FLS Main

Ace your homework & exams now with Quizwiz!

38. PLFA cables passing through a floor or a wall, shall be in metal raceway or rigid nonmetallic conduit to a height of ______ feet. a. 3 c. 7 b. 5 d. 10

c. 7 REF: (NEC) 760.130(B)(2)

4. A lobby smoke detector shall be located on the ceiling within ______ feet of the centerline of each elevator door within the elevator bank under control of the detector. a. 5 b. 11 c. 15 d. 21

d. 21 REF: (NFPA 72) 21.3.5

7. Solve for total resistance in a series circuit where R1=90 Ohms, R2= 20 Ohms, R3=55 Ohms and R4=100 Ohms. a. 120 Ohms b. 195 Ohms c. 21 Ohms d. 265 Ohms

d. 265 Ohms

15. Wall mounted telephone appliances or related jacks shall not be less than ______ in. and not more than __________ in. above floor level with clear access to the applicance that is at least ______ in. wide. a. 66, 39, 40 b. 30, 66, 36 c. 30, 60, 30 d. 36, 66, 30

d. 36, 66, 30 REF: (NFPA 72) 24.8.17

3. The current flowing through a 72 ohm resistor is measured and found to be 0.5 A. What is the voltage drop at the resistor? a. 9V b. 90V c. 360V d. 36V

d. 36V

66. Non-power-limited fire alarm circuit conductors shall have insulation suitable for ________ a. 120 Volts c. 240 Volts b. 300 Volts d. 600 Volts

d. 600 Volts REF: (NEC) 760.49(B)

37. A nonpower-limited fire alarm circuit output voltage shall not be more than _____________ volts nominal. a. 24ac c. 120ac b. 24dc d. 600ac

d. 600ac REF: (NEC) 760.41(A)

97. NPLFA and PLFA wiring passing through a floor or a wall shall be ran in metal raceways or rigid nonmetallic conduit to a height of ________ feet above the floor, unless adequate protection can be afforded by building construction. a. 2 b. 4 c. 5 d. 7

d. 7 REF: (NEC) 760.53(A)(2)

79. What is the minimum size equipment grounding conductor when the rating of the overcurrent device is rated at 60 Amperes? a. 10 AWG Aluminum c. 6 AWG Copper b. 8 AWG Copper d. 8 AWG Aluminum

d. 8 AWG Aluminum REF: (NEC) 250.122

57. Wall mounted visible appliances shall be mounted such that the entire lens is not less than ______ and not greater than _____ above the finished floor. a. 40", 50" c. 80", 90" b. 4", 12" d. 80", 96"

d. 80", 96" REF: (NFPA 72) 18.5.5.1

74. What color shall a grounded conductor 6 AWG or smaller be? a. Continuous white b. Continuous gray c. Green d. A and B e. B and C

d. A and B REF: (NEC) 200.6(A)

64. For a Central Station, which of the following elements of service is not required? a. Retransmission of signals c. Runner service b. Testing and maintenance d. All are required

d. All are required REF: (NFPA 72) 26.3.2

22. Reacceptance testing shall be performed after: a. Added or deleted system components b. Any modification, repair or adjustment to system hardware or wiring. c. Any change to site-specific software d. All of the above

d. All of the above REF: (NFPA 72) 14.4.2

100. When changes are made to site specific software, which of the following shall apply? a. Changes shall be 100% tested c. A revised record of completion shall be performed b. 10 percent of initiating devices shall be tested d. All of the above

d. All of the above REF: (NFPA 72) 14.4.2.4

67. A supervising station fire alarm system is a protected premises that has signals sent to ________. a. Central Station c. Remote Station b. Proprietary Station d. All of the above

d. All of the above REF: (NFPA 72) 3.3.280

55. Voice evacuation messages shall be preceded and followed by a minimum of _____ cycles of the emergency evacuation signal. a. 2 b. 3 c. 4 d. 5

a. 2 REF: (NFPA 72) 24.3.6.4

49. If heat detectors are used to shut down elevator power prior to sprinkler operation, they shall be placed within _______ feet of each sprinkler head. a. 2 b. 3 c. 4 d. 5

a. 2 REF: (NFPA 72) 21.4.2

11. The rating of the overcurrent protection of a piece of equipment is 100 amps. What is the minimum size copper equipment grounding conductor for the grounding of the raceway and equipment? a. #8 AWG b. #10 AWG c. #12 AWG d. #14 AWG

a. #8 AWG REF: (NEC) 250.122 Found under Tables, Grounding , AC Equipment

50. According to the NFPA 72, a 20 foot by 20 foot room or area with a 10 foot ceiling is best covered by a(n) _________ cd wall mount visible notification appliance. a. 15 c. 60 b. 30 d. 75

a. 15 REF: (NFPA 72) 18.5.5.4.1(b)

