Fire alarm test
A signal indicating an emergency requiring immediate action is a ____
Alarm signal
In a dwelling unit the detectors shall be wired in such a manner that actuation of one alarm will actuate ____ alarm(s).
All
Alarm and trouble signals, CAN or CANNOT, have the same tone or color.
Cannot
A smoke detector receiving the required operational test may be removed from the installed location for testing purposes. TRUE/FALSE
False
It is permissible for the fire alarm system to share a circuit with the exit lights? TRUE/FALSE
False
A signal initiated by a fire alarm device such as a manual fire alarm box, automatic fire detector, water flow switch, or other device in which is indicative of the presence of a fire or fire signature
Fire alarm signal
A term usually applied to the simultaneous operation of all the audible alarm signals on a system to indicate the need for evacuation of a building.
General alarm
individuals responsible for the proper installation of fire alarm and signaling systems in accordance with plans, specifications and manufacturers requirements
Installation personnel
What Smoke Detectors Can be used for fire fighters Recall Service?
Lobby Hoist way Machine room
Fire pumps shall be supervised for:
Lose of power Phase reversal If pump is running
an unwanted activation of a signaling system or alarm intiation device in response to a stimulus or condition that is not the result of a potentially hazardous condition is a ______
Nuisance alarm
A fire detection device that responds when the temperature increases at a rate that exceeds a predetermined rate of rise.
Rate of Rise Detector
detectors shall not be installed until after the construction trades have completed the final cleanup TRUE/FALSE
True
An unwanted activation of an alarm initiating device or system output function where the cause has not been identified.
Unknown alarm
any alarm that coours that is not the result of a potentially hazardous condition is known as an _____
Unwanted alarm
smoke detectors CAN OR CANNOT be supported by their current carrying conductors
cannot
the fire alarm signal shall be supplied by a ____ branch circuit
dedicated
residential smoke alarms or smoke detectors are required at what locations?
each sleeping room. outside each sleeping room or each level
Where partitions extend to within 15% of the ceiling height the space separated by the partitions shall not be considered a separate room TRUE/FALSE
false
a smoke detector installed in an duct system is permitted to be used as a substitute for area protection TRUE/FALSE
false
if subject to obvious mechanical damage fire alarm systems notification appliances shall be suitably protected. homemade or improvised guards shall be provided for appliance protection TRUE/FALSE
false
if two buildings are covered by the same fire alarm system must they be civered by the same zone of origin TRUE/FALSE
false
in a new building that has an automatic sprinkler system installed the ohio fire code states all fire alarm boxes may be eliminated TRUE/FALSE
false
smoke detectors installed beneath raised floors or avoce suspended ceiling or both including riased floors and suspended ceiling use for environmental air may be used in lieu of providing detection within the room TRUE/FALSE
false
the location of all detectors in air duct system shall be permanently and clearly identified and recorded
false
a signal indicating a concentration of carbon monoxide at or above the alarm threshold that could pose a risk of life and safety requires ___?
immediate action
individuals who conduct a visual examination of a system or portion therof to verify that it appears to be in operating condition in proper location and is free of physical damage or conditions that impair operation.
inspection personnel
You must be certified by the State of Ohio if you are:
installing fire pumps installing fire alarm systems testing and inspecting fire alarm systems
sensitivity in smoke detectors and single and multiple-station smoke alarms shall be checked when?
within one year of installation and every alternate year there after
what is the maximum travel distance between twi manual fire alarm boxes?
200 feet
the minimum sound level of an audible appliance is a sleeping area is ___
75 dba
wall mounted visible appliances shall be mounted to have the entire lens between ____ inches above the floor
80-96'
The sprinkler water flow alarm must activate within ____ seconds for a water flow equal to or greater than that from the smallest orifice sprinkler in the sprinkler system
9 seconds
audible appliances shall have their tops at least ___ below the ceiling if the Hight permits
90" + 6"
A smoke detector must be tested ______
Annually
optical fiver cables are not permitted in fire alarm systems TRUE/False
False
the word should indicates a mandatory requirment TRUE/FALSE
False Shall is mandatory
For smooth ceilings, all points on the ceiling shall have a detector within a distance equal to _ times the selected spacing.
.7
how far away should an ionization detector with a silencing means be placed from a cooking appliance or heat source?
10 feet
secondary power must be turned on within ____ on loss of primary supply
10 seconds
the maximum distances between visible appliances in a corridor can be no more than ____
100'
Air sampling smoke detector have a maximum air sample target time of _____ seconds from the farthest port to the detector
120 seconds
a public mode audible signal shall habe a sound level of at least ___ aboce the average ambient sound level or ___ above the maxium sound level whichever is greater
15 / 5 dba
where audible appliances are installed they shall be 15 ____ above average ambient sound level
15 DBA *cannot exceed 110 DBA*
A fire alarm system is required to have ____sources of power.
2
A fire sprinkler control valve is required to send a supervisory signal to the fire alarm control panel at not more than _____ revolutions of the hand wheel.
2
Fire alarm systems that are monitored by a central station are required to be connected to _ telephone lines.
2
smoke detectors above and below raised computer floors count as ___ smoke compartments
2
when testing restorable heat detectors how many on each iniating device circuit must be tested each year?
2 or more
The number of supervisory devices permitted to be connected to a single initiating device circuit shall not exceed ___
20
how far away should an ionization detector without a silencing means be placed from a cooking appliance or heat source?
20 feet
trouble signals must be restored in ______.
