S-12 CITYWIDE SPRINKLER SYSTEMS
IF THE SPRINKLER SYS. IS SUPPLIED FROM PUBLIC WATER MAIN, THE CONTROL VALVE SIGN MAY READ ________________.
"SHUTOFF FOR SPRINKLER SYS. LOCATED 6 FEET FROM THIS SIGN"
THE WATER AVAILABLE TO THE CENTRIFUGAL PUMP MUST ALWAYS BE ___________.
UNDER PRESSURE
LARGE DROP SPRINKLER HEADS ARE USED TO BREAK THROUGH THE STRONG __________ OF HIGH CHALLENGE FIRES.
UPDRAFTS
PREACTION SYSTEM ALARMS ARE GIVEN AS SOON AS THE _________ IS OPENED.
VALVE
__________ SHALL BE READILY AVAILABLE TO ANY REPRESENTATIVE OF THE FIRE DEPT. THESE ARE TO BE MAINTAINED ON SITE FOR 3 YEARS.
RECORDS
THE _________ FEATURE SHUTS OFF WATER WHEN THE FIRE IS EXTINGUISHED AND TURNS ON AGAIN IF THE FIRE REKINDLES.
RECYCLING
FDNY CONNECTIONS TO STANDPIPE SYSTEMS SHALL BE PAINTED ____________.
RED
SYSTEMS PARTIALLY OR FULLY OUT OF SERVICE SHALL HAVE A ____________ TAG PLACED ON THE MAIN CONTROL VALVE.
RED
AN ACCELERATOR AND EXHAUSTER ARE USED TO _______THE TIME TO ALLOW WATER INTO THE SYSTEM.
REDUCE
THE COF HOLDER MAY INSPECT, TEST, AND PERFORM ROUTINE MX IF THEY HOLD THE FOLLOWING CERTS:
REFRIGERATION OPERATING ENGINEER, HIGH PRESSURE OPERATING ENGINEER, AND NYS HIGH PRESSURE OPERATING ENGINEER.
PRESSURE MAINTENANCE PUMPS (JOCKEY PUMPS) ARE USED TO __________ PRESSURE IN THE SYSTEM.
RESTORE
FAILURE TO MAKE INSPECTIONS MAY RESULT IN __________ OF THE COF AND COURT PROCEEDINGS.
REVOCATION
__________ TANKS ARE MADE OF WOOD, STEEL, OR CONCRETE.
GRAVITY
FDNY CONNECTIONS TO AUTOMATIC SPRINKLER SYSTEMS SHALL BE PAINTED ___________.
GREEN
BUILD UP OF FOREIGN MATERIALS ON SPRINKLER HEADS IS COMMONLY CALLED _________.
LOADING
ALL INDICATING VALVES IN THE COMPACTOR SPRINKLER SYSTEM SHALL BE ________ OPEN.
SEALED
FDNY CONNECTIONS TO NON-AUTOMATIC SPRINKLER SYSTEMS SHALL BE PAINTED ___________.
SILVER
SPRINKLER SYSTEMS ARE REQUIRED TO HAVE AN APPROVED MOTOR GONG, BELL, HORN, OR ________.
SIREN
THE ________ IN THE DELUGE SYSTEM ARE OPEN AT ALL TIMES.
SPRINKLER HEADS
SPRINKLERS MANUFACTURED AFTER 1/1/2000 ARE REQUIRED TO HAVE A _____________.
SPRINKLER IDENTIFICATION NUMBER (SIN)
REMOTE PUSHBUTTONS ARE USED TO __________ THE PUMP ONLY.
START
IN AN OUTSIDE STEM AND YOLK VALVE (OS&Y), VALVE POSITION IS INDICATED BY THE POSITION OF THE ____________.
STEM
IN BUILDINGS WHERE LIFE HAZARD IS HIGH (SCHOOLS, HOSPITALS) THE ALARM IS TRANSMITTED DIRECTLY TO THE _________.
FIRE DEPARTMENT
___________ ARE DESIGNED TO TAKE WATER FROM A SUPPLY AND DISCHARGE IT UNDER PRESSURE.
FIRE PUMPS
THE _______ TURN ON THE FILL PUMP WHEN THE WATER IN THE TANK IS TOO LOW.