51. When locating smoke detectors and wall partitions extend to within ________ of the ceiling height, the spaces separated by the partitions shall be considered separate rooms. a. 15 percent c. 18 percent b. 15 inches d. 18 inches

a. 15 percent REF: (NFPA 72) 17.5.2

83. The secondary power supply shall have capacity to operate the fire alarm system in non-alarm condition for ____________ hours and at the end of that period be capable of operating all alarm NAC's for a duration of _________ minutes. a. 24, 5 c. 48, 5 b. 12. 5 d. 8. 3

a. 24, 5 REF: (NFPA 72) 10.6.7.2.1

71. A three branch parallel circuit where each branch resistance is 90 ohms, what is the total resistance? a. 30 Ohms c. 270 Ohms b. 90 Ohms d. cannot be determined with the information provided

a. 30 Ohms

29. The definition of solid joist construction is solid projections, whether structural or not, extending downward from the ceiling, which are more than ___________________ in depth and are spaced on ____________ centers or less. a. 4 inches, 3 foot b. 3 inches, 4 foot c. 12 inches, 3 foot d. 12 inches, 12 foot

a. 4 inches, 3 foot REF: (NFPA 72) 3.3.38.4

59. The operational portion of a manual fire alarm box shall be not less than _______ and not more than ______ above floor level. a. 42 inches, 48 inches c. 32 inches, 60 inches b. 3 feet, 5 feet d. 4 inches, 12 inches

a. 42 inches, 48 inches REF: (NFPA 72) 17.14.5

80. The number of waterflow alarm-initiating devices permitted to be connected to a single initiating device circuit shall not exceed __________________. a. 5 c. 15 b. 10 d. 20

a. 5 REF: (NFPA 72) 23.8.5.5.2

88. Manual fire alarm boxes (pull stations) shall be located within _________________ of the exit doorway opening at each exit on each floor. a. 5 feet c. 15 feet b. 10 feet d. 30 feet

a. 5 feet REF: (NFPA 72) 17.14.8.4

8. Solve for total resistance of a circuit with a 20 Ohm, 20 Ohm, and 20 Ohm resistors in parallel. a. 6.67 Ohms b. 15 Ohms c. 60 Ohms d. 8k Ohms

a. 6.67 Ohms

47. Approved device is something that is acceptable to _______. a. Authority Having Jurisdiction c. Factory Mutual b. United Laboratories d. The Project Manager

a. Authority Having Jurisdiction REF: (NFPA 72) 3.2.1

73. Which circuit pathway class designation does not include a redundant path? a. Class B c. Class C b. Class A d. Class X

a. Class B REF: (NFPA 72) 12.3 (1)

58. A watertight and dust tight box connector that also provides a positive ground, is commonly referred to as a _________. a. Myers Hub c. Jake b. Straight Squeeze Connector d. Set screw connector

a. Myers Hub

82. Video image smoke and flame detectors shall be inspected, tested and maintained ____________. a. according to manufacturer's instructions c. annually b. semi-annually d. none of the above

a. according to manufacturer's instructions REF: (NFPA 72) 14.4.3.3

85. Where heat detectors are used to shut down elevators power prior to sprinkler operation, the detector shall have both a_________ rating and a___________ sensitivity as compared to the sprinkler. a. lower temperature, higher sensitivity c. higher temperature, lower sensitivity b. higher temperature, higher sensitivity d. lower temperature, lower sensitivity

a. lower temperature, higher sensitivity REF: (NFPA 72) 21.4.1

56. When installing heat detectors in high ceiling areas, which value would you multiply the listed spacing by, if the ceiling height was 15 feet? a. 0.7 c. 0.71 b. 0.77 d. 0.7(S)

b. 0.77 REF: (NFPA 72) 17.6.3.5.1

20. The minimum size of a copper equipment grounding conductor required for equipment connected to a 40 amp circuit is ______ AWG. a. 6 b. 10 c. 12 d. 16

b. 10 REF: (NEC) Table 250.122

63. The duration from when an initiation device activates and the actuation of alarm notification appliances shall occur within _____ seconds. a. 5 c. 20 b. 10 d. 60

