Where installed in a wet location, all _____ receptacle(s) shall be listed and identified as weather resistant.

250 v , 15A non locking

Snap switches shall not be grouped or ganged in enclosures unless the voltage between adjacent devices does not exceed _____.

300 V (404.8(B)

Receptacles shall not be grouped or ganged in enclosures unless the voltage between adjacent devices does not exceed _____.

300 v

A childcare facility is a building or structure, or portion thereof, used for educational, supervision, or personal care services for more than four children _____ years in age or less.

7 ( 406.2)

Attachment plugs and cord connectors shall be listed and marked with the _____.

All of these

Receptacles incorporating an isolated grounding conductor connection intended for the reduction of electromagnetic interference shall be identified by _____ on the face of the receptacle.

An orange triangle

Listed tamper-resistant receptacles shall be provided where replacements are made at receptacle outlets that are required to be tamper-resistant elsewhere in this Code except where a non-grounding receptacle is replaced with _____ receptacle.

Another non grounding

Switch enclosures shall not be used as _____ for conductors feeding through or tapping off to other switches or overcurrent devices, unless the enclosure complies with 312.8.

Any of these( 404.3)(B)

A receptacle is considered to be in a location protected from the weather when located under roofed open porches, canopies, marquees, and the like, where it will not be subjected to _____.

Beating rain or water run off

Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a nongrounding-type receptacle shall be permitted to be replaced with a GFCI-type receptacle; however, some equipment or appliance manufacturers require that the _____ to the equipment or appliance includes an equipment grounding conductor.

Branch circuit

Metal enclosures for switches or circuit breakers shall be connected to the circuit _____ conductor.

Equipment grounding (404.12)

Automatically controlled receptacles shall be replaced with _____ controlled receptacles.

Equivalently

Where multiple switch locations control the same lighting load such that the entire floor area of the room or space is visible from the single or combined switch locations, the grounded circuit conductor shall be required at all locations.

False ( 404.2)

A snap switch with an integral nonmetallic enclosure complying with 300.15(E) is required to be connected to an equipment grounding conductor.

False(404.9)(B)(2)(ex 3)

Receptacle assemblies and _____ receptacle assemblies listed for work surface or countertop applications shall be permitted to be installed in work surfaces.

GFCI

When replacing receptacles in locations that would require GFCI protection under the current NEC, _____ receptacles shall be installed.

GFCI-protected(406.4(D)(2)(c)

Where a grounding means exists in the receptacle enclosure a(an) _____-type receptacle shall be used.

Grounding

When nongrounding-type receptacles are replaced by GFCI-type receptacles where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, _____ shall be marked "No Equipment Ground."

These receptacles or their cover plates

Receptacles mounted to and supported by a cover shall be secured by more than one screw unless listed and identified for securing by a single screw.

True

Switches shall not be installed within tub or shower spaces unless installed as part of a listed tub or shower assembly.

True (404.4)(C)

Switches and circuit breakers used as switches shall be installed so that they may be operated from a readily accessible place.

True(404.8)

Three-way and four-way switches shall be wired so that all switching is done only in the _____ circuit conductor.

Ungrounded ( 404.2)

Receptacles mounted in boxes set back from the finished surface shall be installed so that the mounting _____ of the receptacle is held rigidly at the finished surface.

Yoke or strap

The metal mounting yoke of a replacement switch is not required to be connected to an equipment grounding conductor if the wiring at the existing switch does not contain an equipment grounding conductor, and the _____.

circuit is GFCI protected(404.9)(B)(2)(ex1)

Snap switches, dimmers, and control switches are considered to be part of the effective ground-fault current path when _____.

the switch is mounted with metal screws to a metal box or a metal cover that is connected to an equipment grounding conductor, or an equipment grounding conductor or equipment bonding jumper is connected to the equipment grounding termination of the snap switch(404.9(B)


Set pelajaran terkait

MAN 4720, Chapter 1, Exam 1 Review

View Set

CSC Healthcare Informatics Exam #2

View Set

Mental Health practice Questions

View Set

Tough, though, thought, through, thorough and throughout

View Set

Geography Trails (South America)

View Set

Maternity and Women's Health Nursing - Women's Health

View Set