FLOATS
_________ SYSTEMS ARE USED FOR THE PROTECTION OF SPECIAL HAZARDOUS OCCUPANCIES.
FOAM SUPPLY
FOR EVERY 1 FOOT THE TANK IS ABOVE THE DISCHARGE OUTLET ___________ PSI OF PRESSURE IS GENERATED.
0.433
REGULAR MX AND MINOR REPAIRS NOT AFFECTING MORE THAN ________ FLOOR(S) ARE CONSIDERED PLANNED REMOVAL FROM SERVICE.
1
SHUTDOWNS AFFECTING MORE THAN _________ FLOOR(S) ARE CONSIDERED UNPLANNED OUT OF SERVICE CONDITIONS.
1
GREEN TAGS INDICATE THAT __________.
NO IMPAIRMENT WAS FOUND
FACILITIES WITH 301-1000 SPRINKLERS REQUIRE ________ SPARES TO BE AVAILABLE.
12
DRY PIPE VALVES ARE USUALLY SET AT ________ PSI ABOVE THE NORMAL TRIP LEVEL.
15-20
AT A DISTANCE OF 4 FEET BELOW THE DEFLECTOR, THE SPRAY PATTERN COVERS A DIAMETER OF _________ FEET WHEN DISCHARGING AT 15 GPM.
16
A MASTER PLUMBER (MP) WITH COF IS LIMITED TO RESIDENTIAL OCCUPANCIES WITH _________ SPRINKLER HEADS OR LESS.
30
IF A MINOR DEFECT IS OBSERVED, IT SHALL BE CORRECTED WITHIN _________ DAYS OR IT WILL BE CONSIDERED AN IMPAIRMENT.
30
THE MAXIMUM GROSS CAPACITY OF PRESSURE TANKS IS _________ GALLONS.
9000
ABOUT ______ PERCENT OF FIRES ARE EXTINGUISHED OR CONTROLLED WHEN SPRINKLERS ARE INSTALLED.
96
SPARE SPRINKLERS SHALL BE KEPT AT THE FACILITY WHEN THE TEMPERATURE DOES NOT EXCEED _________.
100 DEGREES FAHRENHEIT
BOTH ACCLERATOR AND EXHAUSTER ARE ACTIVATED WHEN A DROP OF _______ PSI IS DETECTED IN THE SYSTEM.
2
PRESSURE TANKS SHOULD BE KEPT ________ FULL AND BE MAINTAINED AT OR ABOVE ________ PSI.
2/3, 75
FACILITIES WITH OVER 1000 SPRINKLERS REQUIRE ________ SPARES TO BE AVAILABLE.
24
GRAVITY TANKS SHOULD BE AT LEAST ________ FEET ABOVE THE HIGHEST LINE OF SPRINKLER HEADS.
25
CENTRIFUGAL PUMPS ARE CAPABLE OF DISCHARGING WATER FROM ____________ TO _________ GPM.
25, 5000
RECORDS OF ALL INSPECTIONS AND MX SHALL BE MAINTAINED ON PREMISES FOR A MIN. OF __________ YEARS.
3
PRESSURE TANK TEMPERATURES SHALL BE KEPT AT OR ABOVE _________.
40 DEGREES FAHRENHEIT
THE TEMPERATURE IN THE PUMP ROOM SHOULD BE MAINTAINED ABOVE __________.
40 DEGREES FAHRENHEIT
WET PIPE SYSTEMS HAVE WATER AT A MINIMUM TEMP. OF _______ TO PREVENT THE SYSTEM FROM FREEZING.
40 FAHRENHEIT
GLYCERIN NOT GREATER THAN _________ PERCENT OR GLYCOL NOT GREATHER THAN ________ PERCENT SHALL BE USED TO PROTECT FROM FREEZING.
50, 40
A MINIMUM OF _________ EXTRA SPRINKLER HEADS WITH THE APPROPRIATE WRENCHES SHALL BE AVAILABLE TO REPLACED DAMAGED ONES
6
FACILITIES WITH LESS THAN 300 SPRINKLERS REQUIRE __________ SPARES TO BE AVAILABLE.