b. 10 REF: (NFPA 72) 10.11.1

13. An average ambient sound level greater than ________dBa shall require the use of a visible signal appliance. a. 100 b. 105 c. 110 d. 115

b. 105 REF: (NFPA 72) 18.4.1.1

46. The total sound pressure level produced by combining the ambient sound pressure level with all audible signaling operating shall not exceed ________ dBa at the minimum hearing distance. a. 100 c. 105 b. 110 d. 120

b. 110 REF: (NFPA 72) 18.4.1.2

42. Visible notification appliances located within 18 inches from the ceiling and within 16 feet of a sleeping occupant shall have an intensity of _____. a. 177 dB c. 110 cd b. 177 cd d. 110 dB

b. 177 cd REF: (NFPA 72) 18.5.5.7.2

34. The smallest conductor allowed for a non-power-limited fire protective signaling circuit is ____________ copper. a. 16 AWG c. 20 AWG b. 18 AWG d. 22 AWG

b. 18 AWG REF: (NEC) 760.49(A) & 760.142

39. Power-limited fire alarm circuit conductors shall be at least ________ inches from conductors of any electric light, where not installed in enclosures. a. 1 c. 3 b. 2 d. 4

b. 2 REF: (NEC) 760.136(G)

61. A coded alarm signal shall consist of not less than ______ complete rounds of the number transmitted. a. 2 c. 4 b. 3 d. 5

b. 3 REF: (NFPA 72) 10.11.4

14. A listed relay or other listed appliance connected to the fire alarm system used to initiate control of the protected premises fire safety system for emergency control functions shall be located within _______ feet of the controlled circuit or appliance. a. 2 b. 3 c. 5 d. 10

b. 3 REF: (NFPA 72) 21.2.4

10. Documentation indicating code compliance for a Central Station Service, must be installed within __________________________ ft. of the main fire alarm system controls. a. 2 b. 3 c. 5 d. 6

b. 3 REF: (NFPA 72) 26.3.4.3

54. In Annex A smoke detectors should not be located in a direct airflow nor closer than ________. a. 2 feet from the air supply diffuser or return opening. b. 3 feet from the air supply diffuser or air return opening c. 6 feet from any air source d. 7 times the listed spacing from the diffuser or air return opening.

b. 3 feet from the air supply diffuser or air return opening REF: (NFPA 72) A17.7.4.1

52. In the absence of specific performance-based design criteria, smoke detectors shall be permitted to be located using _____ spacing. a. 20 feet c. 40 feet b. 30 feet d. 50 feet

b. 30 feet REF: (NFPA 72) 17.7.3.2.3.1

24. A voltage of 0.48 V can also be expressed as: a. 4800 mV b. 480 mV c. 48 mV d. 4.8 mV

b. 480 mV

28. Nonpower-limited fire alarm circuits shall have overcurrent protection not to exceed _______________________ amps for No. 18 conductors. a. 5 b. 7 c. 10 d. 12

b. 7 REF: (NEC) 760.43

53. Identify the Class of the following hazard: when combustible dust on electrical equipment could cause abnormal operation or failure of electrical equipment. a. Class I c. Class III b. Class II d. None of the above

b. Class II REF: (NEC) 502.1 or 500.5(C)(1) or (2)

26. Class II locations are those that are hazardous because of the presence of _____. a. chemicals b. combustible dust c. cleaning supplies d. none of the above

b. combustible dust REF: (NEC) 502.1, 500.5(C)

19. When the resistance is increased, the current ________. a. increases b. decreases c. stays the same d. is shorted

b. decreases

86. The proper method of testing a mechanical waterflow device of a wet-pipe system shall be performed by _________. a. setting off an existing sprinkler head and diverting the water to a holding container large enough to contain 200 gallons of water. b. flowing water through an inspector's test connection indicating the flow of water equal to that of a single sprinkler head d. None of the above

b. flowing water through an inspector's test connection indicating the flow of water equal to that of a single sprinkler head REF: (NFPA 72) 14.4.3.2

