Module 4 test
The resistance of switch gear should be checked using
1000 V Mehgometer
When performing thermographic surverys, a major deficiency is indicated by a gradient of
16 degrees c
Wires from the ground fault relay to the trip coil should be no longer than
50 ft
The standard output voltage of potential transformer is 120 V or
69.3 Volts
Which of the following abbreviation is used on electrical drawings to represent on oscilloscope
CRO
Field marking of service equipment shall include the
Date the fault current calculation was performed
Substation transformers used to reduce the voltages and currents in the primary circuits to the levels used in metering equipment are known as
Instrument transformers
A test that can be used to detect loose connection is an
Insulation resistance test
The continuous current that a circuit breaker can carry without exceeding a standard temperature rise is known as the
Overload rating
The basic purpose of switchgear is to provide a means of switching or disconnect power system apparatus and
Provide power system protection by automatically isolating fault components
Busbars are typically made of
Silver plated or tin plated copper or tin plated aluminum
The maximum 60 Hz voltage that can be applied to a switch for one minute
Withstand rating
The three sections of switchgear enclosures are the front section, the Bus section, and the
cable or termination section
A type of oil filled current transformer is the
donut type
According to the NEC, neutral conductors size no.6 and smaller must have a continuous marking of white or
gray
The three basic methods of sensing ground faults are zero sequence, residual, and
ground return
Thermographic surveys are conducted using
infrared imager