6
AUTOMATIC FILL PUMPS FILL THE TANK AT A RATE OF _________ GPM OR MORE.
65
NOTIFICATION TO FDNY IS NOT REQUIRED, PROVIDED SYSTEM IS RETURNED TO SERVICE WITHIN ______ HOURS.
8
THE DROP IN ________ CAUSES A SPECIAL DRY PIPE VALVE TO OPEN.
AIR PRESSURE
WATER ALARMS SERVE AS FIRE EXTINGUISHING SYSTEMS AND SERVE AS A(N) _________.
AUTOMATIC FIRE ALARM.
FDNY CONNECTIONS SHALL BE FITTED WITH A LOWER CHECK VALVE. THIS WILL PREVENT ________ OF WATER.
BACKFLOW
A ________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS PARTIALLY OUT OF SERVICE.
BLUE
THE _________ PUMP INCREASES PRESSURE TO AN ACCEPTABLE LEVEL.
BOOSTER
IF A FIRE HAS BEEN COMPLETELY EXTINGUISHED, THE __________ OR THEIR REPRESENTATIVE MAY CLOSE THE CONTROL VALVE.
BUILDING OWNER
PRESSURE TANKS MAY BE SUPERVISED BY AN APPROVED ________ COMPANY WHICH MONITORS THE ENTIRE SPRINKLER SYSTEM.
CENTRAL STATION
THE __________ PUMP IS THE STANDARD PUMP CURRENTLY USED IN FIRE PROTECTION SYSTEMS.
CENTRIFUGAL
SOME METHODS TO PREVENT ICE INSIDE A GRAVITY TANK ARE _________.
CIRCULATED HOT WATER, STEAM, STEAM COILS, AND SUN HEAT
DRY PIPE VALVES ARE OF A ______ DESIGN.
CLAPPER
__________ VALVES ARE NO LONGER PERMITTED TO BE INSTALLED.
COLD WEATHER
THREE DEVICES USED TO TRIP PREACTION VALVES ARE FIXED TEMP DEVICES, RATE DEVICES, AND ___________ DEVICES.
COMBINATION
THE COF HOLDER SHALL KNOW THE LOCATION OF ALL SPRINKLER HEADS, CONTROL VALVES, SUPPLY LINES AND _________ ROOMS.
COMPACTOR
A SIGN INDICATING THE LOCATION OF ALL _______ SHALL BE KEPT IN THE COMPACTOR ROOM.
CONTROL VALVES
SPRINKLER HEADS EXPOSED TO ___________ CONDITIONS ARE OFTEN COVERED WITH A COAT OF WAX, OR LEAD.
CORROSIVE
GATE VALVES OF THE NON-INDICATING TYPE ARE CALLED ________.
CURB VALVES
_________ SPRINKLERS HAVE BEEN RECALLED.
CYCLING
__________ SHALL BE POSTED ON THE TAG INDICATING BOTH STATIC AND FLOW PRESSURES BEFORE AND AFTER.
DRAIN TEST RESULTS
________ SYSTEMS ARE INSTALLED WHERE A WET PIPE SYSTEM CANNOT BE HEATED TO PREVENT FREEZING.
DRY PIPE
A VERTICAL TURBINE PUMP IS USED TO DRAW WATER FROM A WELL TO ___________.
FILL A STORAGE TANK.
PRIMARY WATER PRESSURE TANKS SHALL BE EQUIPPED WITH TWO _____________.
HIGH AND LOW ALARM SYSTEMS
AUTOMATIC FIRE PUMPS ARE USUALLY NEEDED WHERE A ___________ MAY OCCUR IMMEDIATELY.
HIGH WATER DEMAND
AUTOMATIC BALL DRIP DEVICES SHALL BE INSTALLED IN THE _________ POSITION.
HORIZONTAL
PRIOR TO RETURNING A SYS. TO SERVICE, THE ___________ SHALL ENSURE THAT NECESSARY TESTS AND INSPECTIONS ARE CONDUCTED.