96. When using a volt-ohm-meter (VOM) to measure voltage of a notification device, the meter leads should be ________. a. in series (in line) with the device c. one lead on the positive terminal and the other lead on the conduit electrical ground. b. in parallel (across) with the device

b. in parallel (across) with the device

41. The purpose of Class A fire alarm circuit separation is to ________. a. increase the complexity of the system c. prevent cross talk b. prevent a single event from disabling the circuit d. prevent RFI

b. prevent a single event from disabling the circuit REF: (NFPA 72) 12.3.1

81. Magnetic door holders that allow doors to close upon loss of operating power _______ required to have a secondary power source. a. shall be c. are b. shall not be d. , with sufficient capacity to operate for a duration of 2 hours, shall be

b. shall not be REF: (NFPA 72) 21.8.4

78. If installing a combination audible/visible appliance, the location of the installed appliance shall be determined by _________. a. the location requirement of an audible notification appliance b. the location requirements of a visible notification appliance c. the location of audible notification appliances for wide area signaling d. None of the above

b. the location requirements of a visible notification appliance REF: (NFPA 72) 18.4.8.3 then 18.5.5

16. For smooth ceilings, all points on the ceiling shall have a heat detector within a distance equal to _______ times the selected spacing. a. 0.5 b. 0.8 c. 0.7 d. 0.6

c. 0.7 REF: (NFPA 72) 17.6.3.1.1(2)

89. What effective intensity would be needed when installing one visible appliance on a wall in a 54x54 foot room? a. 30cd c. 110 cd b. 94cd d. 177 cd

c. 110 cd REF: (NFPA 72) 18.5.5.4.1.A

40. Visible notification applicances shall be located not more than _______ feet from end of the corridor with a separation not greater than ________ feet between appliances. a. 100, 15 c. 15, 100 b. 30, 100 d. 15, 30

c. 15, 100 REF: (NFPA 72) 18.5.5.5.5

30. The maximum number of No. 10 THHN copper conductors permitted to be installed in a 4 11/16 x 2 1/8 inch square metal box is: a. 8 b. 14 c. 16 d. 18

c. 16 REF: (NEC) 314.16(A)

5. When buried in earth below 50 mm thick cinder fill, intermediate metal conduit shall be covered _______ in. _______mm from the top. a. 12, 300 b. 6, 150 c. 18, 450 d. 24, 600

c. 18, 450 REF: (NEC) 342.10(C)

69. When you install two 12 Volt batteries in series, the total voltage will be _____. a. 6 Volts c. 24 Volts b. 12 Volts

c. 24 Volts

76. After fully charged batteries have been subject to a single discharge, the batteries shall be recharged within ______ hours. a. 12 c. 48 b. 24 d. 72

c. 48 REF: (NFPA 72) 10.6.10.3.2

17. A bonding jumper not smaller than _____ AWG copper or equivalent shall be connected between the communications grounding electrode and the power grounding electrode at the building structure serves where separate electrodes are used. a. 12 b. 10 c. 6 d. 4

c. 6 REF: (NEC) 800.100(D)

23. Initiation of the alarm signal shall occur within ________ of waterflow of a sprinkler head of the smallest orifice size installed in the system. Movement of water due to waste, surges, or variable pressure shall not be indicated. a. 120 sec b. 30 sec c. 90 sec d. 10 sec

c. 90 sec REF: (NFPA 72) 17.12.2

32. Class ___________ circuits are considered to be more reliable than class ___________ because they remain fully operational during the occurence of a single open or a single ground fault. a. B,A c. A,B b. 2,1 d. 1,2

c. A,B REF: (NFPA 72) 12.3.1-2

1. Which cable is permitted to be substituted for FPLR cable? a. CMG c. CMR b. CM d. none of the above

c. CMR REF: (NEC) 760.154(D)

77. Identify the Class of the following hazardous location: a location with the presence of easilty ignitable fibers or materials producing combustible flyings are handled, manufactured, or used but are not likely to be suspended in air in sufficient quantities to ignite. a. Class I c. Class III b. Class II d. None of the above

c. Class III REF: (NEC) 500.5(D)

98. A DACT is a ____________. a. Digital Alarm Computer Technology b. Digital Alarm Communication Technology c. Digital Alarm Communicator Transmitter d. Digital Alarm Computer Transmitter

c. Digital Alarm Communicator Transmitter REF: (NFPA 72) 3.3.70

87. How should a voltmeter be connected in a DC circuit to read the voltage drop of a load? a. In series with the load c. In parallel with the load b. In parallel with the source d. In series with the source

c. In parallel with the load

84. Who is required to fill out the majority of the Record of Completion when your fire alarm system is finished? a. Owner c. Qualified Installer b. AHJ d. Supervising Station

