 2,080 ÷ 1,000 = 2.08 volts

Calculate the resistance of 190 feet of 12 AWG TW solid uncoated copper conductor. Calculate your answer to four decimal places.

12 AWG solid uncoated copper = 1.93 ohms/kFT R = (DC Res. × L) ÷ (1,000 × 1.05) = (1.93 × 190) ÷ (1,000 × 1.05) = 366.7 ÷ 1,050 = 0.3490 ohms

What is the voltage drop on a 480-volt branch circuit supplying 96 amperes to a 3-phase load 200 feet from supply with 3 AWG THHN uncoated copper conductors? Calculate your answer to two decimal places.

3 AWG uncoated copper = 0.245 ohms/kFT Vd = (DC Res. × I × 1.73L × 1.05) ÷ 1,000 = (0.245 × 96 × 1.73 × 200 × 1.05) ÷ 1,000 = 8,540 ÷ 1,000 = 8.54 volts

What is the voltage drop on a single-phase, 460-volt, branch circuit supplying a 215-ampere load a distance of 118 feet, with 4/0 AWG THWN copper uncoated conductors? Calculate your answer to three decimal places.

4/0 AWG uncoated copper = 0.0608 ohms/kFT Vd = (DC Resist. × I × 2L ) ÷ 1,000 = (0.0608 × 215 × 2 × 118) ÷ 1,000 = 3,084.992 ÷ 1,000 = 3.085 volts

Calculate the resistance of 250 feet of 6 AWG THHN aluminum conductor. Calculate your answer to four decimal places.

6 AWG aluminum = 0.808 ohms/kFT R = (DC Res. × L × 1.05) ÷ 1,000 = (0.808 × 250 × 1.05) ÷ 1,000 = 212.1 ÷ 1,000 = 0.2121 ohms

What is the voltage drop of a single-phase branch circuit supplying a 28-ampere load a distance of 58 feet with 8 AWG THHN stranded aluminum conductors? Calculate your answer to two decimal places.

8 AWG stranded aluminum = 1.28 ohms/kFT Vd = (DC Res. × I × 2L × 1.05) ÷ 1,000 = (1.28 × 28 × 2 × 58 × 1.05) ÷ 1,000 = 4,365.312 ÷ 1,000 = 4.37 volts

Calculate the resistance of 200 feet of 8 AWG coated solid copper conductor. Calculate the answer to four decimal places.

Chapter 9, Table 8, DC resistance8 AWG solid coated copper = 0.786 Ω/kft R = (DC Res. × L) ÷ 1,000 = (0.786 × 200) ÷ 1,000 = 157.2 ÷ 1,000 = 0.1572 Ω

Which of the following does not specifically change the direct current resistance of a particular conductor?

Conductor insulation Chapter 9 Table 8

Calculate the resistance of 500 feet of 250,000 circular mils uncoated copper. Calculate the answer to five decimal places.

250 kcmil uncoated copper = 0.0515 Ω/kft R = (DC Res. × L) ÷ 1,000 = (0.0515 × 500) ÷ 1,000 = 25.75 ÷ 1,000 = 0.02575 Ω

What is the maximum length of a single-phase, 120-volt branch circuit supplying a 10-ampere load with 14 AWG solid copper conductors permitted without exceeding a 3% voltage drop?

Vdmax = supply voltage × 3% = 120 × 0.03 = 3.6 Vcmils 14 AWG copper = 4,110 cmilsL = (cmils × Vd) ÷ (2 × k × I ) = (4,110 × 3.6) ÷ (2 × 12.9 × 10) = 14,796 ÷ 258 = 57.35 ft

What size copper conductors are needed to supply a 3-phase, 208-volt, 200-ampere load at a distance of 250 feet and not exceed a 3% voltage drop?

Vdmax = supply voltage × 3% = 208 × 0.03 = 6.24 Vcmils = (k × L × I × 1.73) ÷ Vd = (12.9 × 200 × 250 × 1.73) ÷ 6.24 = 1,115,850 ÷ 6.24 = 178,822 cmils

A 3-phase service is 240 volts at the service equipment. Presently, there is a 5-volt drop to the downstream distribution panel. What size copper branch-circuit conductors are needed to supply a 38-ampere, 3-phase branch-circuit load at a distance of 110 feet and not exceed a total 5% voltage drop on the feeder plus the branch circuit?

Vdmax = supply voltage × 5%= 240 × 0.05= 12 V Vd (BC) = Vdmax − Vd (feeder)= 12 − 5= 7 V (branch circuit)cmils = (k × I × 1.73 × L ) ÷ Vd (BC)= (12.9 × 38 × 1.73 × 110) ÷ 7= 93,285.06 ÷ 7= 13,326 cmils

What is the maximum current for a single-phase 230-volt branch circuit supplying a load at a distance of 140 feet with 4 AWG copper conductors and holding the voltage drop to 2%?

Vdmax = supply voltage × 2% = 230 × 0.02 = 4.6 Vcmils 4 AWG copper = 41,740 cmilsI max = (cmils × Vd) ÷ (k × 2L ) = (41,740 × 4.6) ÷ (12.9 × 2 × 140) =192,004 ÷ 3,612 = 53.16 A

What minimum size copper wire is needed for a 230-volt, single-phase branch circuit supplying a 65-ampere load a distance of 250 feet to limit the voltage drop within the recommended Code limit?

Vd = supply voltage × 3%= 230 × 0.03= 6.9 voltcmils = (k × I × 2L ) ÷ Vd= (12.9 × 65 × 2 × 250) ÷ 6.9= 419,250 ÷ 6.9= 60,761 cmils Chapter 9, Table 8, Area, cmilsRead (more than) 60,761 = 66,360 cmils66,360 = 2 AWG copper

What minimum size aluminum wire is needed for a 440-volt, 3-phase branch circuit supplying a 60-ampere load a distance of 325 feet and holding the voltage drop within a reasonable limit of efficiency?

Vd = supply voltage × 3%= 440 × 0.03= 13.2 volt cmils = (K × L × I × 1.73) ÷ Vd= (21.2 × 60 × 325 × 1.73) ÷ 13.2= 715,182 ÷ 13.2= 54,180 cmils

What is the maximum length of a single-phase, 110-volt branch circuit supplying a 40-ampere load with 6 AWG aluminum conductors permitted without exceeding a 3% voltage drop?

Vdmax = supply voltage × 3% = 110 × 0.03 = 3.3 Vcmils 6 AWG aluminum = 26,240 cmilsL = (cmils × Vd) ÷ (2 × k × I ) = (26,240 × 3.3) ÷ (2 × 21.2 × 40) = 86,592 ÷ 1,696 = 51.06 ft. max. length (one way)


संबंधित स्टडी सेट्स

US History Unit 7: New Deal Programs

View Set

HESI: Feeding and Eating Disorders

View Set

Athletic Training Chapter 1 Quiz

View Set

Determining Intervals on Which a Function Is Increasing or Decreasing Quiz

View Set

Chapter 6 end of chapter review questions

View Set

Critical Control Points: Principles 2-3

View Set