IMPAIRMENT COORDINATOR
THE BUILDING OWNER SHALL ASSIGN A(N) ____________ TO COMPLY WITH REQUIREMENTS.
IMPAIRMENT COORDINATOR
THE IMPAIRMENT COORDINATOR WILL NOTIFY THE ___________ CARRIER, CENTRAL STATION AND OCCUPANTS.
INSURANCE
GREEN TAGS WILL BE PLACED ON THE ____________.
MAIN CONTROL VALVE
THE COF NUMBER AND SIGNATURE OF COF HOLDER SHALL BE POSTED NEAR THE ____________.
MAIN CONTROL VALVE
WHEN ____________ ARE INSTALLED, THEY ARE USUALLY USED IN COMBINATION WITH A GRAVITY TANK OR A PRESSURE TANK.
MANUALLY ACTIVATED PUMPS
COF HOLDERS SHOULD MANUALLY ACTIVATE THE FIRE PUMPS IAW ___________.
MANUFACTURER INSTRUCTIONS
A _______ SHALL BE REQUIRED TO POST TAGS AT MAIN CONTROL VALVE AND ANY SECTIONAL VALVES.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR
A ________ CAN INSPECT, MAINTAIN, TEST, AND REPAIR ALL FIRE STANDPIPE AND SPRINKLER SYSTEMS.
MASTER FIRE SUPPRESSION PIPING CONTRACTOR (MFSPC)
__________ SHALL NOT BE USED TO FASTEN THE SYSTEM OR BUILDING ATTACHMENTS TO THE STRUCTURE.
NAILS
THE MAIN REASON A SPRINKLER SYS. SUPPLIED BY A GRAVITY TANK FAILS IS __________.
NOT ENOUGH WATER IN THE TANK
THE COF HOLDER SHALL CONDUCT AN INSPECTION OF THE ENTIRE SPRINKLER SYSTEM AT LEAST __________.
ONCE A MONTH
________ NOZZLES ARE USED FOR TRANSFORMER VAULTS AND OTHER HAZARDOUS AREAS.
OPEN-FIXED
WHAT DOES "OOS" STAND FOR?
OUT OF SERVICE
THE __________ IS RESPONSIBLE TO MAINTAIN SPRINKLER SYS. AND TO DETERMINE QUALIFICATIONS.
OWNER
FOR UNPLANNED REMOVAL FROM SERVICE, THE COF HOLDER SHALL IMMEDIATELY REPORT CONDITION TO THE ___________ AND THE FIRE DEPT.
OWNER OF THE BUILDING
_________ SYSTEMS ARE USUALLY FOUND IN BASEMENTS OR OTHER DIFFICULT TO REACH AREAS.
PERFORATED PIPE
MISSING OR DEFECTIVE PIPE HANGERS CAN CAUSE THE SYSTEM TO FAIL DUE TO ______________.
PIPE RUPTURE
IN A PREACTION SYSTEM, THE ___________ IS OPENED BEFORE THE SPRINKLER HEADS.
PREACTION VALVE
MUD, GRAVEL, AND LEAVES MAY CAUSE DAMAGE TO THE ___________.
PUMP
OOS SYSTEMS SHALL BE IDENTIFIED BY PLACING ________ AT FIRE DEPT. CONNECTIONS, SYS. CONTROL VALVES, AND FIRE COMMAND CENTER
TAGS
ON A POST INDICATOR VALVE (PIV), THE POSITION OF THE VALVE IS SHOWN THROUGH A ___________.
TELLTALE
EXTERIOR EXPOSURE SPRINKLERS USE OPEN SPRINKLER HEADS TO FORM A _______ ON THE WALL OF A BUILDING.
WATER CURTAIN
A _________ DISC OF 8-9 INCHES SHALL BE PLACED ON CONNECTIONS TO INDICATE THE SYSTEM IS FULLY OUT OF SERVICE.
WHITE
FDNY CONNECTIONS TO A COMBINED STANDPIPE/SPRINKLER SYSTEM SHALL BE PAINTED ___________.
YELLOW