2-5-5

Lakukan tugas rumah & ujian kamu dengan baik sekarang menggunakan Quizwiz!

Assume a five-kilovolt rated cable to be terminated indoors in switchgear. The thickness of the stress cone at its peak (T) is ? . a. 1/4" b. 1/2" c. 3/4" d. 11/16"

A- 1/4"

Assume a five-kilovolt rated cable to be terminated indoors in switchgear. The cable jacket should be removed for ? plus the depth of the lug barrel. a. 10" b. 12" c. 16" d. 18"

A- 10"

There are ? common termination types. a. 5 b. 6 c. 7 d. 8

A- 5

The upper level at which a termination can withstand surges, such as lightning surges, is known by the initials ? . a. BIL b. LCN c. LSM d. RMS

A- BIL

Without stress control, the cable's electric field becomes very concentrated and the resulting voltage stress is high enough to break down the air. This break down is referred to as a partial discharge or ? . a. corona b. dead short c. electrostatic field d. longitudinal stress

A- corona

The two best insulator materials for providing cable tracking protection are silicone rubber and ? . a. porcelain b. teflon c. varnished cambric d. wood

A- porcelain

The way to shrink a Quick Term II Termination onto the cable is to slide the termination body onto the cable and remove the core. Starting with the loose end, pull while unwinding ? . a. clockwise b. counter-clockwise c. in one quick motion d. slowly

B- counter-clockwise

The upper level at which a 15-kilovolt rated termination can withstand surges, such as lightning, is ? crest. a. 66 kV b. 90 kV c. 110 kV d. 155 kV

C- 110 kV

The type of IEEE termination that provides stress control and should be used in a clean, dry environment is the Class ? . a. 1 b. 2 c. 3 d. 4

C- 3

A termination's ? distance is the surface distance between a conductor and ground, also referred to as the string distance. a. breakdown b. corona c. creepage d. failure

C- creepage

One function that an IEEE Class 1 Termination provides is ? between the high voltage conductor and ground. a. a conductive path b. a semi-conducting bridge c. external leakage protection d. moisture protection

C- external leakage protection

Three problems that are associated with a non-shielded termination include ? , electrical connection of the conductor, and physical protection of the cable insulation. a. lack of corona protection b. longer bend radius c. mechanical support d. no surface leakage protection

C- mechanical support

The function of the bottom seal on an IEEE Class 1 Termination is to provide a(n) ? to the cable jacket and ground wire. a. current path b. equipotential bond c. moisture seal d. path to ground

C- moisture seal

For additional protection, the termination's creepage path may be covered with ? tape. a. copper braided b. semi-conducting c. silicone d. stress relief

C- silicone

The type of stress control used in heat shrink terminations is a ? . a. braided overlay jacket b. prefabricated stress cone c. stress control tube d. stress drain wire

C- stress control tube

In addition to the termination's voltage stress, two conditions are necessary for tracking. One condition is contamination and the other is ? . a. corona b. electrolysis c. high overvoltage condition d. moisture

D- moisture

Some porcelain terminations are referred to as "potheads." A pothead performs sealing functions because it is filled with a(n) ? . a. conductive jell b. insulating tar c. jell that solidifies below 120°F d. potting compound

D- potting compound

A(n) ? gradually increases the total thickness of insulation from the edge of the semi-conducting shield out to a certain point on the cable's insulation. a. beveling tool b. epoxy insulation compound c. layer of tape d. stress cone

D- stress cone

The two functions of a termination insulator are to provide BIL protection against flashover damage and to provide ? protection for the cable's insulation. a. moisture b. phase-to-phase c. rodent d. tracking

D- tracking

An IEEE Class 1 Termination does not provide a seal to the external environment and must be sealed with two layers of tape. Select one: True False

False

Tape termination is not one of the common termination types because it takes too long to apply. Select one: True False

False

A basic (tubular) heat shrink termination for outdoor use can be upgraded by installing separate heat shrink skirt(s). Select one: True False

True

An IEEE Class 1 Termination has two seals located at the top and bottom. Select one: True False

True

One function that an IEEE Class 1 Termination provides is electrical stress control for the cable shield terminus. Select one: True False

True

Terminations are categorized as live-front connections. Select one: True False

True


Set pelajaran terkait

Chapter 7: Creating Republican Governments, 1776-1790

View Set

Dante's Inferno- cantos 9, 24, 26, 34 review questions

View Set

Reproductive Drug Questions (Book, Practice, Evolve and Study Guide)

View Set

Study for quiz 4/Consumer Science Unit 9

View Set

Ch 3 Life Policy Riders, Provisions, Options, and Exclusions

View Set