c. Qualified Installer REF: (NFPA 72) 7.5.6.2

94. What type of signal will a valve tamper switch produce when actuated? a. Alarm c. Supervisory b. Trouble d. Fault

c. Supervisory REF: (NFPA 72) 23.8.5.8.1 & 17.16.1

93. Spot type heat-sensing fire detectors shall be located on the vertical wall ______. a. 4 inches from the ceiling c. Within 4 inches to 12 inches from the ceiling b. 12 inches from the ceiling d. Within 6 inches and not more than 12 inches ceiling

c. Within 4 inches to 12 inches from the ceiling REF: (NFPA 72) 17.6.3.1.3.1

12. The connection of a grounding electrode conductor to a grounding electrode shall be made in a manner that will ensure an _______ grounding path. a. permanent b. efficient c. effective d. adequate

c. effective REF: (NEC) 250.4 & 250.68(B)

6. Chapter 17, in reference to heat detectors, defines the area which a detector shall not be installed on the ceiling and its connected vertical sidewall as ________________. a. 12 inches in from the wall and 4 inches down from the ceiling b. 4 inches in from the wall and 12 inches down from the ceiling c. less than 4 inches from the sidewall d. from 4 inches to 12 inches from the ceiling

c. less than 4 inches from the sidewall REF: (NFPA 72) 17.6.3.1.3.1

18. Under what type of coverage referred to in chapter 17 is the spacing requirements of detectors waived? a. selective coverage b. partial coverage c. non-required coverage d. total coverage

c. non-required coverage REF: (NFPA 72) 17.5.3.3.1 Coverage, detector

99. What color code color temperature classification is used for an extra high heat sensing fire detector? a. blue c. red b. white d. green

c. red REF: (NFPA 72) 17.6.2.1

65. According to Chapter 14 (2013 NFPA 72), sealed lead-acid batteries shall be visually inspected at initial installation or reacceptance and then ___________. a. monthly c. semi-annually b. quarterly d. annually

c. semi-annually REF: (NFPA 72) 14.3.1

45. Waterflow switches used with fire alarm systems must be tested ______. a. monthly c. semi-annually b. quarterly d. annually

c. semi-annually REF: (NFPA 72) 14.4.3.2

91. A supervisory valve switch shall be tested ___________. a. monthly c. semi-annually b. quarterly d. annually

c. semi-annually REF: (NFPA 72) 14.4.3.2

75. When required to be monitored and a building fire alarm system is installed, the activation of a open circuit on the fire suppression system shall annunciate a _______ signal at the FACU. a. trouble c. supervisory b. alarm d. b or c

c. supervisory REF: (NFPA 72) 23.8.5.11.1, 23.8.5.8.1 Supervisory: This fire alarm signal type is related to the supervision of certain field components. As an example the opening and the closing of the Sprinkler valve. Trouble: This fire alarm signal is typical of a device malfunctions.

35. For restorable fixed temperature, spot type heat detectors, _____________ or more detectors shall be tested on each initiating circuit annually. Different detectors shall be tested each year. Within ________ year, each detector shall have been tested. a, five, five c. two, five b. one, two d. two, four

c. two, five REF: (NFPA 72) 14.4.4.5(1-4)

21. In Chapter 17, referencing heat detectors irregular areas, more careful plannng is needed to make certain that no spot on the ceiling is more than ______ away from a detector. a. 1/2 the listed spacing b. 2/3 the listed spacing c. 0.5 x the listed spacing d. 0.7 x the listed spacing

d. 0.7 x the listed spacing REF: (NFPA 72) 17.6.3.1.2

68. A copper equipment grounding conductor for a 40 amp rated circuit shall be _________. a. 12 AWG c. 8AWG b. 14 AWG d. 10 AWG

d. 10 AWG REF: (NEC) 250.122

60. Trouble signals and their restoration to normal shall be indicted within _____ seconds. a. 10 c. 120 b. 60 d. 200

d. 200 REF: (NFPA 72) 10.14.1

43. Additional manual fire alarm boxes (pull stations) shall be provided so that the travel distance to nearest location does not exceed _____ feet on the same floor. a. 50 c. 150 b. 100 d. 200

d. 200 REF: (NFPA 72) 17.14.8.5

48. Smoke and heat detectors shall not be required in combustible blind spaces if which of the following conditions exists: a. Where the ceiling is attached directly to the underside of the supporting beams of a combustible roof or floor deck. b. Where the concealed space is entirely filled with a noncombustible insulation. c. Where there are small concealed spaces over rooms, providing any space in question does not exceed 50 feet square in area. d. All of the above.

