Chapter 10

Ace your homework & exams now with Quizwiz!

What size outlet box is needed for one 12/2 that terminates on a switch and one 12-3 that terminates on a receptacle. The box has 2 cable clamps (internal).

4 x 2 1/8

Table 314.16(A) does not take into consideration the volume of switches and receptacles, True False

True

How many 14 AWG conductors can be installed in a 4 x 1 1/2 square box with a plaster ring marked 3.60 cu inches? The box already contains two duplex receptacles , five 14 AWG wires and two EGC.

4

What is the minimum size box for nine 14 AWG conductors.

4" x 2 1/8

How many 10 AWG conductors permitted in a 4 x 1 1/2 square box

8


Related study sets

Practice Questions - Chapters 17, 18, 19, and 20 - RESPIRATORY

View Set

Marketing Exam 2 Review Chapter 8&9

View Set

Power, Protest, and Change Test (blonde davis) 12/04/17

View Set

Chapter 11 Inflammation and Healing

View Set