Electrical Level 3 Module 1 Load Calculations and Branch Feeder Circuits

Ace your homework & exams now with Quizwiz!

What is the required circuit ampacity for a noncontinuous, three-phase load of 6kW at 208V?

16.65A

What is the total ampacity for a 120V branch circuit consisting of four duplex receptacles rated noncontinuous duty and six duplex receptacles rated continuous duty?

17.25A

What is the load center distance for a 208V, four-wire, three-phase branch circuit with fixed noncontinuous loads from the source of 60A at 45', 40A at 60', 30A at 75', and 25A at 100'

63.55'

What is the required circuit ampacity of a noncontinuous, single-phase load of 8.5kW at 277V?

30.69A

For resistance welders, the rating for the overcurrent protection device should not exceed what percentage of the primary current rating of the welder?

300%

What is the demand load for one household range with a nameplate rating of 11.75kW, 240V, 1Ø?

8kW

What is the total load required by the NEC® for two appliance branch circuits plus a laundry branch circuit?

4,500VA

The allowable ampacity for eleven No. 12 THHN copper conductors in a cable must be adjusted by

50%

What is the motor full-load current for a motor with a nameplate rating of 50hp, 460V, 3Ø?

65A

The load for 10' of multi-outlet assembly used to supply several loads simultaneously is

1,800VA

The maximum size dual-element fuse for a 40hp, 3Ø, 460V motor with a Design Letter D is

100A

What is the load center length for a branch circuit with noncontinuous loads of 20A at 60' and 50A at 125'?

106.43'

Show window lighting is calculated at 200VA per linear foot plus

125%

What is the load for 55' of show window using the linear foot method?

13,750VA

What is the lighting load on a 120V circuit for six 100W incandescent lights and four fluorescent fixtures with a ballast rating of 1.5A, all operating continuously for 8 hours per day? 13.75A

13.75A

Air conditioning overcurrent protective devices can never exceed what percentage of the motor-rated load current or the branch circuit selection current (whichever is greater)?

225%

According to the NEC®, the ampacity of branch circuit conductors must be derated when there are more than how many current-carrying conductors in a raceway?

3

For a given load and length, the branch circuit voltage drop should not exceed

3%

What is the current-carrying capacity for No. 6 THWN aluminum conductors in conduit run through an ambient temperature of 38°C?

44 Amps

What is the voltage drop for a 120V, single-phase, two-wire branch circuit, 100' long, using copper conductors of 6,530 circular mils with a noncontinuous load of 13A? 5.14V

5.14V

Continuous loads are calculated at what percentage of the maximum current rating of the overcurrent device?

80%

What is the load center length for a branch circuit consisting of noncontinuous loads of 125A at 80', 75A at 110', and 50A at 100'?

93'

When connected to 15A or 20A multi-outlet general-purpose branch circuits, which of the following shall not exceed 50% of the branch circuit ampere rating?

Fastened-in-place utilization equipment

What size copper conductor would be required for a 240V, 1Ø circuit supplying a noncontinuous load of 27.5A at a distance of 145', and a maximum voltage drop of 3%?

No. 10

Conductors must be derated when installed in conduit

on or above rooftops