410A test

Ace your homework & exams now with Quizwiz!

The temperature glide for R-410A is less than ________ degrees Fahrenheit over air conditioning and refrigerating operating ranges.

0.3

R-410A cylinders should not be allowed to get warmer than?

125 degree Fahrenheit

HCFC-22 is scheduled for total phaseout in the year?

2020

Manifold low side gauge for R-410A refrigerant must range to?

250 psig with 500 psig to 550 psig retard

A full nitrogen cylinder has a pressure of approx?

2500 psig

Both suction and discharge pressures of R-410A systems are ________ than R-22

40%-70% higher

The low pressure control on R-410A systems will open at?

50 psig

Compressor internal pressure relief (IPR) settings for R-410A systems are?

550 psig to 625 psig

When installing a liquid line filter drier on a R-410A system, be certain that it has a pressure rating of at least:

600 psig

R-410A systems use a high pressure switch that will open at approximately?

610 psig plus or minus 10 psig.

Manifold high side gauge for R-410A refrigerant must range to?

800 psig

Service hoses used with R-410A equipment must be rated to?

800 psig

Temperature glide refers to

A range of condensing and evaporating temperatures for one pressure.

Compression ratio is calculated as?

Absolute discharge pressure divided by absolute suction pressure.

When charging an operating R410A system with liquid refrigerant

Be sure it is throttled into the low side to avoid compressor damage

Polyol Ester (POE)

Can be irritating to the skin, is hygroscopic and has improved heat transfer characteristics over mineral oils.

Near- azeotropic blends fractionation may

Cause the components to leak at uneven rates due to varying vapor pressures.

To remove moisture from polyol ester (POE) lubricant

Change filter/drier and evacuate to 500 microns

Recovery cylinders used with R-410A must have DOT rating of?

DOT 4BA 400 or DOT 4BW 400

Subcooled liquid in the receiver may ________ subcooling, depending on surrounding conditions.

Either gain or lose.

Blends that have fractionated, depending on the constituent make-up, may become

Flammable

A leak detector capable of sensing ________ is needed when working with R-410A

HFC

R-410A;

Is more efficient than R-22, using less energy, therefore it has a lower TEWI

Which of the following statements is true of R-407C? R-407C is a single component refrigerant It is classified as an azeotropic refrigerant It is a binary blend or It may separate (fractionate) into its component refrigerants.

It may separate (fractionate) into its component refrigerants.

When a blend is zeotropic or near-azeotropic (NARM)

It should be transferred from cylinders as a liquid to avoid fractionation.

When a blend is zeotropic or near-azeotropic (NARM)

Leaks may cause a change in composition of the blend, it will have temperature glide, and it can fractionate.

Because of its higher vapor heat capacity, the discharge temperature of R-410A is ________ than R-22

Lower

All service equipment used with R-410A

Must be rated for the higher pressures.

Systems containing R-410A ________ lubricant

Polyol ester

Before working on any electrical circuit

Power should be shut off, locked and tagged at the distribution panel.

It has a high temperature glide is true about what refrigerant?

R-407C

What refrigerant is a good choice for retrofitting an R-22 air conditioning system?

R-407C

The evaporator or indoor coil should be ________ when changing out of existing R-22 equipment to a new R410A system

Replaced with one that meets UL approved design and service pressure rating if 235 psig

The cylinder color code for R-410A is:

Rose

To avoid fractionation, blended refrigerants:

Should be charged in the liquid phase

The flow area of a R-410A metering device is?

Smaller than that of a R-22 metering device.

When charging a R-410A system that uses a thermostatic expansion valve, proper charge can be determined by measuring?

Subcooling

When charging a R-410A system that uses a capillary tube or fixed metering device, proper charge can be determined by measuring?

Superheat

R-410A is also known as?

Suva 410A, AZ-20 and Puron

A system using R-410A refrigerant has bubbles in the sight glass. Technician A says that the system must be low on refrigerant. Technician B says that the bubbles could be caused by the blended refrigerant flashing in the increased volume of the sight glass. Who is correct?

Technician B

The closer the blend comes to being a true azeotrope,

The less the temperature glide it will have.

If a R-410A system develops a leak:

The remaining refrigerant is ok to use because R-410A has a low fractionation rate

Cylinders containing R-410A that are equipped with dip tubes,

To allow liquid to be removed with the cylinder upright.

When calculating subcooling with R-407C

Use the bubble point value only.

When calculating superheat with R-407C

Use the dew point value only.

If a large leak of refrigerant occurs in an enclosed area, you should?

Vacate and ventilate the area

When handling refrigerants, technicians should?

Wear approved eye protection and gloves.

A true azeotropic blend

Will not fractionate, has no temperature glide, qnd behaves as a single component refrigerant.

Manufacturers of equipment using R-410A have redesigned their compressors

With increased wall thickness

Nitrogen cylinders should only be moved

With the protective cap in place.


Related study sets

Ricci Chapter 12 - Test Bank - 4th Edition

View Set

NURS 321 Practice Questions for Quiz #1

View Set

Lord of the Flies (chapters 1-4)

View Set