d. All of the above. REF: (NFPA 72) 17.5.3.1.2

95. Installation personnel shall have which qualification? a. Factory trained and certified for the system being installed b. Certified by a nationally recognized fire certification acceptable to the AHJ c. Registered, licensed, or certified by a state or local authority d. Any of the above

d. Any of the above REF: (NFPA 72) 10.5.2.3

92. What cable types can be substituted for a FPLR cable? a. CMG, CM, FPL c. FPL b. CMP, FPL d. CMR, CMP, FPLP

d. CMR, CMP, FPLP REF: (NEC) 760.154(D)

36. Ohm's Law may be interpreted for purposes of calculation as: a. I=VxR c. V=R/I b. V=I/R d. I=V/R

d. I=V/R

9. What kind of raceway is not permitted in a hospital patient care areas for electrical branch circuits? a. MC b. RMC c. IMC d. Nonmetallic Raceway

d. Nonmetallic Raceway REF: (NEC) 517.30(C)(3)(2)

33. In Chapter 26 who is responsible for conspicuously indicating that the fire alarm system providing service at the protected premises, complies with all the requirements of NFPA 72? a. Building owner c. Central station b. Service technician d. Prime contractor

d. Prime contractor REF: (NFPA 72) 26.3.4

72. Smoke detectors shall not be installed in elevator hoistways unless _____________. a. the hoistway is sprinklered c. there is a heat detector also installed b. to activate smoke relief equipment d. a and b

d. a and b REF: (NFPA 72) 21.3.6

90. Equipment grounding conductors shall be _________. a. permitted to be bare c. insulated b. covered d. any of the above

d. any of the above REF: (NEC) 250.118(1)

25. When two or more smoke alarms are used to provide a fire warning function in a single or multiple dwelling, they shall __________. a. not be from the same manufacturer b. be synced to flash at the same rate c. be opposite colors d. be arranged so that an alarm causes all alarms to sound within the dwelling

d. be arranged so that an alarm causes all alarms to sound within the dwelling REF: (NFPA 72) 29.5.2.1.1

27. In a parallel circuit, current from the power supply (total current) is ______________. a. the product of the current through each branch b. less than the current through one branch c. the same through all branches d. equal to the sum of the current of each branch

d. equal to the sum of the current of each branch

2. Smoke detectors shall not be installed in elevator hoistways unless the ___________. a. building is protected by a smoke control system b. elevator machine room is located above the hoistway c. hoistway is less than 3 stories height d. hoistway is sprinklered or installed to activate elevator hoistway smoke relief equipment

d. hoistway is sprinklered or installed to activate elevator hoistway smoke relief equipment REF: (NFPA 72) 21.3.6

70. A series circuit has a power source of 24 volts AC. The circuit has 3 resistors, R1 = 100 ohms, R2 = 200 ohms and R3 = 100 ohms. The current in the circuit ____________. a. cannot be determined with AC voltage c. is higher in R1 and R3 than in R2b. b. is higher in R2 than in R1 or R3 d. is the same in R1, R2 and R3

d. is the same in R1, R2 and R3

44. A branch circuit powering a power-limited fire alarm system can be supplied by ______. a. ground fault circuit interrupters c. both ground fault interrupters and arc fault interrupters b. arc fault interrupters d. none of the above

d. none of the above REF: (NEC) 760.121(B)

62. When mechanically protecting a notification device and guards, covers or lenses are employed, they _________. a. shall be rated for a seismic zone four c. shall be made of clear solid plastic material b. shall be large enough to cover two devices d. shall be listed for use with the appliance

d. shall be listed for use with the appliance REF: (NFPA 72) 18.3.4.2

31. A ground fault is a(an) ____________ electrical connection between an ungrounded (hot) conductor and metallic enclosure, metallic raceways, metallic equipment or earth. a. deliberate c. designed b. intentional d. unintentional

d. unintentional REF: (NEC) Article 100 Definitions


Related study sets

Marketing Research OSU, MARKETING RESEARCH FINAL EXAM REVIEW (final)

View Set

Public health 203 midterm quiz questions

View Set

Personality 3: Phenomenological-Humanisitic, Social-Cognitive, Integration as a Whole

View Set

Chapter 1: Overview of Database Concepts

View Set

Prep U Chapter 11: The Healthcare delivery system

View Set