What are the common diameters for screws in electrical work?

#6,8,10

The volume allowance for conductors that originate within the box and don't leave? (CT 314.1)

0 conductors are not counted

What is the volume allowance for conductors that originate outside box? (CT 314.1)

1 for each conductor

What is the volume allowance for conductors that pass through the box without splice or connection? (CT 314.1)

1 for each conductor

Based on the largest sized conductor present, 1 or more internal cable clamps have what volume allowance? (CT 314.1)

1 only

If there is a receptacle and a switch on 1 mounting strap, what is the volume allowance?

2

What is the volume allowance for conductors 12 in or greater that are looped and unbroken? (CT 314.1)

2 for a single unbroken conductor

14 AWG = ______ cubic inches

2.00

12 AWG = ______ cubic inches

2.25

10 AWG = _______ cubic inches

2.50

NEC 314.25

All boxes must have cover or faceplate

NEC 314.16

Boxes must be large enough for all conductors and wiring devices

NEC 300.11 and 314.23

Boxes must be securely mounted and fastened in place

NEC 314.27 (A) (1)

Boxes used at luminaire or lamp holder outlets that are vertical, if able to support other than 50 lbs, must be marked on the interior of the box to show the max weight of luminaire that is permitted

Devices such as receptacles, switches, dimmers, timers, etc., have how much volume allowance?

It has 2 for each yoke or mounting strap

Equipment grounding conductors (1 or more) have what volume allowance?

Just 1

Fixture wires (up to 4 and including grounding) has what volume allowance? (CT 314.1)

None

Support fitting such as luminaire studs and hickeys have ______ volume allowance. (CT 314.1)

One for each type of support fitting

NEC 314.24

Outlet/device boxes are required to be an approved depth, so conductors won't be damaged when installing device/equipment

What does the # 32 mean in 6-32 screw?

The number of threads per inch or "pitch" of the thread

True or false. Plaster rings do not go on device boxes,but can be put on square boxes

True

Multitap tool

Used to clean out threaded holes

EXCEPTION TO NEC 314.27

Vertically mounted luminaire weighing no more than 6 lbs can be supported on other boxes or plaster rings that are secured to other boxes, provided luminaire or lamp holder is secured to box with no fewer than 2 NO.6 or larger screws

NEC 300.15

Where conduit, NM Cable, or other cables are installed, a box or conduit body must be installed at each conductor splice connection point, outlet or others.


Set pelajaran terkait

Med Law and Ethics - Mod 11 - Compliance in Healthcare

View Set

INFO 323 - Comprehensive Final Exam

View Set

AP Gov, 4th Quarter, Unit 1, Chapter 15 The Federal Courts, Woll: the Federal Judiciary

View Set

Modules 11 - 13: IP Addressing Exam

View Set

NCLEX -Silversteri -Psychosocial integrity

View Set

17. English Phrasal Verbs in Use Advanced, Unit 17, Time

View Set

Sample Behavioral Interview Questions

View Set

Fundamentals: Infection Prevention - Clinical Questions

View Set