200 seconds
Dwelling unit, standby system shall be capable of operating the system for at least _____ followed by not less than of alarm _____
24 hours 4 minutes
the secondary power source for a fire alarm may be a battery with enough capacity to support the fire alarm panel with Enough power to last ____ after which it shall have enough capacity to sound the notification appliance for at least ____
24 hours 5 minutes
When installing a smoke detector for door release service and the depth of the wall above the door is LESS THAN 24 inches ONE SMOKE DETECTOR IS REQUIRED ON THE HIGHER SIDE OF THE PASSAGE ONLY (depth more than 24" requires 2 one on each side of passage)
24" requires 1 smoke detector on the higher side 2 smoke detectors if the depth is more than 24
coded alarm systems must repeat the code signs at least __ times
3
with a peak ceiling heat and smoke detectors shall be located within ______ if the peak measured horizontally.
3 feet
how long before a fire system is taken out of service should the AHJ be notified in writing
30 days
spacing of spot type smoke detectors on smooth ceiling shall be ______
30'
how far away should a smoke detector be placed from a bathroom that contains a shower or tub?
36 inches
the AHJ shall be notified if the fire system is out of service for _____
4 or more hours within a 24 hour period
a spot type smoke detector located on a ceiling shall be at least ____ from a side wall to the edge of detector and if on a sidewall between _____ down from the ceiling.
4"/12"
when monitoring the sprinkler system to prevent freezing the temerature shall not go below ___ degrees F
40 'F
the height of the manual fire alarm boxes shall be a minimum of ____ and maximum of ____ measured vertically from the floor level to the activating handle or level of box
42" to 48"
a manual fire alarm box (pull station) must be no more than ____ feet from an exit door
5 feet
how far away should a photoelectric detector be placed away from a cooking appliance or heat source?
6 feet
A two-wire Class B circuit has 10 smoke detectors on it. A Class B circuit will typically have an end-of-line device on the last detector in the circuit. The end-of-line device is usually a ____.
Resistor
sprinkler water flow devices must be tested ___
Semi annually
To avoid nuisance alarms the location of the smoke detector shall take into consideration the normal sources of:
Smoke Moisture Dust or Fumes Electrical or mechanical influences
Supplementary circuits only need to be Resistor ____ according to the AHJ (authority having jurisdiction).
Supervised
A sprinkler valve tamper switch is an example of a _____
Supervisory device
A signal indicating the need for action in connection with the supervision of guard tours, the fire supervision systems or equipment, or the maintenance feature of related systems ____
Supervisory signal
Smoke detectors installed in air duct systems are normally used to control spreading smoke. TRUE/FALSE
TRUE
A smoke detector cannot be installed in the following condition unless rated for the application:
Temperatures below 32 deg. F Temperatures above 100 deg. F Humidity above 93 % air velocity above 300 ft/min
A signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component
Trouble Singal
Protective covers for manual pull stations must be _____ and cannot be made on site
listed
an unwanted activation of an alarm initiating device caused by a person acting without malice
malice alarm
a signaling method characterized by simultaneous or sequential transmission or both and reception of multiple signs on a signaling line ciruit a transmission channel or a communication channel including means for positively identifying each signal.
multiplexing
A public emergency alarm reporting system.
municipal fire Alarm System
Cable used in ducts plenums and other air handling spacers used for environmental air _____
must be listed or plenum rated
are smoke detectors permitted to be recessed into the mounting surface YES/NO
no
under group E with occupancy under 50 people is the facility required to be convered by fire detection system
no 1103.7.1 group E ex.2
smoke detectors that use the light obscuration concept to detect smoke are called
photoelectric detectors
manual fire alarm boxes shall be _ in color
red or contrasting colors
manual pull stations and the wall they are mounted on must be of ___ colors.
red or contrasting colors
individuals who perform procedure adjustments recplacement of components system progamming and maintenance as described in the manufacturers service instructions that can affect any aspect to the performance of the system are called ____
service personal
a device which detects the visible or invisible particles of combustion is a ______.
smoke detector
individual responsible for the development of fire alarm and signaling system plans and specifications in accordance with this code
system designer
individuals who perform procedures used to determine the status of a system as intended by conducting acceptance reacceptance or periodic physical checks on systems
testing personnel
In corridors where more than two visible notification appliances are in any field of view, they shall flash in synchronization. TRUE/FALSE
true
Smoke detectors in elevator lobbies, hoist ways, or machine rooms can be used to activate the elevator recall function. Other fire detectors may be permitted if ambient conditions in those locations prohibit the use of smoke detectors TRUE/FALSE
true
Smoke detectors mounted in the air duct of HVAC systems shall initiate either an alarm signal or a supervisory signal at a constantly attended location TRUE/FALSE
true
fire alarm systems that cover more than 1 building must be annunciated separately TRUE/FALSE
true
should different levels of a building be separately zoned TRUE/FALSE
true
someone with a provisional fire alarm license is required to work under someone who is certified TRUE/FALSE
true
the ohio building code requires that wiring for fire alarm systems conform to requirements of NFPA standard 70/72 TRUE/FALSE
true
where fire warning equipment is provided for dewelling units fire signals shall take precedence over any other signal or function even if none fire alarm signal is activated first TRUE/FALSE
true
where partitions extend to within 15% of the ceiling, the spaces by the partitions shall be considered as separate rooms TRUE/FALSE
true
An unwanted activation of an alarm initiating device caused by a person acting without malice.
unintentional alarm